REQUIREMENTS FOR STREETLIGHT DESIGN

AND INSTALLATION PACKAGE

Published: May 2017

CITY OF GRESHAM
DEPARTMENT OF ENVIRONMENTAL SERVICES
1333 NW Eastman Parkway
Gresham, OR 97030
(503) 618-2525

(Go to https://greshamoregon.gov/LED-Streetlights/ for the latest publication)


6.02.14 Streetlighting

Design and installation of a complete streetlighting system shall be the responsibility of


the developer for all streets fronting the property, including pedestrian accessways associated with the
development. Developments will be required to submit a lighting plan that provides pole spacing less than
or equal to the maximum spacing allowed shown in Table 6.02.14a below as well as a photometric analysis
of that layout. The photometric analysis shall provide a point calculation spacing of no more than 4 feet on
center with 2 significant digits of calculation and display. The lighting level design standards are:

Minimum Maximum
Average Average-to-Minimum
Illuminance Ratio
5-Lane Facilities: 0.67 Fc 3.5

3-Lane Facilities: 0.45 Fc 4.0

2-Lane Facilities: 0.30 Fc 6.0

Pedestrian Accessways: 0.30 Fc 6.0

The Manager may require up to double these lighting levels at locations the Manager
determines are high pedestrian activity areas.

Streetlights and streetlight infrastructure shall conform to the City of Gresham Standard
Details. Streetlights per the “Decorative Acorn Streetlight” detail are required in the Downtown Plan District
and the designated centers in the Pleasant Valley and Springwater Plan Districts. Within the Civic
Neighborhood Plan District (as defined in Section 4.1200 of the City of Gresham Development Code),
streetlights per the “Decorative Pendant Streetlight” detail are required on streets with classifications of
Civic Boulevard and Civic Collector. All other streets within the Civic Neighborhood Plan District shall have
streetlights per the “Decorative Acorn Streetlight” detail. Within the Rockwood Town Center portion of the
Rockwood Design District (as defined in Section 7.0500 of the City of Gresham Development Code),
streetlights per the “Decorative Pendant Streetlight” detail are required along Arterials and on all streets
inside the Rockwood Triangle Area (as defined in Section 7.0500 of the City of Gresham Development
Code). All other streets within the Rockwood Town Center shall have streetlights per the “Decorative Acorn
Streetlight” detail.

Streetlights are required to be installed along every street frontage on both sides of the
street, except outside of designated centers and along streets with the following functional classifications:
Major Collector, Standard Collector, Minor Collector, Local Industrial, Local Commercial, Local Transitional,
and Local Queuing. Along streets with the functional classifications listed above, which fall outside of
designated centers, streetlights may be installed on only one side of the street or staggered from one side
to the other. For infill development locations along existing streets, additional streetlighting may be required
at Manager’s discretion, even if streetlights are already installed on the other side of the street.

Streetlight power for new lighting shall be supplied from underground. At Manager
discretion, infill development may meet requirements for streetlighting by installing new lights on existing
utility poles per the "Luminaire Mounted on Existing Wood Pole" detail. If spacing of utility poles is
substandard, additional underground-fed lights may be required along the frontage to meet lighting
standards.

The City of Gresham standard for 35-foot poles is the aluminum davit pole shown in the
“Aluminum Davit Streetlight” detail. The City of Gresham standard for 25-foot poles is the direct-bury
fiberglass pole shown in the “Fiberglass Streetlight Pole” detail.

All streetlighting materials and equipment installed in the public right-of-way must be listed
on the City of Gresham Pre-Approved Materials List for Streetlight Equipment and Materials, with
exceptions made at Manager’s discretion. The City of Gresham Pre-Approved Materials List are available
for download on the City’s website.

Requirements for Streetlight Design and Installation May 2017


Table 6.02.14a: Standard Streetlight Layout and Type
Frontage
Street Classification Height Spacing Luminaire Type
(Ft) (Ft)
Arterial (All)* 35 150 Medium Cobra Head***
Major Collector* 35 150** Large Cobra Head
Standard Collector* 25 130** Medium Cobra Head
Minor Collector* 25 130** Medium Cobra Head
Local Industrial* 35 150** Large Cobra Head
Local Commercial* 25 130** Medium Cobra Head
Local Transitional* 25 140** Residential Cobra Head
Local Queuing* 25 140** Residential Cobra Head
Pedestrian Accessways 12 75** Residential Cobra Head

Civic Neighborhood
Civic Boulevard 18 90 Pendant
Civic Collector 18 100 Pendant
Civic Community 14 100 Acorn
Civic Local 14 100 Acorn
Civic Shared 14 100 Acorn

