Proposal of Exhaust & Make-Up Air for Pantries in Guest Villa connected to
KEF - 01.
As per the kitchen appliance details received by mail by UCC Dated 21/11/2018, indicating changes in
Burner model and addition of pantry in Family Villa Second Floor, following is the proposal and
calculation indicating the changes in the current available services on site.
Therefore total Exhaust requirements for 4.7 / 0.03 = 157 CFM ~ 74 LPS.
Available Make-up Fresh Air from ERU – 01, through Transfer Duct = 65 LPS
Proposal:
This Additional make-up air (9 LPS) is attain by Transfer Ducts from surrounding area.
Therefore total Exhaust requirements for 1.057 / 0.03 = 35.2 CFM ~ 17 LPS.
Available Mechanical Services:
Proposal:
This Additional make-up air (17 LPS) from ERU -01 is diverted to Ground Floor.
Therefore total Exhaust requirements for 4.7 / 0.03 = 157 CFM ~ 74 LPS.
Available Make-up Fresh Air from ERU – 01, through Transfer Duct = 10 LPS
Proposal:
This Additional make-up air (64 LPS) is attain by Transfer Ducts from surrounding area.
Kitchen Exhaust Duct size in Guest Villa – Ground Floor – Dining Pantry is increase from 100 x 100 to
150 x 150 mm.
Available Make-up Fresh Air from ERU – 01, through Transfer Duct = 10 LPS
Proposal:
This Additional make-up air (64 LPS) is attain by Transfer Ducts from surrounding area.
Kitchen Exhaust Duct size in Guest Villa – Ground Floor – Majlis Pantry is increase from 100 x 100 to
150 x 150 mm & the connected Main exhaust duct of size is increase form 100 x 100 to 200 x 150.
Therefore total Exhaust requirements for 1.057 / 0.03 = 35.2 CFM ~ 17 LPS.
Proposal:
The Additional make-up air (7 LPS) is attain by Transfer Ducts from surrounding area.
Main Duct Kitchen Exhaust (K-EAD) size in Guest Villa – Basement Floor – is increase from 150 x 150 to
250 x 150 mm.
Basement Floor – Pantry (Corridor Lobby):
Therefore total Exhaust requirements for 1.057 / 0.03 = 35.2 CFM ~ 17 LPS.
Proposal:
The Additional make-up air (7 LPS) is attain by Transfer Ducts from surrounding area.
Main Duct Kitchen Exhaust (K-EAD) size in Guest Villa – Basement Floor – is increase from 150 x 150 to
250 x 150 mm.