One-Way and Two-Way Slab Design Guide
One-Way and Two-Way Slab Design Guide
Given:
live load: 4.8 kPa fc' = 28 mPa
fy = 420 mPa L: 2.7 m
floor finish: 1.1 kPa f = 0.9 cover = 20 mm
ceiling finish: 0.24 kPa f 1
= 0.85
mech. duct allowance: 0.25 kPa conc. unit wt.= 23.5 kN/m3
electrical load: 0 kPa
partition load: 0 kPa using 12 mm rebars
miscellaneous load: 1 kPa Ad = 113.10 mm2
Solution:
minimum slab thickness, h
L ( 2.7 ) ( 1000 )
h= = = 96.43 mm
28 28
say h = 120 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.12 ) ( 23.5 ) = 2.82 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.41 kPa
Factored Load:
WUDL= 1.2 (DL) = 1.2 ( 5.41 ) = 6.492 kPa
WULL= 1.6 (LL) = 1.6 ( 4.8 ) = 7.68 kPa
WU = WUDL + WULL = 14.172 kPa
At END 1 :
Wu L2 ( 14.172 ) ( 2.7 )2
Mu = = = 9.3922 kN-m
11 11
MU 9.392 x 10e6
Rn = = = 1.181 MPa
f b d12 0.90 x 1000 x (94 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.181
= x 1- 1- = 0.00289
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 94 )
= 313.333333 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 360.957 mm
As 313.333333
say S = 360 mm
At MIDSPAN :
Wu L2 ( 14.172 ) ( 2.7 )2
Mu = = = 6.4571 kN-m
16 16
MU 6.457 x 10e6
Rn = = = 0.812 MPa
f b d12 0.90 x 1000 x (94 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.812
= x 1- 1- = 0.00197
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 94 )
= 313.333333 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 360.957 mm
As 313.333333
say S = 360 mm
At END 2 :
Wu L2 ( 14.172 ) ( 2.7 )2
Mu = = = 9.3922 kN-m
11 11
MU 9.392 x 10e6
Rn = = = 1.181 MPa
f b d12 0.90 x 1000 x (94 )2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.181
= x 1- 1- = 0.00289
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 94 )
= 313.333333 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 360.957 mm
As 313.333333
say S = 360 mm
temperature bars :
Ast = 0.0018 b h
= 0.0018 ( 1000 ) ( 120 )
= 216 mm2
Given:
short side A: 3.7 m fc' = 28 mPa
long side B: 3.7 m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 1 kPa conc. unit wt.= 23.5 kN/m3
SOLUTION:
3.70
ratio m = = 1.000 > 0.500 Two-way Slab!
3.70
d1 = h - (cover) - (rebar f) = 74 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 62 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.12 ) ( 23.5 ) = 2.82 kPa
floor finish = 0.46 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 0.3 kPa
4.07 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.2( 4.07 ) = 4.884 kPa
WULL = 1.6 (LL) = 1.6 ( 1 ) = 1.6 kPa
WU = WUDL + WULL = 6.484 kPa
at midspan
MADL = (WuDL) (CADL) (A2)
= 1.337 kN-m
MALL = (WuLL) (CALL) (A2)
= 0.613 kN-m
MA = MADL + MALL = 1.951 kN-m
at midspan
MBDL = (WuDL) (CBDL) (B2)
= 1.538 kN-m
MBLL = (WuLL) (CBLL) (B2)
= 0.657 kN-m
MB = MBDL + MBLL = 2.195 kN-m
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 2.929 x 10e6
Rn = = = 0.594 MPa
fbd 1
2
0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.594
= x 1- 1- = 0.00143
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
at midspan
MA 1.951 x 10e6
Rn = = = 0.396 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.396
= x 1- 1- = 0.00095
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.565
= x 1- 1- = 0.00386
420 0.85 x 28.0
As = f b d2
= ( 0.00386 ) ( 1000 ) ( 62 )
= 239.184739 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 472.856 mm
As 239.184739
say S = 470 mm
at midspan
MB 2.195 x 10e6
Rn = = = 0.634 MPa
f b d22 0.90 x 1000 x (62 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.634
= x 1- 1- = 0.00153
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 62 )
= 206.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 547.258 mm
As 206.666667
say S = 540 mm
Given:
short side A: 2.7 m fc' = 28 mPa
long side B: 3.7 m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 1 kPa conc. unit wt. = 23.5 kN/m3
SOLUTION:
2.70
ratio m = = 0.73 > 0.500 Two-way Slab!
3.70
d1 = h - (cover) - (rebar f) = 74 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 62 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.12 ) ( 23.5 ) = 2.82 kPa
floor finish = 0.46 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 0.3 kPa
4.070 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.6( 4.07 ) = 4.884 kPa
WULL = 1.6 (LL) = 1.6 ( 1 ) = 1.6 kPa
WU = WUDL + WULL = 6.484 kPa
Solving for Moments:
A. Short Span, Middle Strip
at continuous edge
0.75 0.069
0.730 CA
0.70 0.074
at midspan
for DL: 0.75 0.028
0.730 CADL
0.70 0.03
at midspan
for DL: 0.75 0.009
0.730 CBDL
0.70 0.007
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 3.357 x 10e6
Rn = = = 0.681 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.681
= x 1- 1- = 0.00165
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
at midspan
MA 1.570 x 10e6
Rn = = = 0.318 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.318
= x 1- 1- = 0.00076
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.512
= x 1- 1- = 0.00123
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 62 )
= 206.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 547.258 mm
As 206.666667
say S = 540 mm
Smax= 2h = 2 ( 120 ) = 240 mm or 450 mm
Therefore, Smax = 240 mm
at midspan
MB 0.836 x 10e6
Rn = = = 0.242 MPa
f b d22 0.90 x 1000 x (62 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.242
= x 1- 1- = 0.00058
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 62 )
= 206.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 547.258 mm
As 206.666667
say S = 540 mm
F ONE-WAY SLAB
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab length
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants for computing h and Mu.
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. For the design of sections having different moments, just replace tha value of
denominator for Mu for that corresponding section.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
F TWO-WAY SLAB
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
F TWO-WAY SLAB
NTERPOLATION
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
S-1 DESIGN OF TWO-WAY SLAB (CA
Given:
short side A: 3m fc' = 28 mPa
long side B: 4.5 m fy = 415 mPa
f = 0.9
LOADS: f = 0.85
live load: 1.9 kPa conc. unit wt.= 23.5 kN/m3
SOLUTION:
3.00
ratio m = = 0.667 > 0.500 Two-way Slab!
4.50
d1 = h - (cover) - (rebar f) = 99 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 87 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.125 ) ( 23.5 ) = 2.94 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0 kPa
electrical load = 0.25 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.53 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.2( 5.53 ) = 6.633 kPa
WULL = 1.6 (LL) = 1.6 ( 1.9 ) = 3.04 kPa
WU = WUDL + WULL = 9.673 kPa
at midspan
MBDL = (WuDL) (CBDL) (B2)
= 2.762 kN-m
MBLL = (WuLL) (CBLL) (B2)
= 1.512 kN-m
MB = MBDL + MBLL = 4.273 kN-m
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 5.474 x 10e6
Rn = = = 0.621 MPa
f b d12 0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.621
= x 1- 1- = 0.00152
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
at midspan
MA 3.176 x 10e6
Rn = = = 0.360 MPa
fbd 1
2
0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.360
= x 1- 1- = 0.00087
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.067
= x 1- 1- = 0.00263
415 0.85 x 28.0
As = f b d2
= ( 0.00337 ) ( 1000 ) ( 87 )
= 293.493976 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 385.357 mm
As 293.493976
say S = 380 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.627
= x 1- 1- = 0.00153
415 0.85 x 28.0
As = f b d2
= ( 0.00337 ) ( 1000 ) ( 87 )
= 293.493976 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 385.357 mm
As 293.493976
say S = 380 mm
SOLUTION:
3.00
ratio m = = 0.667 > 0.500 Two-way Slab!