Downtown
Downtown Boulevard 16 80 Acorn
Non-Boulevard Streets in
14 100 Acorn
Downtown

Rockwood Town Center


Boulevard 18 90 Pendant
Local Streets Inside the Triangle 18 90 Pendant
Local Streets Outside the Triangle 14 100 Acorn

* Only applies to streets outside of the designated centers in the Downtown and Civic
Neighborhood Plan Districts, the Rockwood Town Center portion of the Rockwood Design
District, and the designated centers within the Pleasant Valley and Springwater Plan Areas.
** Lighting required on one street frontage only or staggered from side to side. Streetlights
are required on both frontages (both sides of the street) on all other street classifications
and cases.
*** If lighting is only on one side of the street, install Large Cobra Head fixture.

Pole footings shall be installed with 2 feet of clearance between the face of curb and the
face of the pole. Lights shall be no closer than 15 feet to a tree.

All new installations with power supplied underground shall include a service disconnect
between the PGE power supply junction box and the first streetlight junction box, as shown in the
“Streetlight Disconnect” detail, unless otherwise directed by the Manager.

Requirements for Streetlight Design and Installation May 2017


SEE GRESHAM PRE-APPROVED MATERIALS
LIST FOR PRE-APPROVED LIGHT FIXTURES
BRACKET
#6 SOLID BARE COPPER
INSTALL INLINE FUSED
GROUND WIRE
DISCONNECT 5 AMP SLOW
BLOW FUSE WITHIN 6" OF 6' MAST ARM
THE DRIP LOOP, AS DOUBLE BRACE WIND RODS (IF APPLICABLE)
DIRECTED. SEE GRESHAM
PRE-APPROVED
MATERIALS LIST. STREETLIGHT MAST ARM
(SEE GRESHAM PRE-APPROVED MATERIALS LIST)
#10 COPPER INSULATED
EXTERNAL GROUND CLAMP
FILENAME: y:\des\transportation\cad\pws details\cad\639.dwg, Plotted 4/13/2017 2:57 PM, By: Bogert, Kimberly, ANSI FULL BLEED A (8.50 X 11.00 INCHES)

STREETLIGHT CONDUCTOR (SEE


PGE APPROVED PRODUCTS
LIST) - 48" TAIL COILED ON POLE 20" (SEE NOTE #6)
AFTER DRIP LOOP INSTALLED. 12" (SEE NOTE #7)

CONTRACTOR TO INSTALL
DRIP LOOP & SECURE TO TELEPHONE OR CABLE
POLE WITH 3 STAPLES COMPANY ATTACHMENT POINT

PROTECT GROUND WIRE 8' ABOVE SURFACE

NOTES:

1. SEE GRESHAM PRE-APPROVED MATERIALS LIST


FOR PRE-APPROVED MAST ARMS AND LUMINAIRES.

2. VERIFY REQUIRED WATTAGE WITH CITY.

3. MINIMUM 30 FEET MOUNTING HEIGHT ON


LUMINAIRES OVER 8,500 LUMENS.

4. IF OTHER UTILITIES ARE ON POLE, "QUALIFIED


WORKERS" SHALL PERFORM THE WORK AND MUST
FOLLOW NESC REQUIREMENTS.

5. PGE WILL MAKE CONNECTIONS TO SECONDARY.

6. 20 INCH CLEARANCE MAY BE REDUCED TO 4 INCH


IF MAST ARM AND FIXTURE ARE OBVIOUSLY
EFFECTIVELY GROUNDED

7. 12 INCH CLEARANCE MAY BE REDUCED TO 3 INCH


5/8" X 8' GALVANIZED IF STREETLIGHT CONDUCTORS ARE INSTALLED IN
GROUND ROD A NON CONDUCTIVE CONDUIT

NTS
CM
LUMINAIRE MOUNTED ON APR 2017

EXISTING WOOD POLE


639-P
BONDING LUG
GROUND WIRE 4' MIN (WHEN REQUIRED)
(WHEN REQUIRED)
45° CHAMFER TYP
JUNCTION BOX COVER
STAINLESS
INSTALL JUNCTION 12"
STEEL/BRASS "L" 12"
BOX LEVEL WITH
BOLTS OR HEX HEAD
SIDEWALK 3 1/2"
BOLTS

3/4" - 0"
CRUSHED
SIDEWALK 12"
FILENAME: y:\des\transportation\cad\pws details\cad\junction boxes.dwg, Plotted 4/13/2017 2:59 PM, By: Bogert, Kimberly, ANSI FULL BLEED A (8.50 X 11.00 INCHES)

