You are on page 1of 6

Company: Project: Engineering Contractor:

OFFSITES ENGINEERING WORKS


FOR THE ERBIL REFINERY
40,000 B/D EXPANSION PROJECT

Contract no.: 10J01762-01


Company doc. no.: Job no.: 10J01762 Engineering doc. no.:
N/A Sheet 1 of 6 10J01762-ICT-DS-000-005

OFFSITES ENGINEERING WORKS FOR THE


ERBIL REFINERY 40,000 B/D EXPANSION PROJECT

DATA SHEET FOR PRESSURE TRANSMITTERS

D0 27/07/2011 Approved for Design Lucarelli Pagliardini Cilia


C0 30/03/2011 Issued for Company approval Mariotti Pagliardini Cilia
REV. DATE REVISION TITLE PREPARED CHECKED APPROVED

File name: 10J01762-ICT-DS-000-005-D0.doc Printed on 26/07/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR PRESSURE TRANSMITTERS
Company doc. no.: Rev.: C0 D0 Engineering doc. no.:
N/A Sheet 2 of 6 10J01762-ICT-DS-000-005

001 002 003


01 TAG NO. 3#-PIT-058A 3#-PIT-058B 3#-PIT-057
02 MANUFACTURER / MODEL NO. * *
03 TYPE Gauge Pressure Transmitter Gauge Pressure Transmitter Gauge Pressure Transmitter
GENERAL

05 P&ID 10J01762-PRO-DW-000-004 10J01762-PRO-DW-000-004 10J01762-PRO-DW-000-003


06 SERVICE Crude oil tank inlet Crude oil tank inlet Fuel oil to plant fuel tank
07 LINE/EQUIPMENT NO. 18”-AA1-CO-507-P 18”-AA1-CO-507-P 3”-AA1-FO-516-I
08 MOUNTING/WEIGHT Bracket on 2” standpipe / * Bracket on 2” standpipe / * Bracket on 2” standpipe / *
09 AMBIENT TEMPERATURE LIMITS 0÷50 °C 0÷50 °C 0÷50 °C
PROCESS DATA

10 DESIGN TEMP. / PRESSURE 0 ÷60 °C / 10 bar g 0 ÷60 °C / 10 bar g 0 ÷130 °C / 10 bar g


11 FLUID/PHASE Crude oil / liquid Crude oil / liquid Fuel oil / liquid
12 PRESSURE MIN/NORM/MAX 0.2 / 1.0 / 1.5 bar g 0.2 / 1.0 / 1.5 bar g 6.3 / - / 7.1 bar g
13 TEMPERATURE MIN/NORM/MAX 10/ 20/ 30 °C 10/ 20/ 30 °C -/ 100/ - °C
14 MAX STATIC PRESSURE 2 bar g 2 bar g 8.5 bar g (Note 2)
15 CALIBRATED INPUT RANGE 0÷4 bar g * 0÷4 bar g * 0÷10 bar g
16 CHARACTERISTIC Linear Linear Linear
INST.CHARACT.

17 ACCURACY / REPEATABILITY ±0.1% of span * ±0.1% of span * ±0.1% of span


18 LOWER/UPPER RANGE LIMITS * * *
19 MIN/MAX SPAN * * *
20 ZERO ADJUSTMENT Yes Yes Yes
21 RESPONSE TIME * * *
22 MAX STATIC PRESSURE * * *
23 TYPE electronic * electronic * electronic *
ELEMENT/SENSOR

24 MATERIAL,ELEMENT (SENSOR) AISI 316L AISI 316L AISI 316L


25 MATERIAL,SOCKET (INLET PORT) AISI 316 AISI 316 AISI 316
26 MATERIAL,SENSOR BOLTS/NUTS AISI 316 AISI 316 AISI 316
27 PROCESS CONN.SIZE/TYPE ½” NPT-F, with flange adapter ½” NPT-F, with flange adapter MFR STD – capillary connection
28 POSITION OF CONNECTION * * *
29 SOUR SERVICE SPEC. Not required Not required Not required
30 DIMENSION / MATERIAL / Aluminium epoxy coated * / Aluminium epoxy coated * / Aluminium epoxy coated *
31 ENCLOSURE PROTECTION IP 65 (min) IP 65 (min) IP 65 (min)
HOUSING