4.50
d1 = h - (cover) - (rebar f) = 84 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 72 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.13 ) ( 23.5 ) = 3.06 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.645 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.6( 5.65 ) = 6.774 kPa
WULL = 1.6 (LL) = 1.6 ( 3.8 ) = 6.08 kPa
WU = WUDL + WULL = 12.854 kPa
at midspan
for DL: 0.7 0.046
0.667 CADL
0.65 0.054
at midspan
for DL: 0.7 0.011
0.667 CBDL
0.65 0.009
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 9.679 x 10e6
Rn = = = 1.524 MPa
fbd 1
2
0.90 x 1000 x (84 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.524
= x 1- 1- = 0.00375
420 0.85 x 28.0
As = f b d1
= ( 0.00375 ) ( 1000 ) ( 84 )
= 315.274084 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 358.735 mm
As 315.274084
say S = 350 mm
at midspan
MA 6.504 x 10e6
Rn = = = 1.024 MPa
f b d12 0.90 x 1000 x (84 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.024
= x 1- 1- = 0.00249
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.911
= x 1- 1- = 0.00221
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
at midspan
MB 2.803 x 10e6
Rn = = = 0.601 MPa
f b d22 0.90 x 1000 x (72 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.601
= x 1- 1- = 0.00145
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
0.90 0.022
0.667 CA
0.85 0.019
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
SLAB DESIGN
Given:
live load: 1.9 kPa fc' = 28 mPa
fy = 420 mPa L: 1.25 m
floor finish: 1.1 kPa f = 0.9 cover = 20 mm
ceiling finish: 0.24 kPa f 1
= 0.85
mech. duct allowance: 0.25 kPa conc. unit wt.= 23.5 kN/m3
electrical load: 0 kPa
partition load: 0 kPa using 12 mm rebars
miscellaneous load: 1 kPa Ad = 113.10 mm2
Solution:
minimum slab thickness, h
L ( 1.25 ) ( 1000 )
h= = = 44.64 mm
28 28
say h = 100 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.1 ) ( 23.5 ) = 2.35 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
4.94 kPa
Factored Load:
WUDL= 1.4 (DL) = 1.4 ( 4.94 ) = 6.916 kPa
WULL= 1.7 (LL) = 1.7 ( 1.9 ) = 3.23 kPa
WU = WUDL + WULL = 10.146 kPa
At END 1 :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 1.4412 kN-m
11 11
MU 1.441 x 10e6
Rn = = = 0.292 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.292
= x 1- 1- = 0.00070
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At MIDSPAN :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 0.9908 kN-m
16 16
MU 0.991 x 10e6
Rn = = = 0.201 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.201
= x 1- 1- = 0.00048
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At END 2 :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 1.4412 kN-m
11 11
MU 1.441 x 10e6
Rn = = = 0.292 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.292
= x 1- 1- = 0.00070
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
temperature bars :
Ast = 0.0018 bh
= 0.0018 ( 1000 ) ( 100 )
= 180 mm2
say S = 620 mm
Therefore, CA =
Smax = 5h = 5 ( 100 ) = 500 mm or 450 mm
Therefore, Smax = 450 mm
Given:
short side A: 2.83 m fc' = 28 mPa
long side B: 4.925 m fy = 415 mPa
f = 0.9
LOADS: f = 0.85
live load: 4.8 kPa conc. unit wt.= 23.5 kN/m3
SOLUTION:
2.83
ratio m = = 0.574 > 0.500 Two-way Slab!
4.93
d1 = h - (cover) - (rebar f) = 99 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 87 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.125 ) ( 23.5 ) = 2.94 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0 kPa
electrical load = 0.25 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.53 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.2( 5.53 ) = 6.633 kPa
WULL = 1.6 (LL) = 1.6 ( 4.8 ) = 7.68 kPa
WU = WUDL + WULL = 14.313 kPa
at midspan
MADL = (WuDL) (CADL) (A2)
= 1.834 kN-m
MALL = (WuLL) (CALL) (A2)
= 3.695 kN-m
MA = MADL + MALL = 5.529 kN-m
at midspan
MBDL = (WuDL) (CBDL) (B2)
= 0.560 kN-m
MBLL = (WuLL) (CBLL) (B2)
= 1.207 kN-m
MB = MBDL + MBLL = 1.767 kN-m
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 9.464 x 10e6
Rn = = = 1.073 MPa
f b d12 0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.073
= x 1- 1- = 0.00265
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
at midspan
MA 5.529 x 10e6
Rn = = = 0.627 MPa
fbd 1
2
0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.627
= x 1- 1- = 0.00153
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.430
= x 1- 1- = 0.00105
415 0.85 x 28.0
As = f b d2
= ( 0.00337 ) ( 1000 ) ( 87 )
= 293.493976 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 385.357 mm
As 293.493976
say S = 380 mm
at midspan
MB 1.767 x 10e6
Rn = = = 0.259 MPa
f b d22 0.90 x 1000 x (87 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.259
= x 1- 1- = 0.00063
415 0.85 x 28.0
As = f b d2
= ( 0.00337 ) ( 1000 ) ( 87 )
= 293.493976 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 385.357 mm
As 293.493976
say S = 380 mm
Given:
short side A: 3m fc' = 28 mPa
long side B: 4.5 m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 3.8 kPa conc. unit wt. = 23.5 kN/m3
SOLUTION:
3.00
ratio m = = 0.667 > 0.500 Two-way Slab!
4.50
2 ( 3.00 + 4.50 ) (1000)
h= = 83.333 mm
180
say h = 130 mm > hmin = 90 mm ok!
d1 = h - (cover) - (rebar f) = 84 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 72 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.13 ) ( 23.5 ) = 3.06 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.645 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.6( 5.65 ) = 6.774 kPa
WULL = 1.6 (LL) = 1.6 ( 3.8 ) = 6.08 kPa
WU = WUDL + WULL = 12.854 kPa
at midspan
for DL: 0.7 0.081
0.667 CADL
0.65 0.085
at midspan
for DL: 0.7 0.014
0.667 CBDL
0.65 0.012
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.941
= x 1- 1- = 0.00229
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
at midspan
MA 9.260 x 10e6
Rn = = = 1.458 MPa
fbd 1
2
0.90 x 1000 x (84 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.458
= x 1- 1- = 0.00359
420 0.85 x 28.0
As = f b d1
= ( 0.00359 ) ( 1000 ) ( 84 )
= 301.146955 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 375.564 mm
As 301.146955
say S = 370 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.841
= x 1- 1- = 0.00457
420 0.85 x 28.0
1.4 fc' 1.4 28
rmin = or = or
fy 4 fy 420 4 x 420
= 0.00333333 or 0.0031497 Therefore, use 0.00333
As = f b d2
= ( 0.00457 ) ( 1000 ) ( 72 )
= 328.8656 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 343.909 mm
As 328.8656
say S = 340 mm
at midspan
MB 5.062 x 10e6
Rn = = = 1.085 MPa
f b d22 0.90 x 1000 x (72 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.085
= x 1- 1- = 0.00264
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
F ONE-WAY SLAB
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab length
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants for computing h and Mu.
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. For the design of sections having different moments, just replace tha value of
denominator for Mu for that corresponding section.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
0.90 0.025
0.574 CA
0.85 0.029
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
0.60 0.034
0.574 CA
0.55 0.035
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
S-2 DESIGN OF TWO-WAY SLAB (CA
Given:
short side A: 4m fc' = 28 mPa
long side B: 4.5 m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 1.9 kPa conc. unit wt.= 23.5 kN/m3
SOLUTION:
4.00
ratio m = = 0.889 > 0.500 Two-way Slab!
4.50
d1 = h - (cover) - (rebar f) = 99 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 87 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.125 ) ( 23.5 ) = 2.94 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0 kPa
electrical load = 0.25 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.53 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.2( 5.53 ) = 6.633 kPa
WULL = 1.6 (LL) = 1.6 ( 1.9 ) = 3.04 kPa
WU = WUDL + WULL = 9.673 kPa
at midspan
MBDL = (WuDL) (CBDL) (B2)
= 2.423 kN-m
MBLL = (WuLL) (CBLL) (B2)
= 1.418 kN-m
MB = MBDL + MBLL = 3.841 kN-m
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 7.101 x 10e6
Rn = = = 0.805 MPa
f b d12 0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.805
= x 1- 1- = 0.00195
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 99 )
= 330 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 342.727 mm
As 330
say S = 340 mm
at midspan
MA 4.676 x 10e6
Rn = = = 0.530 MPa
fbd 1
2
0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.530
= x 1- 1- = 0.00128
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 99 )
= 330 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 342.727 mm
As 330
say S = 340 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.412
= x 1- 1- = 0.00347
420 0.85 x 28.0
As = f b d2
= ( 0.00347 ) ( 1000 ) ( 87 )
= 301.810826 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 374.738 mm
As 301.810826
say S = 370 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.564
= x 1- 1- = 0.00136
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 87 )
= 290 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 390 mm
As 290
say S = 390 mm
SOLUTION:
3.00
ratio m = = 0.667 > 0.500 Two-way Slab!