ROCK
BUSHING, TYP
3" MIN
2 IN

3" MAX PORTLAND CEMENT CONCRETE APRON

12" OF COVER TO BE
3/4" - 0" CONDUIT
MARKED "SIGNALS"
CRUSHED ROCK OR "LIGHTING" AS
DIRECTED (MIN 1"
INSTALLATION IN SIDEWALK OR AT BACK OF CURB
LETTER HEIGHT)

USE LOCKING LID


FOR LIGHTING JUNCTION BOX
LS
BOXES. NA COVER WITH
SIG
RECESSED
FACE LIFTING EYE OR
SIDEWALK (AS MAX 3/8" LIFT
SHOWN ON OF CURB
LIFT EYE HOLE
PLANS)

BACK OF TR
AV
SIDEWALK EL
LA
NE
HTI
NG
12" MIN D
LIG
W L

12" MIN

JUNCTION BOX
NOT TO BE USED IN TRAVEL LANES,
SHOULDERS OR AREAS EXPOSED TO
JUNCTION BOX PLACEMENT WITHIN SIDEWALKS TRAFFIC. SEE GRESHAM PRE-APPROVED
(JUNCTION BOXES TO BE LOCATED MATERIALS LIST.
ONLY IN FLAT AREAS OF SIDEWALKS,
TYPE L W D
CONCRETE JUNCTION BOXES ARE
NOT TO BE INSTALLED IN SLOPES OF JB1 17" 10" 12"
RAMPS OR DRIVEWAYS)
JB2 22" 12" 12"
JB3 30" 17" 12"
JUNCTION BOXES PLACED WITHIN
SIDEWALKS SHALL INCLUDE A FULL JUNCTION BOX DIMENSION TABLE
PANEL REMOVAL AND REINSTALL
NTS
CM
ELECTRICAL APR 2017

JUNCTION BOXES
TBD
PGE
TRANSFORMER

CONDUIT (PER PGE REQUIREMENTS)


STREETLIGHT POLE
FILENAME: y:\des\transportation\cad\pws details\cad\streetlight disconnect.dwg, Plotted 4/13/2017 3:00 PM, By: Bogert, Kimberly, ANSI FULL BLEED A (8.50 X 11.00 INCHES)

PGE TYPE 1730 JUNCTION BOX


ELECTRICAL MIN 10 FT, MAX 50 FT FROM
TRANSFORMER.

1" CONDUIT
SEE STREETLIGHT
DETAILS AND
ELECTRICAL JUNCTION CITY STREETLIGHT SERVICE
BOXES DETAIL LIGHTING DISCONNECT. SEE GRESHAM
PRE-APPROVED MATERIALS LIST.

2" CONDUIT STREETLIGHT POLE

LIGHTING JUNCTION
BOX (TYPE JB2)
LIGHTING
1" CONDUIT

2" CONDUIT

NOTES:

1. MINIMUM CONDUCTOR SIZE SHALL BE 10 GA. CONDUCTORS SHALL BE UPSIZED IF REQUIRED TO KEEP
VOLTAGE DROP TO LESS THAN 3%. 3-CONDUCTOR 7-STRAND COPPER WIRE WITH .030" XLPE
INSULATION, FILLERS, AND CLEAR MYLAR WRAP TAPE NON-SHIELDED OVERALL .045" BLACK PVC
JACKET (UL) TC-ER XHHW-2/VW-1 600V 90C DRY/WET, SUN RESISTANT, DIRECT BURY, CC:
BLACK/RED/GREEN FOR 220 VOLT AND BLACK/WHITE/GREEN FOR 120 VOLT.

2. ALL EMPTY CONDUITS MUST HAVE A #14 LOCATE WIRE AND A NONCONDUCTIVE PULL LINE, 500 POUND
RATED, WITH 6 FEET OF LINE EXTENDING FROM EACH END OF THE CONDUIT.

3. INSTALL ELECTRICAL GRADE SCHEDULE 40 GRAY PVC CONDUIT WITH FIBERGLASS BENDS. ALL PVC
JOINTS SHALL BE GLUED. ALL FACTORY OR FIELD CUT CONDUITS SHALL BE CHAMFERED TO PREVENT
DAMAGE TO CABLES. A WOODEN, PLASTIC, OR HARD RUBBER MANDREL CONFIGURED FOR THE
CONDUIT INSIDE DIAMETER SHALL BE PULLED THROUGH TO TEST FOR OBSTRUCTIONS AND
OUT-OF-ROUND CONDUIT.