32 CABLE ENTRY ISO M20x1.5mm ISO M20x1.5mm ISO M20x1.5mm


33 EX. CLASSIFICATION Ex-d IIB-T3 / ATEX 94/9/EC Ex-d IIB-T3 / ATEX 94/9/EC Ex-d IIB-T3 / ATEX 94/9/EC
34 PROTECTIVE COATING Mfr. Std. Mfr. Std. Mfr. Std.
35 INDICATOR Integrated LCD display (barg units) Integr. LCD display (barg units) Integr. LCD display (barg units)
TRANSM.

36 OUTPUT SIGNAL/COMUNICATION 4-20 mA, 2 wire / HART 4-20 mA, 2 wire / HART 4-20 mA, 2 wire / HART
37 SUPPLY VOLTAGE 24 VDC (loop powered) 24 VDC (loop powered) 24 VDC (loop powered)
38 CONSUMPTION / LOAD LIMITATION * * *
39 TYPE Not required Not required Flush flanged remote seal(note 3)
40 MATERIAL, UPPER/LOWER PART - - AISI 316L
CHEMICAL SEAL

41 MATERIAL, BOLTS / NUTS - - ASTM A193 B7 / A 194 2H *


42 MATERIAL, DIAPHRAGM - - AISI 316L
43 FILL FLUID - - Silicone oil
44 CAPILLARY LENGTH/DIAMETER - - 2.0 m / ID 1mm *
45 MATERIAL,CAPILLARY/ARMOUR - - AISI 316L /Armored AISI-316
46 PROCESS CONN. SIZE/TYPE - - 1 ½” ANSI-300RF
47 INSTRUMENT CONN. SIZE/TYPE - - Capillary Remote coupling *
48 MOUNTING BRACKET Yes, 2” pipe bracket Yes, 2” pipe bracket Yes, 2” pipe bracket
49 MATERIAL, MOUNTING BRACKET AISI * AISI * AISI *
ACCESSORIES

50 MANIFOLD Not required Not required Not required


51 MANIFOLD MATERIAL
52 MANIFOLD PROCESS CONN.
53 MANIFOLD PRESSURE RATING
54 TROPICALIZATION Required (Mfr Std) Required (Mfr Std) Required (Mfr Std)
55 TAG / DATA PLATE MTL. Required / SS Required / SS Required / SS
NOTES:
(*) Information to be supplied or to be confirmed by Supplier.
(1) Supplier is required to provide, as a minimum, the following documents: technical bulletins, O&M manuals, manufacturing data book, quality book (with all test
reports, material certificates, mechanical/electrical protection certificates, calibration certificates...) as per purchaser requisition documents.
(2) Max static pressure pending on shut-off pressure of pump. This value shall be confirmed later
(3) Flashing ring included; flush ring connection 1 x ½” NPT-F, with Std plug.

File name: 10J01762-ICT-DS-000-005-D0.doc Printed on 26/07/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR PRESSURE TRANSMITTERS
Company doc. no.: Rev.: C0 D0 Engineering doc. no.:
N/A Sheet 3 of 6 10J01762-ICT-DS-000-005

004 005 006


01 TAG NO. 3#-PIT-053B 3#-PIT-053C 3#-PIT-064
02 MANUFACTURER / MODEL NO. * * *
03 TYPE Gauge Pressure Transmitter Gauge Pressure Transmitter Gauge Pressure Transmitter
GENERAL