4.50
d1 = h - (cover) - (rebar f) = 84 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 72 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.13 ) ( 23.5 ) = 3.06 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.645 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.6( 5.65 ) = 6.774 kPa
WULL = 1.6 (LL) = 1.6 ( 3.8 ) = 6.08 kPa
WU = WUDL + WULL = 12.854 kPa
at midspan
for DL: 0.7 0.04
0.667 CADL
0.65 0.044
at midspan
for DL: 0.7 0.011
0.667 CBDL
0.65 0.009
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 8.329 x 10e6
Rn = = = 1.312 MPa
fbd 1
2
0.90 x 1000 x (84 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.312
= x 1- 1- = 0.00321
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
at midspan
MA 6.304 x 10e6
Rn = = = 0.993 MPa
f b d12 0.90 x 1000 x (84 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.993
= x 1- 1- = 0.00241
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.432
= x 1- 1- = 0.00352
420 0.85 x 28.0
As = f b d2
= ( 0.00352 ) ( 1000 ) ( 72 )
= 253.3411 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 446.434 mm
As 253.3411
say S = 440 mm
at midspan
MB 2.803 x 10e6
Rn = = = 0.601 MPa
f b d22 0.90 x 1000 x (72 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.601
= x 1- 1- = 0.00145
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
0.90 0.022
0.889 CA
0.85 0.019
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
S-1 DESIGN OF TWO-WAY SLAB (CA
Given:
short side A: 2.83 m fc' = 28 mPa
long side B: 4.925 m fy = 415 mPa
f = 0.9
LOADS: f = 0.85
live load: 4.8 kPa conc. unit wt.= 23.5 kN/m3
SOLUTION:
2.83
ratio m = = 0.574 > 0.500 Two-way Slab!
4.93
d1 = h - (cover) - (rebar f) = 99 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 87 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.125 ) ( 23.5 ) = 2.94 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0 kPa
electrical load = 0.25 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.53 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.2( 5.53 ) = 6.633 kPa
WULL = 1.6 (LL) = 1.6 ( 4.8 ) = 7.68 kPa
WU = WUDL + WULL = 14.313 kPa
at midspan
MADL = (WuDL) (CADL) (A2)
= 1.940 kN-m
MALL = (WuLL) (CALL) (A2)
= 3.757 kN-m
MA = MADL + MALL = 5.697 kN-m
at midspan
MBDL = (WuDL) (CBDL) (B2)
= 0.560 kN-m
MBLL = (WuLL) (CBLL) (B2)
= 1.207 kN-m
MB = MBDL + MBLL = 1.767 kN-m
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 9.803 x 10e6
Rn = = = 1.111 MPa
f b d12 0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.111
= x 1- 1- = 0.00274
415 0.85 x 28.0
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
at midspan
MA 5.697 x 10e6
Rn = = = 0.646 MPa
f b d12 0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.646
= x 1- 1- = 0.00158
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 2.793
= x 1- 1- = 0.00718
415 0.85 x 28.0
As = f b d2
= ( 0.00718 ) ( 1000 ) ( 87 )
= 624.574637 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 181.083 mm
As 624.574637
say S = 180 mm
at midspan
MB 1.767 x 10e6
Rn = = = 0.259 MPa
f b d22 0.90 x 1000 x (87 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.259
= x 1- 1- = 0.00063
415 0.85 x 28.0
As = f b d2
= ( 0.00337 ) ( 1000 ) ( 87 )
= 293.493976 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 385.357 mm
As 293.493976
say S = 380 mm
Given:
short side A: 3m fc' = 28 mPa
long side B: 4.5 m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 3.8 kPa conc. unit wt. = 23.5 kN/m3
SOLUTION:
3.00
ratio m = = 0.667 > 0.500 Two-way Slab!
4.50
d1 = h - (cover) - (rebar f) = 84 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 72 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.13 ) ( 23.5 ) = 3.06 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.645 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.6( 5.65 ) = 6.774 kPa
WULL = 1.6 (LL) = 1.6 ( 3.8 ) = 6.08 kPa
WU = WUDL + WULL = 12.854 kPa
at midspan
for DL: 0.7 0.033
0.667 CADL
0.65 0.034
at midspan
for DL: 0.7 0.015
0.667 CBDL
0.65 0.013
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 9.525 x 10e6
Rn = = = 1.500 MPa
f b d12 0.90 x 1000 x (84 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.500
= x 1- 1- = 0.00369
420 0.85 x 28.0
As = f b d1
= ( 0.00369 ) ( 1000 ) ( 84 )
= 310.074645 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 364.751 mm
As 310.074645
say S = 360 mm
at midspan
MA 4.934 x 10e6
Rn = = = 0.777 MPa
fbd 1
2
0.90 x 1000 x (84 )2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.777
= x 1- 1- = 0.00188
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.692
= x 1- 1- = 0.00418
420 0.85 x 28.0
As = f b d2
= ( 0.00418 ) ( 1000 ) ( 72 )
= 301.227492 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 375.464 mm
As 301.227492
say S = 370 mm
at midspan
MB 4.419 x 10e6
Rn = = = 0.947 MPa
f b d22 0.90 x 1000 x (72 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.947
= x 1- 1- = 0.00230
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
0.60 0.036
0.574 CA
0.55 0.037
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
SLAB DESIGN
Given:
live load: 1.9 kPa fc' = 28 mPa
fy = 420 mPa L: 1.25 m
floor finish: 1.1 kPa f = 0.9 cover = 20 mm
ceiling finish: 0.24 kPa f 1
= 0.85
mech. duct allowance: 0.25 kPa conc. unit wt.= 23.5 kN/m3
electrical load: 0 kPa
partition load: 0 kPa using 12 mm rebars
miscellaneous load: 1 kPa Ad = 113.10 mm2
Solution:
minimum slab thickness, h
L ( 1.25 ) ( 1000 )
h= = = 44.64 mm
28 28
say h = 100 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.1 ) ( 23.5 ) = 2.35 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
4.94 kPa
Factored Load:
WUDL= 1.4 (DL) = 1.4 ( 4.94 ) = 6.916 kPa
WULL= 1.7 (LL) = 1.7 ( 1.9 ) = 3.23 kPa
WU = WUDL + WULL = 10.146 kPa
At END 1 :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 1.4412 kN-m
11 11
MU 1.441 x 10e6
Rn = = = 0.292 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.292
= x 1- 1- = 0.00070
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At MIDSPAN :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 0.9908 kN-m
16 16
MU 0.991 x 10e6
Rn = = = 0.201 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.201
= x 1- 1- = 0.00048
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At END 2 :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 1.4412 kN-m
11 11
MU 1.441 x 10e6
Rn = = = 0.292 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.292
= x 1- 1- = 0.00070
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
temperature bars :
Ast = 0.0018 bh
= 0.0018 ( 1000 ) ( 100 )
= 180 mm2
say S = 620 mm
Therefore, CA =
Smax = 5h = 5 ( 100 ) = 500 mm or 450 mm
Therefore, Smax = 450 mm
Given:
short side A: 2.83 m fc' = 28 mPa
long side B: 4.925 m fy = 415 mPa
f = 0.9
LOADS: f = 0.85
live load: 4.8 kPa conc. unit wt.= 23.5 kN/m3
SOLUTION:
2.83
ratio m = = 0.574 > 0.500 Two-way Slab!
4.93
d1 = h - (cover) - (rebar f) = 99 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 87 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.125 ) ( 23.5 ) = 2.94 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0 kPa
electrical load = 0.25 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.53 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.2( 5.53 ) = 6.633 kPa
WULL = 1.6 (LL) = 1.6 ( 4.8 ) = 7.68 kPa
WU = WUDL + WULL = 14.313 kPa
at midspan
MADL = (WuDL) (CADL) (A2)
= 1.834 kN-m
MALL = (WuLL) (CALL) (A2)
= 3.695 kN-m
MA = MADL + MALL = 5.529 kN-m
at midspan
MBDL = (WuDL) (CBDL) (B2)
= 0.560 kN-m
MBLL = (WuLL) (CBLL) (B2)
= 1.207 kN-m
MB = MBDL + MBLL = 1.767 kN-m
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 9.464 x 10e6
Rn = = = 1.073 MPa
f b d12 0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.073
= x 1- 1- = 0.00265
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
at midspan
MA 5.529 x 10e6
Rn = = = 0.627 MPa
fbd 1
2
0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.627
= x 1- 1- = 0.00153
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.430
= x 1- 1- = 0.00105
415 0.85 x 28.0
As = f b d2
= ( 0.00337 ) ( 1000 ) ( 87 )
= 293.493976 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 385.357 mm
As 293.493976
say S = 380 mm
at midspan
MB 1.767 x 10e6
Rn = = = 0.259 MPa
f b d22 0.90 x 1000 x (87 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.259
= x 1- 1- = 0.00063
415 0.85 x 28.0
As = f b d2
= ( 0.00337 ) ( 1000 ) ( 87 )
= 293.493976 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 385.357 mm
As 293.493976
say S = 380 mm
Given:
short side A: 3.5 m fc' = 28 mPa
long side B: 4.5 m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 1.9 kPa conc. unit wt. = 23.5 kN/m3
SOLUTION:
3.50
ratio m = = 0.778 > 0.500 Two-way Slab!
