Halishahar Tank Transmission Pipeline: The design head is 34m.

Considering safety and water


hammering effect, we should double the design head i.e. maximum surge pressure in the pipeline is
(34mx2) =68m=666,682N/m2.

At the blind end of the header pipe, total pressure will be = πX(0.6)2X68=754,000N.

Compressive Load will occur at the supporting H-Beam fixed at 60 0 angle = 754,000N/cos300=870,645N.

Calculation Formulas:

Calculation:
Now let us consider 1000mm length UB203x133x30 as inclined support against backpressure created by
water hammer inside the header pipe. This support shall make 60 0 with the vertical blind flange. Both
ends of the support shall be restrained according to the drawings.
I-Section Details Input:

h1 187.6 mm
h2 9.6 mm
h3 9.6 mm
b1 6.4 mm
b2 133.9 mm
b3 133.9 mm
d1 98.6 mm
d2 98.6 mm
L= 1000 mm

Calculation:
A1= 1200.64 mm2
A2= 1285.44 mm2
A3= 1285.44 mm2
A= 3771.52 mm2
Ixx= 2.85E+07 mm4
Iyy= 3.85E+06 mm4

Rxx= 86.98 mm

Ryy= 31.93 mm

Force according to Euler Critical Load


Formula:

F= 133,315,532.19 N

Safety Factor= 153.12 Designed I-Section is OK

Young’s modulus E = 210 GN/m2


Yield Strength Sy = 500 MN/m2
End fix Factor for both end fixed K = 0.65