05 P&ID 10J01762-PRO-DW-000-002-1 10J01762-PRO-DW-000-002-2 10J01762-PRO-DW-000-005-1


06 SERVICE Crude oil to refinery Crude oil to refinery Diesel oil to tanks
07 LINE/EQUIPMENT NO. 6”-BA1-CO-523-P 6”-BA1-CO-533-P 6”-AA1-DT-516-P
08 MOUNTING/WEIGHT Bracket on 2” standpipe / * Bracket on 2” standpipe / * Bracket on 2” standpipe / *
09 AMBIENT TEMPERATURE LIMITS 0÷50 °C 0÷50 °C 0÷50 °C
PROCESS DATA

10 DESIGN TEMP. / PRESSURE 0 ÷60 °C / 25 bar g 0 ÷60 °C / 25 bar g 0 ÷80 °C / 16 bar g


11 FLUID/PHASE Crude oil / liquid Crude oil / liquid Fuel oil / liquid
12 PRESSURE MIN/NORM/MAX 18.0 / - / 18.9 bar g 18.0 / - / 18.9 bar g 5.0 / - / 5.6 bar g
13 TEMPERATURE MIN/NORM/MAX 10/ 20/ 30 °C 10/ 20/ 30 °C 38 / - / 50 °C
14 MAX STATIC PRESSURE 22.5 bar g (Note 2) 22.5 bar g (Note 2) 7.0 bar g (Note 2)
15 CALIBRATED INPUT RANGE 0÷30 bar g * 0÷30 bar g * 0÷10 bar g *
16 CHARACTERISTIC Linear Linear Linear
INST.CHARACT.

17 ACCURACY / REPEATABILITY ±0.1% of span * ±0.1% of span * ±0.1% of span *


18 LOWER/UPPER RANGE LIMITS * * *
19 MIN/MAX SPAN * * *
20 ZERO ADJUSTMENT Yes Yes Yes
21 RESPONSE TIME * * *
22 MAX STATIC PRESSURE * * *
23 TYPE electronic * electronic * electronic *
ELEMENT/SENSOR

24 MATERIAL,ELEMENT (SENSOR) AISI 316L AISI 316L AISI 316L


25 MATERIAL,SOCKET (INLET PORT) AISI 316 AISI 316 AISI 316
26 MATERIAL,SENSOR BOLTS/NUTS AISI 316 AISI 316 AISI 316
27 PROCESS CONN.SIZE/TYPE ½” NPT-F, with flange adapter ½” NPT-F, with flange adapter ½” NPT-F, with flange adapter
28 POSITION OF CONNECTION * * *
29 SOUR SERVICE SPEC. Not required Not required Not required
30 DIMENSION / MATERIAL / Aluminium epoxy coated * / Aluminium epoxy coated * / Aluminium epoxy coated *
31 ENCLOSURE PROTECTION IP 65 (min) IP 65 (min) IP 65 (min)
HOUSING

32 CABLE ENTRY ISO M20x1.5mm ISO M20x1.5mm ISO M20x1.5mm


33 EX. CLASSIFICATION Ex-d IIB-T3 / ATEX 94/9/EC Ex-d IIB-T3 / ATEX 94/9/EC Ex-d IIB-T3 / ATEX 94/9/EC
34 PROTECTIVE COATING Mfr. Std. Mfr. Std. Mfr. Std.
35 INDICATOR Integrated LCD display (barg units) Integr. LCD display (barg units) Integr. LCD display (barg units)
TRANSM.