4.50
2 ( 3.50 + 4.50 ) (1000)
h= = 88.889 mm
180
say h = 130 mm > hmin = 90 mm ok!
d1 = h - (cover) - (rebar f) = 84 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 72 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.13 ) ( 23.5 ) = 3.06 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.645 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.6( 5.65 ) = 6.774 kPa
WULL = 1.6 (LL) = 1.6 ( 1.9 ) = 3.04 kPa
WU = WUDL + WULL = 9.814 kPa
at midspan
for DL: 0.8 0.026
0.778 CADL
0.75 0.028
at midspan
for DL: 0.8 0.023
0.778 CBDL
0.75 0.019
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.264
= x 1- 1- = 0.00309
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
at midspan
MA 3.824 x 10e6
Rn = = = 0.602 MPa
fbd 1
2
0.90 x 1000 x (84 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.602
= x 1- 1- = 0.00145
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.055
= x 1- 1- = 0.00257
420 0.85 x 28.0
1.4 fc' 1.4 28
rmin = or = or
fy 4 fy 420 4 x 420
= 0.00333333 or 0.0031497 Therefore, use 0.00333
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
at midspan
MB 3.876 x 10e6
Rn = = = 0.831 MPa
f b d22 0.90 x 1000 x (72 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.831
= x 1- 1- = 0.00201
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
F ONE-WAY SLAB
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab length
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants for computing h and Mu.
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. For the design of sections having different moments, just replace tha value of
denominator for Mu for that corresponding section.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
0.90 0.025
0.574 CA
0.85 0.029
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
0.60 0.034
0.574 CA
0.55 0.035
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
SLAB DESIGN
Given:
live load: 3.8 kPa fc' = 28 mPa
fy = 420 mPa L: 1.25 m
floor finish: 1.1 kPa f = 0.9 cover = 20 mm
ceiling finish: 0.24 kPa f 1
= 0.85
mech. duct allowance: 0.25 kPa conc. unit wt.= 23.5 kN/m3
electrical load: 0 kPa
partition load: 0 kPa using 12 mm rebars
miscellaneous load: 1 kPa Ad = 113.10 mm2
Solution:
minimum slab thickness, h
L ( 1.25 ) ( 1000 )
h= = = 44.64 mm
28 28
say h = 100 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.1 ) ( 23.5 ) = 2.35 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
4.94 kPa
Factored Load:
WUDL= 1.4 (DL) = 1.4 ( 4.94 ) = 6.916 kPa
WULL= 1.7 (LL) = 1.7 ( 3.8 ) = 6.46 kPa
WU = WUDL + WULL = 13.376 kPa
At END 1 :
Wu L2 ( 13.376 ) ( 1.25 )2
Mu = = = 1.9000 kN-m
11 11
MU 1.900 x 10e6
Rn = = = 0.386 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.386
= x 1- 1- = 0.00093
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At MIDSPAN :
Wu L2 ( 13.376 ) ( 1.25 )2
Mu = = = 1.3063 kN-m
16 16
MU 1.306 x 10e6
Rn = = = 0.265 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.265
= x 1- 1- = 0.00063
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At END 2 :
Wu L2 ( 13.376 ) ( 1.25 )2
Mu = = = 1.9000 kN-m
11 11
MU 1.900 x 10e6
Rn = = = 0.386 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.386
= x 1- 1- = 0.00093
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
temperature bars :
Ast = 0.0018 bh
= 0.0018 ( 1000 ) ( 100 )
= 180 mm2
say S = 620 mm
Therefore, CA =
Smax = 5h = 5 ( 100 ) = 500 mm or 450 mm
Therefore, Smax = 450 mm
Given:
short side A: 2.83 m fc' = 28 mPa
long side B: 4.925 m fy = 415 mPa
f = 0.9
LOADS: f = 0.85
live load: 4.8 kPa conc. unit wt.= 23.5 kN/m3
SOLUTION:
2.83
ratio m = = 0.574 > 0.500 Two-way Slab!
4.93
d1 = h - (cover) - (rebar f) = 99 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 87 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.125 ) ( 23.5 ) = 2.94 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0 kPa
electrical load = 0.25 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.53 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.2( 5.53 ) = 6.633 kPa
WULL = 1.6 (LL) = 1.6 ( 4.8 ) = 7.68 kPa
WU = WUDL + WULL = 14.313 kPa
at midspan
MADL = (WuDL) (CADL) (A2)
= 1.940 kN-m
MALL = (WuLL) (CALL) (A2)
= 3.757 kN-m
MA = MADL + MALL = 5.697 kN-m
at midspan
MBDL = (WuDL) (CBDL) (B2)
= 0.560 kN-m
MBLL = (WuLL) (CBLL) (B2)
= 1.207 kN-m
MB = MBDL + MBLL = 1.767 kN-m
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 9.803 x 10e6
Rn = = = 1.111 MPa
f b d12 0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.111
= x 1- 1- = 0.00274
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
at midspan
MA 5.697 x 10e6
Rn = = = 0.646 MPa
fbd 1
2
0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.646
= x 1- 1- = 0.00158
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 2.793
= x 1- 1- = 0.00718
415 0.85 x 28.0
As = f b d2
= ( 0.00718 ) ( 1000 ) ( 87 )
= 624.574637 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 181.083 mm
As 624.574637
say S = 180 mm
at midspan
MB 1.767 x 10e6
Rn = = = 0.259 MPa
f b d22 0.90 x 1000 x (87 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.259
= x 1- 1- = 0.00063
415 0.85 x 28.0
As = f b d2
= ( 0.00337 ) ( 1000 ) ( 87 )
= 293.493976 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 385.357 mm
As 293.493976
say S = 380 mm
Given:
short side A: 3.5 m fc' = 28 mPa
long side B: 4.5 m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 1.9 kPa conc. unit wt. = 23.5 kN/m3
SOLUTION:
3.50
ratio m = = 0.778 > 0.500 Two-way Slab!
4.50
2 ( 3.50 + 4.50 ) (1000)
h= = 88.889 mm
180
say h = 130 mm > hmin = 90 mm ok!
d1 = h - (cover) - (rebar f) = 84 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 72 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.13 ) ( 23.5 ) = 3.06 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.645 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.6( 5.65 ) = 6.774 kPa
WULL = 1.6 (LL) = 1.6 ( 1.9 ) = 3.04 kPa
WU = WUDL + WULL = 9.814 kPa
at midspan
for DL: 0.8 0.029
0.778 CADL
0.75 0.031
at midspan
for DL: 0.8 0.029
0.778 CBDL
0.75 0.031
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.454
= x 1- 1- = 0.00357
420 0.85 x 28.0
As = f b d1
= ( 0.00357 ) ( 1000 ) ( 84 )
= 300.165245 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 376.792 mm
As 300.165245
say S = 370 mm
at midspan
MA 4.111 x 10e6
Rn = = = 0.647 MPa
fbd 1
2
0.90 x 1000 x (84 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.647
= x 1- 1- = 0.00156
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.667
= x 1- 1- = 0.00161
420 0.85 x 28.0
1.4 fc' 1.4 28
rmin = or = or
fy 4 fy 420 4 x 420
= 0.00333333 or 0.0031497 Therefore, use 0.00333
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
at midspan
MB 5.037 x 10e6
Rn = = = 1.080 MPa
f b d22 0.90 x 1000 x (72 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.080
= x 1- 1- = 0.00263
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
F ONE-WAY SLAB
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab length
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants for computing h and Mu.
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. For the design of sections having different moments, just replace tha value of
denominator for Mu for that corresponding section.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
0.90 0.025
0.574 CA
0.85 0.029
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
0.60 0.036
0.574 CA
0.55 0.037
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
SLAB DESIGN
Given:
live load: 1.9 kPa fc' = 28 mPa
fy = 420 mPa L: 1.25 m
floor finish: 1.1 kPa f = 0.9 cover = 20 mm
ceiling finish: 0.24 kPa f 1
= 0.85
mech. duct allowance: 0.25 kPa conc. unit wt.= 23.5 kN/m3
electrical load: 0 kPa
partition load: 0 kPa using 12 mm rebars
miscellaneous load: 1 kPa Ad = 113.10 mm2
Solution:
minimum slab thickness, h
L ( 1.25 ) ( 1000 )
h= = = 44.64 mm
28 28
say h = 100 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.1 ) ( 23.5 ) = 2.35 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
4.94 kPa
Factored Load:
WUDL= 1.4 (DL) = 1.4 ( 4.94 ) = 6.916 kPa
WULL= 1.7 (LL) = 1.7 ( 1.9 ) = 3.23 kPa
WU = WUDL + WULL = 10.146 kPa
At END 1 :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 1.4412 kN-m
11 11
MU 1.441 x 10e6
Rn = = = 0.292 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.292
= x 1- 1- = 0.00070
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At MIDSPAN :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 0.9908 kN-m
16 16
MU 0.991 x 10e6
Rn = = = 0.201 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.201
= x 1- 1- = 0.00048
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At END 2 :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 1.4412 kN-m
11 11
MU 1.441 x 10e6
Rn = = = 0.292 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.292
= x 1- 1- = 0.00070
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
temperature bars :
Ast = 0.0018 bh
= 0.0018 ( 1000 ) ( 100 )
= 180 mm2
say S = 620 mm
Therefore, CA =
Smax = 5h = 5 ( 100 ) = 500 mm or 450 mm
Therefore, Smax = 450 mm
Given:
short side A: 2.83 m fc' = 28 mPa
long side B: 4.925 m fy = 415 mPa
f = 0.9
LOADS: f = 0.85
live load: 4.8 kPa conc. unit wt.= 23.5 kN/m3
SOLUTION:
2.83
ratio m = = 0.574 > 0.500 Two-way Slab!