4. ELECTRICAL BUILDING PERMIT REQUIRED.

NTS
CM
APR 2017
STREETLIGHT DISCONNECT
TBD
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 1

PRE-APPROVED MATERIALS LIST - STREETLIGHTS

SUBMITTALS
FOR FIELD QUALIFICATION
STREETLIGHT EQUIPMENT AND MATERIALS

PROJECT MANAGER: ________________________________________________

PROJECT: ________________________________________________

CONTRACT NO.: ________________________________________________

SUBMITTING
CONTRACTOR: ________________________________________________

DATE SUBMITTED: ________________________________________________

CONTRACTOR
REPRESENTATIVE: ________________________________________________

PHONE: ________________________________________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 2

‘PRE-APPROVED MATERIALS LIST’ INSTRUCTIONS

These sheets are to be furnished for each project, by the Project Manager. They are also found on
the City of Gresham’s Internet site. They will be provided for each project, to ensure that they are the
most current copy.

INITIAL SUBMITTAL
The Developer/Contractor will:
1. Submit the Streetlight Sheets electronically
2. Fill out the Streetlight Sheets based on the projects requirements
a. In the CONTENTS pages check the box for all items that are “NOT ON PROJECT”.
This removes the need to submit the materials page(s) for these items.
b. For materials that are on the project:
i. Check the listed brand and circle the model to be used, or
ii. Write in a brand and model proposed for installation based on the project plans
and specifications. Submit one catalogue cut sheet for initial qualification.
iii. Except for conduit and wire, do not mark more than two options per item.

The Development Engineer will:


1. Review initial submittal and fill out the INITIAL SUBMITTAL box in the CONTENTS
pages and specific materials pages for listed materials.
2. Submit write in products to the Streetlight Engineer for approval.
3. Return a copy of the Streetlight Sheets to the Contractor

CONSTRUCTION
Materials delivered to job site shall be clearly marked as to brand and model/part description
(verified on materials), or shall be accompanied by supplier’s certification as to brand and model/part
description.

The Contractor will:


1. Install materials QUALIFIED by the Development Engineer during the INITIAL
SUBMITTAL. Install per plan and specifications.

The Inspector will:


1. Verify materials installed match the Contractor’s INITIAL SUBMITTAL. Verify the
materials are installed per plan and specifications.

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 3

CONTENTS INITIAL SUBMITTAL


AGREE WITH “NOT ON PROJECT”
NOT ON
PAGE NO. ILLUMINATION SPECIFIC PROJECT RETURNED FOR CORRECTION
Date:________________________
4 FIBERGLASS POLES
Name:_______________________
5 DECORATIVE POLES
Qualifications or corrections are subject to all
6 ALUMINUM DAVIT POLES requirements of the current issue of the City of
7 POLE FOOTINGS Gresham Public Works Standards as modified by
the Project Special Provisions.
8 WOOD POLE MAST ARMS
9 LED COBRA HEAD LIGHT FIXTURES
10 DECORATIVE LIGHT FIXTURES
11 PHOTOELECTRIC CELLS
12 LED LIGHT SHIELDS
13 IN-LINE FUSED DISCONNECTS
14 WIRE CONNECTORS
15 SERVICE PEDESTALS
16 JUNCTION BOX (CONCRETE)
17 JUNCTION BOX (HYBRID)
18 CONDUIT (METALLIC)
19 CONDUIT (NON-METALLIC)
20 CONDUIT BUSHINGS
21 GROUND ROD AND CLAMP
22 XHHW WIRE
23 OVERHEAD WIRE EQUIPMENT

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 4

FIBERGLASS POLES INITIAL SUBMITTAL


QUALIFIED
DESCRIPTION: Fiberglass light poles and bases used for supporting
luminaires. QUALIFIED AS NOTED

USE: For use with illumination systems and luminaires.