36 OUTPUT SIGNAL/COMUNICATION 4-20 mA, 2 wire / HART 4-20 mA, 2 wire / HART 4-20 mA, 2 wire / HART
37 SUPPLY VOLTAGE 24 VDC (loop powered) 24 VDC (loop powered) 24 VDC (loop powered)
38 CONSUMPTION / LOAD LIMITATION * * *
39 TYPE Not required Not required Not required
40 MATERIAL, UPPER/LOWER PART - - -
CHEMICAL SEAL

41 MATERIAL, BOLTS / NUTS - - -


42 MATERIAL, DIAPHRAGM - - -
43 FILL FLUID - - -
44 CAPILLARY LENGTH/DIAMETER - - -
45 MATERIAL,CAPILLARY/ARMOUR - - -
46 PROCESS CONN. SIZE/TYPE - - -
47 INSTRUMENT CONN. SIZE/TYPE - - -
48 MOUNTING BRACKET Yes, 2” pipe bracket Yes, 2” pipe bracket Yes, 2” pipe bracket
49 MATERIAL, MOUNTING BRACKET AISI * AISI * AISI *
ACCESSORIES

50 MANIFOLD Not required Not required Not required


51 MANIFOLD MATERIAL
52 MANIFOLD PROCESS CONN.
53 MANIFOLD PRESSURE RATING
54 TROPICALIZATION Required (Mfr Std) Required (Mfr Std) Required (Mfr Std)
55 TAG / DATA PLATE MTL. Required / SS Required / SS Required / SS
NOTES:
(*) Information to be supplied or to be confirmed by Supplier.
(1) Supplier is required to provide, as a minimum, the following documents: technical bulletins, O&M manuals, manufacturing data book, quality book (with all test
reports, material certificates, mechanical/electrical protection certificates, calibration certificates...) as per purchaser requisition documents.
(2) Max static pressure pending on shut-off pressure of pump. This value shall be confirmed later

File name: 10J01762-ICT-DS-000-005-D0.doc Printed on 26/07/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR PRESSURE TRANSMITTERS
Company doc. no.: Rev.: C0 D0 Engineering doc. no.:
N/A Sheet 4 of 6 10J01762-ICT-DS-000-005

007 008 009


01 TAG NO. 3#-PIT-068 3#-PIT-072 3#-PIT-076
02 MANUFACTURER / MODEL NO. * * *
03 TYPE Gauge Pressure Transmitter Gauge Pressure Transmitter Gauge Pressure Transmitter
GENERAL

05 P&ID 10J01762-PRO-DW-000-006 10J01762-PRO-DW-000-007 10J01762-PRO-DW-000-008


06 SERVICE Kerosene to loading area Naphtha to loading area HDT Naphtha to refinery
07 LINE/EQUIPMENT NO. 6”-AA1-KE-513-P 6”-AA1-NA-513-P 4”-AA1-NA-525-P
08 MOUNTING/WEIGHT Bracket on 2” standpipe / * Bracket on 2” standpipe / * Bracket on 2” standpipe / *
09 AMBIENT TEMPERATURE LIMITS 0÷50 °C 0÷50 °C 0÷50 °C
PROCESS DATA

10 DESIGN TEMP. / PRESSURE 0 ÷80 °C / 16 bar g 0 ÷80 °C / 16 bar g 0 ÷80 °C / 13.8 bar g
11 FLUID/PHASE Kerosene / liquid Naphtha / liquid HDT Naphtha / liquid
12 PRESSURE MIN/NORM/MAX 4.7 / - / 5.3 bar g 4.0 / - / 7.2 bar g 7.1 / - / 7.7 bar g
13 TEMPERATURE MIN/NORM/MAX 38 / - / 50 °C 38 / - / 50 °C 38 / - / 50 °C
14 MAX STATIC PRESSURE 6.5 bar g (Note 2) 9.0 bar g (Note 2) 9.5 bar g (Note 2)
15 CALIBRATED INPUT RANGE 0÷10 bar g * 0÷20 bar g * 0÷20 bar g *
16 CHARACTERISTIC Linear Linear Linear
INST.CHARACT.