4.93
d1 = h - (cover) - (rebar f) = 99 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 87 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.125 ) ( 23.5 ) = 2.94 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0 kPa
electrical load = 0.25 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.53 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.2( 5.53 ) = 6.633 kPa
WULL = 1.6 (LL) = 1.6 ( 4.8 ) = 7.68 kPa
WU = WUDL + WULL = 14.313 kPa
at midspan
MADL = (WuDL) (CADL) (A2)
= 1.834 kN-m
MALL = (WuLL) (CALL) (A2)
= 3.695 kN-m
MA = MADL + MALL = 5.529 kN-m
at midspan
MBDL = (WuDL) (CBDL) (B2)
= 0.560 kN-m
MBLL = (WuLL) (CBLL) (B2)
= 1.207 kN-m
MB = MBDL + MBLL = 1.767 kN-m
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 9.464 x 10e6
Rn = = = 1.073 MPa
f b d12 0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.073
= x 1- 1- = 0.00265
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
at midspan
MA 5.529 x 10e6
Rn = = = 0.627 MPa
fbd 1
2
0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.627
= x 1- 1- = 0.00153
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.430
= x 1- 1- = 0.00105
415 0.85 x 28.0
As = f b d2
= ( 0.00337 ) ( 1000 ) ( 87 )
= 293.493976 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 385.357 mm
As 293.493976
say S = 380 mm
at midspan
MB 1.767 x 10e6
Rn = = = 0.259 MPa
f b d22 0.90 x 1000 x (87 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.259
= x 1- 1- = 0.00063
415 0.85 x 28.0
As = f b d2
= ( 0.00337 ) ( 1000 ) ( 87 )
= 293.493976 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 385.357 mm
As 293.493976
say S = 380 mm
Given:
short side A: 2.5 m fc' = 28 mPa
long side B: 3.5 m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 3.8 kPa conc. unit wt. = 23.5 kN/m3
SOLUTION:
2.50
ratio m = = 0.714 > 0.500 Two-way Slab!
3.50
2 ( 2.50 + 3.50 ) (1000)
h= = 66.667 mm
180
say h = 130 mm > hmin = 90 mm ok!
d1 = h - (cover) - (rebar f) = 84 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 72 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.13 ) ( 23.5 ) = 3.06 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.645 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.6( 5.65 ) = 6.774 kPa
WULL = 1.6 (LL) = 1.6 ( 3.8 ) = 6.08 kPa
WU = WUDL + WULL = 12.854 kPa
at midspan
for DL: 0.75 0.04
0.714 CADL
0.70 0.046
at midspan
for DL: 0.75 0.009
0.714 CBDL
0.70 0.007
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.918
= x 1- 1- = 0.00223
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
at midspan
MA 3.694 x 10e6
Rn = = = 0.582 MPa
fbd 1
2
0.90 x 1000 x (84 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.582
= x 1- 1- = 0.00140
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.622
= x 1- 1- = 0.00150
420 0.85 x 28.0
1.4 fc' 1.4 28
rmin = or = or
fy 4 fy 420 4 x 420
= 0.00333333 or 0.0031497 Therefore, use 0.00333
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
at midspan
MB 1.565 x 10e6
Rn = = = 0.335 MPa
f b d22 0.90 x 1000 x (72 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.335
= x 1- 1- = 0.00080
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
F ONE-WAY SLAB
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab length
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants for computing h and Mu.
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. For the design of sections having different moments, just replace tha value of
denominator for Mu for that corresponding section.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
0.90 0.025
0.574 CA
0.85 0.029
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
0.60 0.034
0.574 CA
0.55 0.035
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
SLAB DESIGN
Given:
live load: 1.9 kPa fc' = 28 mPa
fy = 420 mPa L: 1.25 m
floor finish: 1.1 kPa f = 0.9 cover = 20 mm
ceiling finish: 0.24 kPa f 1
= 0.85
mech. duct allowance: 0.25 kPa conc. unit wt.= 23.5 kN/m3
electrical load: 0 kPa
partition load: 0 kPa using 12 mm rebars
miscellaneous load: 1 kPa Ad = 113.10 mm2
Solution:
minimum slab thickness, h
L ( 1.25 ) ( 1000 )
h= = = 44.64 mm
28 28
say h = 100 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.1 ) ( 23.5 ) = 2.35 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
4.94 kPa
Factored Load:
WUDL= 1.4 (DL) = 1.4 ( 4.94 ) = 6.916 kPa
WULL= 1.7 (LL) = 1.7 ( 1.9 ) = 3.23 kPa
WU = WUDL + WULL = 10.146 kPa
At END 1 :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 1.4412 kN-m
11 11
MU 1.441 x 10e6
Rn = = = 0.292 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.292
= x 1- 1- = 0.00070
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At MIDSPAN :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 0.9908 kN-m
16 16
MU 0.991 x 10e6
Rn = = = 0.201 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.201
= x 1- 1- = 0.00048
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At END 2 :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 1.4412 kN-m
11 11
MU 1.441 x 10e6
Rn = = = 0.292 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.292
= x 1- 1- = 0.00070
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
temperature bars :
Ast = 0.0018 bh
= 0.0018 ( 1000 ) ( 100 )
= 180 mm2
say S = 620 mm
Therefore, CA =
Smax = 5h = 5 ( 100 ) = 500 mm or 450 mm
Therefore, Smax = 450 mm
Given:
short side A: 2.83 m fc' = 28 mPa
long side B: 4.925 m fy = 415 mPa
f = 0.9
LOADS: f = 0.85
live load: 4.8 kPa conc. unit wt.= 23.5 kN/m3
SOLUTION:
2.83
ratio m = = 0.574 > 0.500 Two-way Slab!
4.93
d1 = h - (cover) - (rebar f) = 99 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 87 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.125 ) ( 23.5 ) = 2.94 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0 kPa
electrical load = 0.25 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.53 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.2( 5.53 ) = 6.633 kPa
WULL = 1.6 (LL) = 1.6 ( 4.8 ) = 7.68 kPa
WU = WUDL + WULL = 14.313 kPa
at midspan
MADL = (WuDL) (CADL) (A2)
= 1.834 kN-m
MALL = (WuLL) (CALL) (A2)
= 3.695 kN-m
MA = MADL + MALL = 5.529 kN-m
at midspan
MBDL = (WuDL) (CBDL) (B2)
= 0.560 kN-m
MBLL = (WuLL) (CBLL) (B2)
= 1.207 kN-m
MB = MBDL + MBLL = 1.767 kN-m
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 9.464 x 10e6
Rn = = = 1.073 MPa
f b d12 0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.073
= x 1- 1- = 0.00265
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
at midspan
MA 5.529 x 10e6
Rn = = = 0.627 MPa
fbd 1
2
0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.627
= x 1- 1- = 0.00153
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.430
= x 1- 1- = 0.00105
415 0.85 x 28.0
As = f b d2
= ( 0.00337 ) ( 1000 ) ( 87 )
= 293.493976 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 385.357 mm
As 293.493976
say S = 380 mm
at midspan
MB 1.767 x 10e6
Rn = = = 0.259 MPa
f b d22 0.90 x 1000 x (87 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.259
= x 1- 1- = 0.00063
415 0.85 x 28.0
As = f b d2
= ( 0.00337 ) ( 1000 ) ( 87 )
= 293.493976 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 385.357 mm
As 293.493976
say S = 380 mm
Given:
short side A: 2.5 m fc' = 28 mPa
long side B: 3m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 1.9 kPa conc. unit wt. = 23.5 kN/m3
SOLUTION:
2.50
ratio m = = 0.833 > 0.500 Two-way Slab!