RETURNED FOR CORRECTION
Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO.
Name:_______________________
POLE STUB PIECE Qualifications or corrections are subject to all
Shakespeare BHS3099N3BL9901 (39357) requirements of the current issue of the City of
Gresham Public Works Standards as modified by
CMT 25-STUB-UP (39371) the Project Special Provisions.
____________________ __________________
____________________ __________________
____________________ ____________________

POLE TOP PIECE


Shakespeare BHT3099S3BL9901 (39356)
(CU1105)
CMT MDS30-F-100-S1-HS-PC-NP-1B-22
(39370) (CU1106)
____________________ __________________
____________________ __________________
____________________ ____________________

8” MAST ARMS
Shakespeare OPAR-0.7-PGE-BR
Valmont 1HS23808B475
Whatley SB8-2DDB
____________________ ____________________
____________________ ____________________

6’ MAST ARMS
Shakespeare OPAR-6
Valmont 1MA0632B475 W/HARDWARE
Whatley MA-75
____________________ ____________________
____________________ ____________________

8’ MAST ARMS
Shakespeare OPAR-8
Valmont 1MA0832B475
Whatley MA-96
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 5

INITIAL SUBMITTAL
DECORATIVE POLES QUALIFIED
DESCRIPTION: Decorative light poles and bases used for supporting QUALIFIED AS NOTED
luminaires.
RETURNED FOR CORRECTION
USE: For use with illumination systems and luminaires. Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO. Name:_______________________
Qualifications or corrections are subject to all
ACORN LIGHT POLES requirements of the current issue of the City of
Continental Pole PGE-14 Gresham Public Works Standards as modified by
Continental Pole PGE-16 the Project Special Provisions.

____________________ __________________
____________________ __________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

PENDANT LIGHT POLES


Philips Hadco CP0606-18A-HFP3
____________________ __________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

PENDANT LIGHT ARMS


Philips Hadco CA0606D-310-P4APM
____________________ __________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 6

INITIAL SUBMITTAL
ALUMINUM DAVIT POLES
QUALIFIED
DESCRIPTION: Aluminum light poles and bases used for supporting
QUALIFIED AS NOTED
luminaires.
RETURNED FOR CORRECTION
USE: For use with illumination systems and luminaires.
Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO. Name:_______________________
DAVIT POLES Qualifications or corrections are subject to all
requirements of the current issue of the City of
Valmont 350086106D4Z Gresham Public Works Standards as modified by
Hapco RTA35D8B4D16-GC the Project Special Provisions.
____________________ __________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 7

INITIAL SUBMITTAL
POLE FOOTINGS
QUALIFIED
DESCRIPTION: Light pole footings used for supporting luminaires.
QUALIFIED AS NOTED
USE: For use with illumination systems and luminaires. RETURNED FOR CORRECTION
Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO.
Name:_______________________
FOOTINGS FOR 25-35 FOOT POLES
Qualifications or corrections are subject to all
Old Castle 5CL-LB-PGE requirements of the current issue of the City of
____________________ __________________ Gresham Public Works Standards as modified by
the Project Special Provisions.
____________________ __________________
____________________ __________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

FOOTINGS FOR DECORATIVE POLES


Old Castle 20R-LB-4-PGE
____________________ __________________
____________________ __________________
____________________ __________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 8

INITIAL SUBMITTAL
WOOD POLE MAST ARMS
QUALIFIED
DESCRIPTION: Mast arms used for supporting luminaires.
QUALIFIED AS NOTED
USE: For use with illumination systems and luminaires. RETURNED FOR CORRECTION
Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO.
Name:_______________________
4-FT MAST ARM
Qualifications or corrections are subject to all
Valmont ACSC 125-040 requirements of the current issue of the City of
Utility Metals U125S040 Gresham Public Works Standards as modified by
the Project Special Provisions.
SALCO WP-125-4-S
Maclean Power Systems S-125-4G
____________________ ____________________
____________________ ____________________
____________________ ____________________

6-FT MAST ARM


Utility Metals P125S060
SALCO WP-125-6-S
Maclean Power Systems S-125-6G
____________________ __________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

8-FT MAST ARM


Utility Metals S1252080
SALCO WPSG-125-8-S-PGE
Maclean Power Systems S-125-8SG-30R
____________________ __________________
____________________ __________________
____________________ __________________
____________________ __________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 9

INITIAL SUBMITTAL
LED COBRA HEAD LIGHT FIXTURES
QUALIFIED
DESCRIPTION: Light fixtures used for illumination systems.
QUALIFIED AS NOTED
USE: For use with illumination systems and poles. RETURNED FOR CORRECTION
Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO.
Name:_______________________
RESIDENTIAL COBRA HEAD
Qualifications or corrections are subject to all
Leotek Electronics EC1-6M-MV-NW-2-GY-350-WL requirements of the current issue of the City of
Leotek Electronics EC1-6M-MV-NW-2-GY-530-WL Gresham Public Works Standards as modified by
the Project Special Provisions.
Leotek Electronics EC1-6M-MV-NW-2-GY-700-WL
____________________ ____________________
____________________ ____________________
____________________ ____________________