17 ACCURACY / REPEATABILITY ±0.1% of span * ±0.1% of span * ±0.1% of span *


18 LOWER/UPPER RANGE LIMITS * * *
19 MIN/MAX SPAN * * *
20 ZERO ADJUSTMENT Yes Yes Yes
21 RESPONSE TIME * * *
22 MAX STATIC PRESSURE * * *
23 TYPE electronic * electronic * electronic *
ELEMENT/SENSOR

24 MATERIAL,ELEMENT (SENSOR) AISI 316L AISI 316L AISI 316L


25 MATERIAL,SOCKET (INLET PORT) AISI 316 AISI 316 AISI 316
26 MATERIAL,SENSOR BOLTS/NUTS AISI 316 AISI 316 AISI 316
27 PROCESS CONN.SIZE/TYPE ½” NPT-F, with flange adapter ½” NPT-F, with flange adapter ½” NPT-F, with flange adapter
28 POSITION OF CONNECTION * * *
29 SOUR SERVICE SPEC. Not required Not required Not required
30 DIMENSION / MATERIAL / Aluminium epoxy coated * / Aluminium epoxy coated * / Aluminium epoxy coated *
31 ENCLOSURE PROTECTION IP 65 (min) IP 65 (min) IP 65 (min)
HOUSING

32 CABLE ENTRY ISO M20x1.5mm ISO M20x1.5mm ISO M20x1.5mm


33 EX. CLASSIFICATION Ex-d IIB-T3 / ATEX 94/9/EC Ex-d IIB-T3 / ATEX 94/9/EC Ex-d IIB-T3 / ATEX 94/9/EC
34 PROTECTIVE COATING Mfr. Std. Mfr. Std. Mfr. Std.
35 INDICATOR Integrated LCD display (barg units) Integr. LCD display (barg units) Integr. LCD display (barg units)
TRANSM.

36 OUTPUT SIGNAL/COMUNICATION 4-20 mA, 2 wire / HART 4-20 mA, 2 wire / HART 4-20 mA, 2 wire / HART
37 SUPPLY VOLTAGE 24 VDC (loop powered) 24 VDC (loop powered) 24 VDC (loop powered)
38 CONSUMPTION / LOAD LIMITATION * * *
39 TYPE Not required Not required Not required
40 MATERIAL, UPPER/LOWER PART - -
CHEMICAL SEAL

41 MATERIAL, BOLTS / NUTS - -


42 MATERIAL, DIAPHRAGM - -
43 FILL FLUID - -
44 CAPILLARY LENGTH/DIAMETER - -
45 MATERIAL,CAPILLARY/ARMOUR - -
46 PROCESS CONN. SIZE/TYPE - -
47 INSTRUMENT CONN. SIZE/TYPE - -
48 MOUNTING BRACKET Yes, 2” pipe bracket Yes, 2” pipe bracket Yes, 2” pipe bracket
49 MATERIAL, MOUNTING BRACKET AISI * AISI * AISI *
ACCESSORIES

50 MANIFOLD Not required Not required Not required


51 MANIFOLD MATERIAL
52 MANIFOLD PROCESS CONN.
53 MANIFOLD PRESSURE RATING
54 TROPICALIZATION Required (Mfr Std) Required (Mfr Std) Required (Mfr Std)
55 TAG / DATA PLATE MTL. Required / SS Required / SS Required / SS
NOTES:
(*) Information to be supplied or to be confirmed by Supplier.
(1) Supplier is required to provide, as a minimum, the following documents: technical bulletins, O&M manuals, manufacturing data book, quality book (with all test
reports, material certificates, mechanical/electrical protection certificates, calibration certificates...) as per purchaser requisition documents.
(2) Max static pressure pending on shut-off pressure of pump. This value shall be confirmed later

File name: 10J01762-ICT-DS-000-005-D0.doc Printed on 26/07/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR PRESSURE TRANSMITTERS
Company doc. no.: Rev.: C0 D0 Engineering doc. no.:
N/A Sheet 5 of 6 10J01762-ICT-DS-000-005

010 011 012


01 TAG NO. 3#-PIT-080 3#-PIT-084 3#-PIT-113
02 MANUFACTURER / MODEL NO. * * *
03 TYPE Gauge Pressure Transmitter Gauge Pressure Transmitter Gauge Pressure Transmitter
GENERAL