3.00
2 ( 2.50 + 3.00 ) (1000)
h= = 61.111 mm
180
say h = 130 mm > hmin = 90 mm ok!
d1 = h - (cover) - (rebar f) = 84 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 72 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.13 ) ( 23.5 ) = 3.06 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.645 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.6( 5.65 ) = 6.774 kPa
WULL = 1.6 (LL) = 1.6 ( 1.9 ) = 3.04 kPa
WU = WUDL + WULL = 9.814 kPa
at midspan
for DL: 0.85 0.024
0.833 CADL
0.80 0.026
at midspan
for DL: 0.85 0.012
0.833 CBDL
0.80 0.011
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.596
= x 1- 1- = 0.00144
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
at midspan
MA 1.773 x 10e6
Rn = = = 0.279 MPa
fbd 1
2
0.90 x 1000 x (84 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.279
= x 1- 1- = 0.00067
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.562
= x 1- 1- = 0.00135
420 0.85 x 28.0
1.4 fc' 1.4 28
rmin = or = or
fy 4 fy 420 4 x 420
= 0.00333333 or 0.0031497 Therefore, use 0.00333
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
at midspan
MB 1.213 x 10e6
Rn = = = 0.260 MPa
f b d22 0.90 x 1000 x (72 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.260
= x 1- 1- = 0.00062
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
F ONE-WAY SLAB
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab length
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants for computing h and Mu.
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. For the design of sections having different moments, just replace tha value of
denominator for Mu for that corresponding section.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
0.90 0.025
0.574 CA
0.85 0.029
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
0.60 0.034
0.574 CA
0.55 0.035
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
SLAB DESIGN
Given:
live load: 1.9 kPa fc' = 28 mPa
fy = 420 mPa L: 1.25 m
floor finish: 1.1 kPa f = 0.9 cover = 20 mm
ceiling finish: 0.24 kPa f 1
= 0.85
mech. duct allowance: 0.25 kPa conc. unit wt.= 23.5 kN/m3
electrical load: 0 kPa
partition load: 0 kPa using 12 mm rebars
miscellaneous load: 1 kPa Ad = 113.10 mm2
Solution:
minimum slab thickness, h
L ( 1.25 ) ( 1000 )
h= = = 44.64 mm
28 28
say h = 100 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.1 ) ( 23.5 ) = 2.35 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
4.94 kPa
Factored Load:
WUDL= 1.4 (DL) = 1.4 ( 4.94 ) = 6.916 kPa
WULL= 1.7 (LL) = 1.7 ( 1.9 ) = 3.23 kPa
WU = WUDL + WULL = 10.146 kPa
At END 1 :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 1.4412 kN-m
11 11
MU 1.441 x 10e6
Rn = = = 0.292 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.292
= x 1- 1- = 0.00070
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At MIDSPAN :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 0.9908 kN-m
16 16
MU 0.991 x 10e6
Rn = = = 0.201 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.201
= x 1- 1- = 0.00048
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At END 2 :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 1.4412 kN-m
11 11
MU 1.441 x 10e6
Rn = = = 0.292 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.292
= x 1- 1- = 0.00070
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
temperature bars :
Ast = 0.0018 bh
= 0.0018 ( 1000 ) ( 100 )
= 180 mm2
say S = 620 mm
Therefore, CA =
Smax = 5h = 5 ( 100 ) = 500 mm or 450 mm
Therefore, Smax = 450 mm
Given:
short side A: 2.83 m fc' = 28 mPa
long side B: 4.925 m fy = 415 mPa
f = 0.9
LOADS: f = 0.85
live load: 4.8 kPa conc. unit wt.= 23.5 kN/m3
SOLUTION:
2.83
ratio m = = 0.574 > 0.500 Two-way Slab!
4.93
d1 = h - (cover) - (rebar f) = 99 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 87 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.125 ) ( 23.5 ) = 2.94 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0 kPa
electrical load = 0.25 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.53 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.2( 5.53 ) = 6.633 kPa
WULL = 1.6 (LL) = 1.6 ( 4.8 ) = 7.68 kPa
WU = WUDL + WULL = 14.313 kPa
at midspan
MADL = (WuDL) (CADL) (A2)
= 1.940 kN-m
MALL = (WuLL) (CALL) (A2)
= 3.757 kN-m
MA = MADL + MALL = 5.697 kN-m
at midspan
MBDL = (WuDL) (CBDL) (B2)
= 0.560 kN-m
MBLL = (WuLL) (CBLL) (B2)
= 1.207 kN-m
MB = MBDL + MBLL = 1.767 kN-m
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 9.803 x 10e6
Rn = = = 1.111 MPa
f b d12 0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.111
= x 1- 1- = 0.00274
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
at midspan
MA 5.697 x 10e6
Rn = = = 0.646 MPa
fbd 1
2
0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.646
= x 1- 1- = 0.00158
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 2.793
= x 1- 1- = 0.00718
415 0.85 x 28.0
As = f b d2
= ( 0.00718 ) ( 1000 ) ( 87 )
= 624.574637 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 181.083 mm
As 624.574637
say S = 180 mm
at midspan
MB 1.767 x 10e6
Rn = = = 0.259 MPa
f b d22 0.90 x 1000 x (87 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.259
= x 1- 1- = 0.00063
415 0.85 x 28.0
As = f b d2
= ( 0.00337 ) ( 1000 ) ( 87 )
= 293.493976 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 385.357 mm
As 293.493976
say S = 380 mm
Given:
short side A: 2.5 m fc' = 28 mPa
long side B: 3m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 1.9 kPa conc. unit wt. = 23.5 kN/m3
SOLUTION:
2.50
ratio m = = 0.833 > 0.500 Two-way Slab!
3.00
2 ( 2.50 + 3.00 ) (1000)
h= = 61.111 mm
180
say h = 130 mm > hmin = 90 mm ok!
d1 = h - (cover) - (rebar f) = 84 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 72 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.13 ) ( 23.5 ) = 3.06 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.645 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.6( 5.65 ) = 6.774 kPa
WULL = 1.6 (LL) = 1.6 ( 1.9 ) = 3.04 kPa
WU = WUDL + WULL = 9.814 kPa
at midspan
for DL: 0.85 0.028
0.833 CADL
0.80 0.029
at midspan
for DL: 0.85 0.013
0.833 CBDL
0.80 0.01
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.705
= x 1- 1- = 0.00170
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
at midspan
MA 1.960 x 10e6
Rn = = = 0.309 MPa
fbd 1
2
0.90 x 1000 x (84 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.309
= x 1- 1- = 0.00074
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.372
= x 1- 1- = 0.00089
420 0.85 x 28.0
1.4 fc' 1.4 28
rmin = or = or
fy 4 fy 420 4 x 420
= 0.00333333 or 0.0031497 Therefore, use 0.00333
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
at midspan
MB 1.251 x 10e6
Rn = = = 0.268 MPa
f b d22 0.90 x 1000 x (72 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.268
= x 1- 1- = 0.00064
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
F ONE-WAY SLAB
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab length
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants for computing h and Mu.
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. For the design of sections having different moments, just replace tha value of
denominator for Mu for that corresponding section.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
0.90 0.025
0.574 CA
0.85 0.029
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
0.60 0.036
0.574 CA
0.55 0.037
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
SLAB DESIGN
Given:
live load: 3.8 kPa fc' = 28 mPa
fy = 420 mPa L: 1.25 m
floor finish: 1.1 kPa f = 0.9 cover = 20 mm
ceiling finish: 0.24 kPa f 1
= 0.85
mech. duct allowance: 0.25 kPa conc. unit wt.= 23.5 kN/m3
electrical load: 0 kPa
partition load: 0 kPa using 12 mm rebars
miscellaneous load: 1 kPa Ad = 113.10 mm2
Solution:
minimum slab thickness, h
L ( 1.25 ) ( 1000 )
h= = = 44.64 mm
28 28
say h = 100 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.1 ) ( 23.5 ) = 2.35 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
4.94 kPa
Factored Load:
WUDL= 1.4 (DL) = 1.4 ( 4.94 ) = 6.916 kPa
WULL= 1.7 (LL) = 1.7 ( 3.8 ) = 6.46 kPa
WU = WUDL + WULL = 13.376 kPa
At END 1 :
Wu L2 ( 13.376 ) ( 1.25 )2
Mu = = = 1.9000 kN-m
11 11
MU 1.900 x 10e6
Rn = = = 0.386 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.386
= x 1- 1- = 0.00093
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At MIDSPAN :
Wu L2 ( 13.376 ) ( 1.25 )2
Mu = = = 1.3063 kN-m
16 16
MU 1.306 x 10e6
Rn = = = 0.265 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.265
= x 1- 1- = 0.00063
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At END 2 :
Wu L2 ( 13.376 ) ( 1.25 )2
Mu = = = 1.9000 kN-m
11 11
MU 1.900 x 10e6
Rn = = = 0.386 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.386
= x 1- 1- = 0.00093
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
temperature bars :
Ast = 0.0018 bh
= 0.0018 ( 1000 ) ( 100 )
= 180 mm2
say S = 620 mm
Therefore, CA =
Smax = 5h = 5 ( 100 ) = 500 mm or 450 mm
Therefore, Smax = 450 mm
Given:
short side A: 3m fc' = 28 mPa
long side B: 5m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 1.9 kPa conc. unit wt.= 23.5 kN/m3
SOLUTION:
3.00
ratio m = = 0.600 > 0.500 Two-way Slab!