MEDIUM COBRA HEAD


Leotek Electronics EC3-10M-MV-NW-2-GY-350-WL
Leotek Electronics EC3-10M-MV-NW-2-GY-530-WL
Leotek Electronics EC3-10M-MV-NW-2-GY-700-WL
____________________ ____________________
____________________ ____________________

LARGE COBRA HEAD


Leotek Electronics EC7-20M-MV-NW-3-GY-350-WL
Leotek Electronics EC7-20M-MV-NW-3-GY-530-WL
Leotek Electronics EC7-20M-MV-NW-3-GY-700-WL
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 10

INITIAL SUBMITTAL
DECORATIVE LIGHT FIXTURES
QUALIFIED
DESCRIPTION: Decorative light fixtures used for supporting
QUALIFIED AS NOTED
luminaires.
RETURNED FOR CORRECTION
USE: For use with illumination systems and poles.
Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO. Name:_______________________
ACORN LIGHTS Qualifications or corrections are subject to all
requirements of the current issue of the City of
King Luminaire K118R-B3AR-IV-75(SSL)-1036-120
Gresham Public Works Standards as modified by
____________________ __________________ the Project Special Provisions.
____________________ __________________
____________________ __________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

PENDANT LIGHTS
Cyclone Lighting SY21P1-GAL-3-60W-3K-120-DIM-CP4377
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 11

INITIAL SUBMITTAL
PHOTOELECTRIC CELLS
QUALIFIED
DESCRIPTION: A photoelectronic device used for turning
QUALIFIED AS NOTED
on luminaires.
RETURNED FOR CORRECTION
USE: To activate illumination systems.
Date:________________________
Name:_______________________
BRAND/MANUFACTURER CATALOGUE/PART NO.
Qualifications or corrections are subject to all
PHOTO CELL FOR COBRA AND PENDANT LIGHTS requirements of the current issue of the City of
Gresham Public Works Standards as modified by
Ripley LongLife II 6390LL-BK the Project Special Provisions.
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

PHOTO CELL FOR ACORN LIGHTS


Ripley RD8645
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 12

INITIAL SUBMITTAL
LED LIGHT SHIELDS
QUALIFIED
DESCRIPTION: Light fixture shields used for limiting light for house
QUALIFIED AS NOTED
side or cul-de-sac situations.
RETURNED FOR CORRECTION
USE: For use with illumination systems and luminaires.
Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO. Name:_______________________
HOUSE SIDE SHIELD Qualifications or corrections are subject to all
requirements of the current issue of the City of
Leotek Electronics HHS EC1 (6M) Gresham Public Works Standards as modified by
Leotek Electronics HHS EC3 (10M) the Project Special Provisions.
Leotek Electronics HHS EC7 (18M)
Leotek Electronics HHS EC7 (20M)
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

CUL-DE-SAC SHIELD
Leotek Electronics CSS EC1 (6M)
Leotek Electronics CSS EC3 (10M)
Leotek Electronics CSS EC7 (18M)
Leotek Electronics CSS EC7 (20M)
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 13

INITIAL SUBMITTAL
IN-LINE FUSED DISCONNECTS
QUALIFIED
DESCRIPTION: In-line fused disconnects used for disconnecting
QUALIFIED AS NOTED
luminaires from power for servicing.
RETURNED FOR CORRECTION
USE: For use with illumination systems and luminaires.
Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO. Name:_______________________
DISCONNECTS Qualifications or corrections are subject to all
requirements of the current issue of the City of
Littelfuse WPB1 Gresham Public Works Standards as modified by
Littelfuse LEB-JJ the Project Special Provisions.
Bussmann 2A0660
Bussmann HEB-JJ
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 14

INITIAL SUBMITTAL
WIRE CONNECTORS
QUALIFIED
DESCRIPTION: Wire connectors used for splicing wire together.
QUALIFIED AS NOTED
USE: For use with illumination systems and luminaires. RETURNED FOR CORRECTION
Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO.
Name:_______________________
CONNECTORS
Qualifications or corrections are subject to all
Ideal WeatherProof® Model 61® Gray/Orange requirements of the current issue of the City of
Ideal WeatherProof® Model 62® Gray/Red Gresham Public Works Standards as modified by
the Project Special Provisions.
Ideal WeatherProof® Model 63® Gray/Dk. Blue

Ideal UnderGround® Model 60® Gray/Gray


Ideal UnderGround® Model 64® Gray/Dk. Blue
Ideal UnderGround® Model 66® Gray/Dk. Blue