05 P&ID 10J01762-PRO-DW-000-009-1 10J01762-PRO-DW-000-010 10J01762-PRO-DW-000-015


06 SERVICE Gasoline to loading area Slop storage Sour water system
07 LINE/EQUIPMENT NO. 6”-AA1-GL-513-P 6”-AA1-SO-510-P 3”-AA3-ZW-507-P
08 MOUNTING/WEIGHT Bracket on 2” standpipe / * Bracket on 2” standpipe / * Bracket on 2” standpipe / *
09 AMBIENT TEMPERATURE LIMITS 0÷50 °C 0÷50 °C 0÷50 °C
PROCESS DATA

10 DESIGN TEMP. / PRESSURE 0 ÷80 °C / 10 bar g 0 ÷90 °C / 10 bar g 0 ÷ 87 °C / 10 bar g


11 FLUID/PHASE Gasoline / liquid Slop / liquid Water / liquid
12 PRESSURE MIN/NORM/MAX 4.5 / - / 5.1 bar g 4.0 / - / 5.6 bar g 5.9 / - / 6.2 bar g
13 TEMPERATURE MIN/NORM/MAX 38 / - / 50 °C 38 / - / 60 °C 57 °C
14 MAX STATIC PRESSURE 6.0 bar g (Note 2) 6.5 bar g (Note 2) 7.5 bar g (Note 2)
15 CALIBRATED INPUT RANGE 0÷10 bar g * 0÷10 bar g * 0÷10 bar g *
16 CHARACTERISTIC Linear Linear Linear
INST.CHARACT.

17 ACCURACY / REPEATABILITY ±0.1% of span * ±0.1% of span * ±0.1% of span *


18 LOWER/UPPER RANGE LIMITS * * *
19 MIN/MAX SPAN * * *
20 ZERO ADJUSTMENT Yes Yes Yes
21 RESPONSE TIME * * *
22 MAX STATIC PRESSURE * * *
23 TYPE electronic * electronic * electronic *
ELEMENT/SENSOR

24 MATERIAL,ELEMENT (SENSOR) AISI 316L AISI 316L AISI 316L


25 MATERIAL,SOCKET (INLET PORT) AISI 316 AISI 316 AISI 316
26 MATERIAL,SENSOR BOLTS/NUTS AISI 316 AISI 316 AISI 316
27 PROCESS CONN.SIZE/TYPE ½” NPT-F, with flange adapter ½” NPT-F, with flange adapter ½” NPT-F, with flange adapter
28 POSITION OF CONNECTION * * *
29 SOUR SERVICE SPEC. Not required Not required NACE MR 0175
30 DIMENSION / MATERIAL / Aluminium epoxy coated * / Aluminium epoxy coated * / Aluminium epoxy coated *
31 ENCLOSURE PROTECTION IP 65 (min) IP 65 (min) IP 65 (min)
HOUSING

32 CABLE ENTRY ISO M20x1.5mm ISO M20x1.5mm ISO M20x1.5mm


33 EX. CLASSIFICATION Ex-d IIB-T3 / ATEX 94/9/EC Ex-d IIB-T3 / ATEX 94/9/EC Ex-d IIB-T3 / ATEX 94/9/EC
34 PROTECTIVE COATING Mfr. Std. Mfr. Std. Mfr. Std.
35 INDICATOR Integrated LCD display (barg units) Integr. LCD display (barg units) Integr. LCD display (barg units)
TRANSM.