5.00
d1 = h - (cover) - (rebar f) = 99 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 87 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.125 ) ( 23.5 ) = 2.94 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0 kPa
electrical load = 0.25 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.53 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.2( 5.53 ) = 6.633 kPa
WULL = 1.6 (LL) = 1.6 ( 1.9 ) = 3.04 kPa
WU = WUDL + WULL = 9.673 kPa
at midspan
MADL = (WuDL) (CADL) (A2)
= 2.865 kN-m
MALL = (WuLL) (CALL) (A2)
= 1.778 kN-m
MA = MADL + MALL = 4.644 kN-m
at midspan
MBDL = (WuDL) (CBDL) (B2)
= 1.161 kN-m
MBLL = (WuLL) (CBLL) (B2)
= 0.684 kN-m
MB = MBDL + MBLL = 1.845 kN-m
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 6.965 x 10e6
Rn = = = 0.790 MPa
f b d12 0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.790
= x 1- 1- = 0.00191
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 99 )
= 330 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 342.727 mm
As 330
say S = 340 mm
at midspan
MA 4.644 x 10e6
Rn = = = 0.526 MPa
fbd 1
2
0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.526
= x 1- 1- = 0.00127
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 99 )
= 330 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 342.727 mm
As 330
say S = 340 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.639
= x 1- 1- = 0.00154
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 87 )
= 290 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 390 mm
As 290
say S = 390 mm
at midspan
MB 1.845 x 10e6
Rn = = = 0.271 MPa
f b d22 0.90 x 1000 x (87 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.271
= x 1- 1- = 0.00065
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 87 )
= 290 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 390 mm
As 290
say S = 390 mm
Given:
short side A: 3m fc' = 28 mPa
long side B: 5m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 3.8 kPa conc. unit wt. = 23.5 kN/m3
SOLUTION:
3.00
ratio m = = 0.6 > 0.500 Two-way Slab!
5.00
2 ( 3.00 + 5.00 ) (1000)
h= = 88.889 mm
180
say h = 130 mm > hmin = 90 mm ok!
d1 = h - (cover) - (rebar f) = 84 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 72 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.13 ) ( 23.5 ) = 3.06 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.645 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.6( 5.65 ) = 6.774 kPa
WULL = 1.6 (LL) = 1.6 ( 3.8 ) = 6.08 kPa
WU = WUDL + WULL = 12.854 kPa
at midspan
for DL: 0.6 0.04
0.600 CADL
0.55 0.044
at midspan
for DL: 0.6 0.011
0.600 CBDL
0.55 0.009
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.239
= x 1- 1- = 0.00303
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
at midspan
MA 5.886 x 10e6
Rn = = = 0.927 MPa
fbd 1
2
0.90 x 1000 x (84 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.927
= x 1- 1- = 0.00225
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.997
= x 1- 1- = 0.00497
420 0.85 x 28.0
1.4 fc' 1.4 28
rmin = or = or
fy 4 fy 420 4 x 420
= 0.00333333 or 0.0031497 Therefore, use 0.00333
As = f b d2
= ( 0.00497 ) ( 1000 ) ( 72 )
= 358.132379 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 315.805 mm
As 358.132379
say S = 310 mm
at midspan
MB 3.991 x 10e6
Rn = = = 0.855 MPa
f b d22 0.90 x 1000 x (72 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.855
= x 1- 1- = 0.00207
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
F ONE-WAY SLAB
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab length
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants for computing h and Mu.
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. For the design of sections having different moments, just replace tha value of
denominator for Mu for that corresponding section.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
0.90 0.025
0.600 CA
0.85 0.029
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
0.90 0.022
0.600 CA
0.85 0.019
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
SLAB DESIGN
Given:
live load: 3.8 kPa fc' = 28 mPa
fy = 420 mPa L: 1.25 m
floor finish: 1.1 kPa f = 0.9 cover = 20 mm
ceiling finish: 0.24 kPa f 1
= 0.85
mech. duct allowance: 0.25 kPa conc. unit wt.= 23.5 kN/m3
electrical load: 0 kPa
partition load: 0 kPa using 12 mm rebars
miscellaneous load: 1 kPa Ad = 113.10 mm2
Solution:
minimum slab thickness, h
L ( 1.25 ) ( 1000 )
h= = = 44.64 mm
28 28
say h = 100 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.1 ) ( 23.5 ) = 2.35 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
4.94 kPa
Factored Load:
WUDL= 1.4 (DL) = 1.4 ( 4.94 ) = 6.916 kPa
WULL= 1.7 (LL) = 1.7 ( 3.8 ) = 6.46 kPa
WU = WUDL + WULL = 13.376 kPa
At END 1 :
Wu L2 ( 13.376 ) ( 1.25 )2
Mu = = = 1.9000 kN-m
11 11
MU 1.900 x 10e6
Rn = = = 0.386 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.386
= x 1- 1- = 0.00093
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At MIDSPAN :
Wu L2 ( 13.376 ) ( 1.25 )2
Mu = = = 1.3063 kN-m
16 16
MU 1.306 x 10e6
Rn = = = 0.265 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.265
= x 1- 1- = 0.00063
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At END 2 :
Wu L2 ( 13.376 ) ( 1.25 )2
Mu = = = 1.9000 kN-m
11 11
MU 1.900 x 10e6
Rn = = = 0.386 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.386
= x 1- 1- = 0.00093
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
temperature bars :
Ast = 0.0018 bh
= 0.0018 ( 1000 ) ( 100 )
= 180 mm2
say S = 620 mm
Therefore, CA =
Smax = 5h = 5 ( 100 ) = 500 mm or 450 mm
Therefore, Smax = 450 mm
Given:
short side A: 3m fc' = 28 mPa
long side B: 5m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 3.8 kPa conc. unit wt.= 23.5 kN/m3
SOLUTION:
3.00
ratio m = = 0.600 > 0.500 Two-way Slab!
5.00
d1 = h - (cover) - (rebar f) = 99 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 87 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.125 ) ( 23.5 ) = 2.94 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0 kPa
electrical load = 0.25 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.53 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.2( 5.53 ) = 6.633 kPa
WULL = 1.6 (LL) = 1.6 ( 3.8 ) = 6.08 kPa
WU = WUDL + WULL = 12.713 kPa
at midspan
MADL = (WuDL) (CADL) (A2)
= 2.030 kN-m
MALL = (WuLL) (CALL) (A2)
= 3.174 kN-m
MA = MADL + MALL = 5.203 kN-m
at midspan
MBDL = (WuDL) (CBDL) (B2)
= 0.663 kN-m
MBLL = (WuLL) (CBLL) (B2)
= 1.064 kN-m
MB = MBDL + MBLL = 1.727 kN-m
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 9.268 x 10e6
Rn = = = 1.051 MPa
f b d12 0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.051
= x 1- 1- = 0.00256
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 99 )
= 330 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 342.727 mm
As 330
say S = 340 mm
at midspan
MA 5.203 x 10e6
Rn = = = 0.590 MPa
fbd 1
2
0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.590
= x 1- 1- = 0.00142
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 99 )
= 330 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 342.727 mm
As 330
say S = 340 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.467
= x 1- 1- = 0.00112
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 87 )
= 290 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 390 mm
As 290
say S = 390 mm
at midspan
MB 1.727 x 10e6
Rn = = = 0.254 MPa
f b d22 0.90 x 1000 x (87 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.254
= x 1- 1- = 0.00061
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 87 )
= 290 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 390 mm
As 290
say S = 390 mm
Given:
short side A: 3.5 m fc' = 28 mPa
long side B: 4.5 m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 1.9 kPa conc. unit wt. = 23.5 kN/m3
SOLUTION:
3.50
ratio m = = 0.778 > 0.500 Two-way Slab!
4.50
2 ( 3.50 + 4.50 ) (1000)
h= = 88.889 mm
180
say h = 130 mm > hmin = 90 mm ok!
d1 = h - (cover) - (rebar f) = 84 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 72 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.13 ) ( 23.5 ) = 3.06 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.645 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.6( 5.65 ) = 6.774 kPa
WULL = 1.6 (LL) = 1.6 ( 1.9 ) = 3.04 kPa
WU = WUDL + WULL = 9.814 kPa
at midspan
for DL: 0.8 0.026
0.778 CADL
0.75 0.028
at midspan
for DL: 0.8 0.023
0.778 CBDL
0.75 0.019
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.264
= x 1- 1- = 0.00309
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
at midspan
MA 3.824 x 10e6
Rn = = = 0.602 MPa
fbd 1
2
0.90 x 1000 x (84 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.602
= x 1- 1- = 0.00145
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.055
= x 1- 1- = 0.00257
420 0.85 x 28.0
1.4 fc' 1.4 28
rmin = or = or
fy 4 fy 420 4 x 420
= 0.00333333 or 0.0031497 Therefore, use 0.00333
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
at midspan
MB 3.876 x 10e6
Rn = = = 0.831 MPa
f b d22 0.90 x 1000 x (72 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.831
= x 1- 1- = 0.00201
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
F ONE-WAY SLAB
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab length
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants for computing h and Mu.