____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 15

INITIAL SUBMITTAL
SERVICE PEDESTALS
QUALIFIED
DESCRIPTION: Service pedestals used for providing one connection
QUALIFIED AS NOTED
point between City lights and PGE power source.
RETURNED FOR CORRECTION
USE: For use with illumination systems and luminaires.
Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO. Name:_______________________
PEDESTALS Qualifications or corrections are subject to all
requirements of the current issue of the City of
Cooper B-line CUP4111 Gresham Public Works Standards as modified by
____________________ __________________ the Project Special Provisions.
____________________ __________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

PAD MOUNT
Cooper B-line MB1515
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 16

INITIAL SUBMITTAL
JUNCTION BOX (CONCRETE)
QUALIFIED
DESCRIPTION: Open-bottom boxes of pre-cast reinforced
QUALIFIED AS NOTED
concrete w/Brass or stainless steel fasteners. Polymer
concrete also. RETURNED FOR CORRECTION
Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO.
Name:_______________________
JB1
Qualifications or corrections are subject to all
ARMORCAST A6001425TA requirements of the current issue of the City of
Christy Concrete/Oldcastle 36-1017PB, (DPF or HBBOA lid) Gresham Public Works Standards as modified by
the Project Special Provisions.
CDR SA20101512
Carson Industries H1118-12 w/H1118-P1 lid
Quazite PG1118BA12 w/PG1118HA lid
BES Concrete C9E w/C9T lid
Brooks Products 36PB w/ concrete,
galv cast iron, or galv
steel lid
Newbasis PCA111812A5
Christy Concrete/Oldcastle N9 w/ SYN09-T lid
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

JB2
ARMORCAST A6001946TAPCX12
Christy Concrete/Oldcastle 37-1220PB, 38-1324PB
(DPF or HBBOA lid)
CDR SA20132412
Carson Industries H1324-12 w/
H1324-P1 lid
BES Concrete C16E w/C16T lid
Brooks Products 40PB w/galv cast iron
or galv steel lid
Newbasis PCA132412A5
Quazite PG1324BA12 w/PG1324HA lid
Christy Concrete/Oldcastle N30 w/ HBBOA lid
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 17

INITIAL SUBMITTAL
JUNCTION BOX (HYBRID)
QUALIFIED
DESCRIPTION: Open-bottom boxes made of polymer, QUALIFIED AS NOTED
fiberglass, and/or polymer concrete.
RETURNED FOR CORRECTION
USE: Pull box for 120V AC conduit runs. Junction box for Date:________________________
DC conduit runs. (splices to loop feeder cable).
Name:_______________________
BRAND/MANUFACTURER CATALOGUE/PART NO.
Qualifications or corrections are subject to all
JB1 requirements of the current issue of the City of
Gresham Public Works Standards as modified by
Christy Concrete/Oldcastle Box - S1118B12AA the Project Special Provisions.
Lid – S1118HBBOA
Synertech Box - S1118B12FA
Lid – S1118HBBOA01
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

JB2
Christy Concrete/Oldcastle Box - S1324B12AA
Lid –S1324HBBOA
Synertech Box - S1324B12FA
Lid – S1324HBBOA01
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ___________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 18

INITIAL SUBMITTAL
CONDUIT (METALLIC)
QUALIFIED
DESCRIPTION: Galvanized rigid conduit and fittings.
QUALIFIED AS NOTED
USE: Houses electrical conductors. RETURNED FOR CORRECTION
Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO.
Republic All galv. rigid conduit Name:_______________________
Picoma All galv. rigid conduit Qualifications or corrections are subject to all
requirements of the current issue of the City of
Allied Tube & Conduit All galv. rigid conduit Gresham Public Works Standards as modified by
Conduit Pipe Products All galv. rigid conduit the Project Special Provisions.
Western Tube & Conduit All galv. rigid conduit
Wheatland Tube Co. All galv. rigid conduit CMO REQUIRED (If steel or iron, see specifications)
Shamrock (T&B) All galv. rigid conduit Received Date: ___________________
Cal Pipe Manufacturing All galv. rigid conduit
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

Liquid-Tight Flexible
Anamet Electrical Inc. Type UA
(Anaconda Sealtite)
Southwire Titan Type UL
AFC Cable Systems LiquidTuff Type LFMC
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 19