36 OUTPUT SIGNAL/COMUNICATION 4-20 mA, 2 wire / HART 4-20 mA, 2 wire / HART 4-20 mA, 2 wire / HART
37 SUPPLY VOLTAGE 24 VDC (loop powered) 24 VDC (loop powered) 24 VDC (loop powered)
38 CONSUMPTION / LOAD LIMITATION * * *
39 TYPE Not required Not required Not required
40 MATERIAL, UPPER/LOWER PART - -
CHEMICAL SEAL

41 MATERIAL, BOLTS / NUTS - -


42 MATERIAL, DIAPHRAGM - -
43 FILL FLUID - -
44 CAPILLARY LENGTH/DIAMETER - -
45 MATERIAL,CAPILLARY/ARMOUR - -
46 PROCESS CONN. SIZE/TYPE - -
47 INSTRUMENT CONN. SIZE/TYPE - -
48 MOUNTING BRACKET Yes, 2” pipe bracket Yes, 2” pipe bracket Yes, 2” pipe bracket
49 MATERIAL, MOUNTING BRACKET AISI * AISI * AISI *
ACCESSORIES

50 MANIFOLD Not required Not required Not required


51 MANIFOLD MATERIAL
52 MANIFOLD PROCESS CONN.
53 MANIFOLD PRESSURE RATING
54 TROPICALIZATION Required (Mfr Std) Required (Mfr Std) Required (Mfr Std)
55 TAG / DATA PLATE MTL. Required / SS Required / SS Required / SS
NOTES:
(*) Information to be supplied or to be confirmed by Supplier.
(1) Supplier is required to provide, as a minimum, the following documents: technical bulletins, O&M manuals, manufacturing data book, quality book (with all test
reports, material certificates, mechanical/electrical protection certificates, calibration certificates...) as per purchaser requisition documents.
(2) Max static pressure pending on shut-off pressure of pump. This value shall be confirmed later

File name: 10J01762-ICT-DS-000-005-D0.doc Printed on 26/07/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR PRESSURE TRANSMITTERS
Company doc. no.: Rev.: C0 D0 Engineering doc. no.:
N/A Sheet 6 of 6 10J01762-ICT-DS-000-005

013 014 015


01 TAG NO. 3#-PIT-114 3#-PIT-116 3#-PIT-120
02 MANUFACTURER / MODEL NO. * * *
03 TYPE Gauge Pressure Transmitter Gauge Pressure Transmitter Gauge Pressure Transmitter
GENERAL

05 P&ID 10J01762-PRO-DW-000-015 10J01762-PRO-DW-000-006 10J01762-PRO-DW-000-012-1


06 SERVICE Sour water tank blanketing Kerosene to tanks Utility water to filtering package
07 LINE/EQUIPMENT NO. 4”-AA3-BG-502-P 6”-AA1-KE-503-P 6”-AA4-UW-506-P
08 MOUNTING/WEIGHT Bracket on 2” standpipe / * Bracket on 2” standpipe / * Bracket on 2” standpipe / *
09 AMBIENT TEMPERATURE LIMITS 0÷50 °C 0÷50 °C 0÷50 °C
PROCESS DATA

10 DESIGN TEMP. / PRESSURE 0 ÷80 °C / 10 bar g 0 ÷80 °C / 16 bar g 0 ÷60 °C / 17 bar g


11 FLUID/PHASE Blanketing gas / gas Kerosene / liquid Water / liquid
12 PRESSURE MIN/NORM/MAX - / 18 / - mbar 4.7 / - / 5.3 bar g 11.2 / - / 12.2 bar g
13 TEMPERATURE MIN/NORM/MAX 40 ÷50 °C 38 / - / 50 °C - / 30 / - °C
14 MAX STATIC PRESSURE 50 mbar (Note 2) 6.5 bar g (Note 4) 14.5 bar g (Note 4)
15 CALIBRATED INPUT RANGE 0÷ 0.6 bar g * 0÷10 bar g * 0÷20 bar g *
16 CHARACTERISTIC Linear Linear Linear
INST.CHARACT.