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. For the design of sections having different moments, just replace tha value of
denominator for Mu for that corresponding section.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
0.90 0.025
0.600 CA
0.85 0.029
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
0.60 0.034
0.600 CA
0.55 0.035
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
SLAB DESIGN
Given:
live load: 1.9 kPa fc' = 28 mPa
fy = 420 mPa L: 1.25 m
floor finish: 1.1 kPa f = 0.9 cover = 20 mm
ceiling finish: 0.24 kPa f 1
= 0.85
mech. duct allowance: 0.25 kPa conc. unit wt.= 23.5 kN/m3
electrical load: 0 kPa
partition load: 0 kPa using 12 mm rebars
miscellaneous load: 1 kPa Ad = 113.10 mm2
Solution:
minimum slab thickness, h
L ( 1.25 ) ( 1000 )
h= = = 44.64 mm
28 28
say h = 100 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.1 ) ( 23.5 ) = 2.35 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
4.94 kPa
Factored Load:
WUDL= 1.4 (DL) = 1.4 ( 4.94 ) = 6.916 kPa
WULL= 1.7 (LL) = 1.7 ( 1.9 ) = 3.23 kPa
WU = WUDL + WULL = 10.146 kPa
At END 1 :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 1.4412 kN-m
11 11
MU 1.441 x 10e6
Rn = = = 0.292 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.292
= x 1- 1- = 0.00070
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At MIDSPAN :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 0.9908 kN-m
16 16
MU 0.991 x 10e6
Rn = = = 0.201 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.201
= x 1- 1- = 0.00048
420 0.85 x 28.0
As = f b d
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
At END 2 :
Wu L2 ( 10.146 ) ( 1.25 )2
Mu = = = 1.4412 kN-m
11 11
MU 1.441 x 10e6
Rn = = = 0.292 MPa
f b d12 0.90 x 1000 x (74 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.292
= x 1- 1- = 0.00070
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 74 )
= 246.666667 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 458.514 mm
As 246.666667
say S = 450 mm
temperature bars :
Ast = 0.0018 bh
= 0.0018 ( 1000 ) ( 100 )
= 180 mm2
say S = 620 mm
Therefore, CA =
Smax = 5h = 5 ( 100 ) = 500 mm or 450 mm
Therefore, Smax = 450 mm
Given:
short side A: 3.5 m fc' = 28 mPa
long side B: 7m fy = 415 mPa
f = 0.9
LOADS: f = 0.85
live load: 3.8 kPa conc. unit wt.= 23.5 kN/m3
SOLUTION:
3.50
ratio m = = 0.500 = 0.500 Two-way Slab!
7.00
d1 = h - (cover) - (rebar f) = 99 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 87 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.125 ) ( 23.5 ) = 2.94 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0 kPa
electrical load = 0.25 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.53 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.2( 5.53 ) = 6.633 kPa
WULL = 1.6 (LL) = 1.6 ( 3.8 ) = 6.08 kPa
WU = WUDL + WULL = 12.713 kPa
at midspan
MADL = (WuDL) (CADL) (A2)
= 2.438 kN-m
MALL = (WuLL) (CALL) (A2)
= 3.650 kN-m
MA = MADL + MALL = 6.087 kN-m
at midspan
MBDL = (WuDL) (CBDL) (B2)
= 2.275 kN-m
MBLL = (WuLL) (CBLL) (B2)
= 3.575 kN-m
MB = MBDL + MBLL = 5.850 kN-m
Strength Design:
A. Short Span, Middle Strip
at continuous edge
MA 11.524 x 10e6
Rn = = = 1.306 MPa
f b d12 0.90 x 1000 x (99 )
2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.306
= x 1- 1- = 0.00324
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
at midspan
MA 6.087 x 10e6
Rn = = = 0.690 MPa
fbd 1
2
0.90 x 1000 x (99 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.690
= x 1- 1- = 0.00169
415 0.85 x 28.0
As = f b d1
= ( 0.00337 ) ( 1000 ) ( 99 )
= 333.975904 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 338.647 mm
As 333.975904
say S = 330 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.555
= x 1- 1- = 0.00388
415 0.85 x 28.0
As = f b d2
= ( 0.00388 ) ( 1000 ) ( 87 )
= 337.300458 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 335.309 mm
As 337.300458
say S = 330 mm
at midspan
MB 5.850 x 10e6
Rn = = = 0.859 MPa
f b d22 0.90 x 1000 x (87 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.859
= x 1- 1- = 0.00211
415 0.85 x 28.0
As = f b d2
= ( 0.00337 ) ( 1000 ) ( 87 )
= 293.493976 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 385.357 mm
As 293.493976
say S = 380 mm
Given:
short side A: 3.5 m fc' = 28 mPa
long side B: 5m fy = 420 mPa
f = 0.9
LOADS: f = 0.85
live load: 1.9 kPa conc. unit wt. = 23.5 kN/m3
SOLUTION:
3.50
ratio m = = 0.7 > 0.500 Two-way Slab!
5.00
2 ( 3.50 + 5.00 ) (1000)
h= = 94.444 mm
180
say h = 130 mm > hmin = 90 mm ok!
d1 = h - (cover) - (rebar f) = 84 mm
d2 = h - (cover) - (rebar f) - (half of rebar f) = 72 mm
Dead Loads:
slab self-weight = h x conc. unit wt.= ( 0.13 ) ( 23.5 ) = 3.06 kPa
floor finish = 1.1 kPa
ceiling finish = 0.24 kPa
mech. duct allowance = 0.25 kPa
electrical load = 0 kPa
partition load = 0 kPa
miscellaneous loads = 1 kPa
5.645 kPa
Factored Load:
WUDL = 1.2 (DL) = 1.6( 5.65 ) = 6.774 kPa
WULL = 1.6 (LL) = 1.6 ( 1.9 ) = 3.04 kPa
WU = WUDL + WULL = 9.814 kPa
at midspan
for DL: 0.7 0.026
0.700 CADL
0.65 0.028
at midspan
for DL: 0.7 0.023
0.700 CBDL
0.65 0.019
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.231
= x 1- 1- = 0.00301
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
at midspan
MA 3.684 x 10e6
Rn = = = 0.580 MPa
fbd 1
2
0.90 x 1000 x (84 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 0.580
= x 1- 1- = 0.00140
420 0.85 x 28.0
As = f b d1
= ( 0.00333 ) ( 1000 ) ( 84 )
= 280 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 403.929 mm
As 280
say S = 400 mm
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.420
= x 1- 1- = 0.00349
420 0.85 x 28.0
1.4 fc' 1.4 28
rmin = or = or
fy 4 fy 420 4 x 420
= 0.00333333 or 0.0031497 Therefore, use 0.00333
As = f b d2
= ( 0.00349 ) ( 1000 ) ( 72 )
= 251.131586 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 450.362 mm
As 251.131586
say S = 450 mm
at midspan
MB 5.187 x 10e6
Rn = = = 1.112 MPa
f b d22 0.90 x 1000 x (72 ) 2
0.85 fc' 2 Rn
r = x 1- 1-
fy 0.85 fc'
(0.85)( 28 ) 2 x 1.112
= x 1- 1- = 0.00271
420 0.85 x 28.0
As = f b d2
= ( 0.00333 ) ( 1000 ) ( 72 )
= 240 mm2
using 12 mm bars
Ad (1000) ( 113.10) (1000)
S= = = 471.25 mm
As 240
say S = 470 mm
F ONE-WAY SLAB
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab length
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants for computing h and Mu.
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. For the design of sections having different moments, just replace tha value of
denominator for Mu for that corresponding section.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
0.90 0.025
0.500 CA
0.85 0.029
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.
0.60 0.034
0.500 CA
0.55 0.035
RESULTING TABLE
Middle Strip Column Strip
SLAB
As (mm2) S (mm) As (mm2) S (mm)
GUIDELINES:
1. Fill-up only colored cells with their corresponding values.
slab dimensions
concrete stress and strain
type of loading
miscellaneous dead loads
rebars diameter and concrete cover
constants from the table of values
2. Avoid editing non-colored cells for it may cause unreasonable design.
3. Give the exact dimensions of the slab. Don't forget to subtract the supporting
beam dimensions.
4. Checking computations using calculator may will not match with the computer's
computations due to rounding-off numbers. Computer uses complete decimal
numbers and exact values.
5. Having discontinuous edge will depend upon the case of the slab.
As seen on the table, depends on slab's case.