INITIAL SUBMITTAL
CONDUIT (NON-METALLIC)
QUALIFIED
DESCRIPTION: PVC, High Density Polyethylene, and
Fiberglass rigid non-metallic conduit and fittings.
QUALIFIED AS NOTED
RETURNED FOR CORRECTION
USE: Houses electrical conductors.
Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO. Name:_______________________
PVC (UL 651) Qualifications or corrections are subject to all
requirements of the current issue of the City of
PW Pipe Sch. 40 & 80
Gresham Public Works Standards as modified by
Carlon Sch. 40 & 80 the Project Special Provisions.
Cantex Sch. 40
J-M Manufacturing Sch. 40 & 80
Kraloy Sch. 40
Ipex/Scepter Sch. 40
Cresline Northwest Sch. 40
Ridgeline Sch. 40
Heritage Plastics Central Sch. 40
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

HDPE (UL 651B)


Carlon Sch. 40 & 80
Arnco/Dura-Line Sch. 40 & 80
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 20

INITIAL SUBMITTAL
CONDUIT BUSHINGS
QUALIFIED
DESCRIPTION: Conduit bushings with insulated throat QUALIFIED AS NOTED
but no bonding lug.
RETURNED FOR CORRECTION
USE: Used on the ends of conduit when bonding lugs are Date:________________________
not needed.
Name:_______________________
BRAND/MANUFACTURER CATALOGUE/PART NO.
Qualifications or corrections are subject to all
METALLIC requirements of the current issue of the City of
Gresham Public Works Standards as modified by
Bridgeport #363 thru #370 the Project Special Provisions.
T&B #1224,1226 thru 1229
RACO #1127 thru 1134 CMO REQUIRED (If steel or iron, see specifications)
Crouse-Hinds #1033 thru 1038 Received Date: ___________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

POLYMER END BELL


Cantex #5144005 thru 5144010
PW Pipe #6150-0200, 6150-300
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 21

INITIAL SUBMITTAL
GROUND ROD AND CLAMP
QUALIFIED
DESCRIPTION: Copper coated 5/8 inch metal rod, QUALIFIED AS NOTED
8 feet to 10 feet long w/clamp
RETURNED FOR CORRECTION
USE: All poles, conduit runs with 120V+ AC, and controller
Date:________________________
must be bonded to ground rod using full-contact clamps.
Name:_______________________
BRAND/MANUFACTURER CATALOGUE/PART NO.
Qualifications or corrections are subject to all
GROUND ROD requirements of the current issue of the City of
Gresham Public Works Standards as modified by
Thomas & Betts (Blackburn) 6258 the Project Special Provisions.
Eritech 615880
PP Porcelain Products 8438 CMO REQUIRED (If steel or iron, see specifications)
Petron Pacific 5/8” Received Date: ___________________
Hubbell/Chance C615855
____________________ ____________________
____________________ ____________________

CLAMP
Thomas & Betts (Blackburn) JAB58H
Burndy GRC58
PENN-UNION CAB or CEB
PP Porcelain Products 8058
Eritech HDC58
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

CHEMICAL GROUND SYSTEM


Tessco n/a
Superior Grounding Systems n/a
Erico n/a
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 22

INITIAL SUBMITTAL
XHHW WIRE
QUALIFIED
DESCRIPTION: XHHW is stranded copper conductor
with cross linked polyethylene insulation. No THWN will
QUALIFIED AS NOTED
be used. RETURNED FOR CORRECTION
USE: All single conductor applications are XHHW.
Date:________________________
Name:_______________________
BRAND/MANUFACTURER CATALOGUE/PART NO.
Qualifications or corrections are subject to all
Rome Cable (Anixter) WIRE requirements of the current issue of the City of
General Cable (Anixter) Gresham Public Works Standards as modified by
the Project Special Provisions.
Southwire MUST
Encore Wire
Service Wire Co BE
Kris Tech (KT) Wire
____________________ MARKED.
____________________
____________________ ADDITIONAL
____________________
____________________ MARKINGS
____________________
____________________ ARE
____________________
____________________ ALLOWED.

MAY 2017
CITY OF GRESHAM STREETLIGHT EQUIPMENT AND MATERIALS Page 23

OVERHEAD WIRE EQUIPMENT INITIAL SUBMITTAL


DESCRIPTION: Wedge grip clamps allow for sag before the QUALIFIED
conductor is cut.
QUALIFIED AS NOTED
USE: Installed at any point on the conductor. RETURNED FOR CORRECTION
Date:________________________
BRAND/MANUFACTURER CATALOGUE/PART NO.
PCC Insulators 1061F Name:_______________________
PCC Insulators 1062F Qualifications or corrections are subject to all
requirements of the current issue of the City of
PCC Insulators 1063F Gresham Public Works Standards as modified by
____________________ ____________________ the Project Special Provisions.
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________
____________________ ____________________