17 ACCURACY / REPEATABILITY ±0.1% of span * ±0.1% of span * ±0.1% of span *


18 LOWER/UPPER RANGE LIMITS * * *
19 MIN/MAX SPAN * * *
20 ZERO ADJUSTMENT Yes Yes Yes
21 RESPONSE TIME * * *
22 MAX STATIC PRESSURE * * *
23 TYPE electronic * electronic * electronic *
ELEMENT/SENSOR

24 MATERIAL,ELEMENT (SENSOR) AISI 316L AISI 316L AISI 316L


25 MATERIAL,SOCKET (INLET PORT) AISI 316 AISI 316 AISI 316
26 MATERIAL,SENSOR BOLTS/NUTS AISI 316 AISI 316 AISI 316
27 PROCESS CONN.SIZE/TYPE ½” NPT-F, with flange adapter ½” NPT-F, with flange adapter ½” NPT-F, with flange adapter
28 POSITION OF CONNECTION * * *
29 SOUR SERVICE SPEC. NACE MR 0175 Not required Not required
30 DIMENSION / MATERIAL / Aluminium epoxy coated * / Aluminium epoxy coated * / Aluminium epoxy coated
31 ENCLOSURE PROTECTION IP 65 (min) IP 65 (min) IP 65 (min)
HOUSING

32 CABLE ENTRY ISO M20x1.5mm ISO M20x1.5mm ISO M20x1.5mm


33 EX. CLASSIFICATION Ex-d IIB-T3 / ATEX 94/9/EC Ex-d IIB-T3 / ATEX 94/9/EC Ex-d IIB-T3 / ATEX 94/9/EC
34 PROTECTIVE COATING Mfr. Std. Mfr. Std. Mfr. Std.
35 INDICATOR Remote LCD display (barg units) Integrated LCD display (barg units) Integrated LCD display (barg units)
TRANSM.

36 OUTPUT SIGNAL/COMUNICATION 4-20 mA, 2 wire / HART 4-20 mA, 2 wire / HART 4-20 mA, 2 wire / HART
37 SUPPLY VOLTAGE 24 VDC (loop powered) 24 VDC (loop powered) 24 VDC (loop powered)
38 CONSUMPTION / LOAD LIMITATION * * *
39 TYPE Not required Not required Not required
40 MATERIAL, UPPER/LOWER PART - - -
CHEMICAL SEAL

41 MATERIAL, BOLTS / NUTS - - -


42 MATERIAL, DIAPHRAGM - - -
43 FILL FLUID - - -
44 CAPILLARY LENGTH/DIAMETER - - -
45 MATERIAL,CAPILLARY/ARMOUR - - -
46 PROCESS CONN. SIZE/TYPE - - -
47 INSTRUMENT CONN. SIZE/TYPE - - -
48 MOUNTING BRACKET N° 2 x 2” pipe bracket (Note 3) Yes, 2” pipe bracket Yes, 2” pipe bracket
49 MATERIAL, MOUNTING BRACKET AISI * AISI * AISI *
ACCESSORIES

50 MANIFOLD Not required Not required Not required


51 MANIFOLD MATERIAL
52 MANIFOLD PROCESS CONN.
53 MANIFOLD PRESSURE RATING
54 TROPICALIZATION Required (Mfr Std) Required (Mfr Std) Required (Mfr Std)
55 TAG / DATA PLATE MTL. Required / SS Required / SS Required / SS
NOTES: (*) Information to be supplied or to be confirmed by Supplier.
(1) Supplier is required to provide, as a minimum, the following documents: technical bulletins, O&M manuals, manufacturing data book, quality book (with all test reports, material
certificates, mechanical/electrical protection certificates, calibration certificates...) as per purchaser requisition documents.
(2) Value to be confirmed later (pending on tank Design Pressure)
(3)The second 2” pipe bracket support is for the remote LCD display located at tank grade.
(4) Max static pressure pending on shut-off pressure of pump. This value shall be confirmed later

File name: 10J01762-ICT-DS-000-005-D0.doc Printed on 26/07/2011

You might also like