Generator Protection
Generator Protection
Purpose
• Generator, prime mover
• External power system, processes it supplies
Considerations
• Expense
• Risk
• Continuity of service
• Damage to system, processes it supplies
• MW rating
• Utility interface requirements
ANSI/IEEE Device Numbers
VFG
(1)
EXTERNAL
SOURCE
OF TERMINAL FAULT 1
CURRENT -
80
60
FAULT
40
F
%O
20
20 45 60 85 100
I
N
DISTRIB
XFMR. 59N
(n:1)
59P
• Resistor size
– terminal fault current of 5-10 A primary
– based on generator line-ground capacitive reactance
• Low fault current minimizes generator damage
• IN contains 3rd harmonic
Phase-ground Fault: High resistance grounding
I
N G
I
N
DISTRIB
59N 27-
XFMR. 3N
(n:1)
Alternate
59P
5/5
51GN
A B
Alternate
51
• 51 must operate
before current
SUBTRANSIENT
decays below
PLE OF RATED
TD ″ = 0.03S
4
MPU
• 3∅∅ fault is worst
CURRENT - MULTIP
∅− ∅
FAULT 3∅ WITH
FULL LOAD @
30°LAG
case
3∅
2
FAULT
51 PICKUP
• Pre-fault load
1.75
current
STEADY-STATE (3∅) STEADY-STATE (∅− ∅)
provides more
0.9
time to operate
0
1
TIME - SECONDS
Voltage-restrained TOC Relay 51V
51V
100%
25%
V
25% 100%
51V
87G
32
POWER
G SOURCE
32
32-1
32-2
NON- OTHER
ELEC 64 49 ELEC 32-2 86NE
TRIPS TRIPS
32-1
86NE 86E
40
G POWER
SOURCE
40
Loss-of-field protection: Power trajectory
jQ
0.75 GEN.
THERMAL
CAPACITY
A
P
BE1-GPS100 and BE1-40Q
CHARACTERISTICS
-0.4 8°
OPERATING
ZONE
-0.6
Stator thermal
protection relay (49) CONSTANT
G RTD SENSING CURRENT
connected to resistor SOURCE
temperature detector
embedded in stator
slot
Typical settings:
LOWER TEMP UPPER TEMP
ALARM TRIP
- Alarm 120°C
- Trip 130°C
Overexcitation protection
• Overexcitation can occur due to:
– higher than rated voltage
– lower than rated frequency at rated or
less than rated voltage
– unit off line and voltage regulator out of service
or defective
• Overexcitation condition produces thermal stress
to the generator.
• IEEE C50.13 specifies that generator should
withstand 105% of rated voltage at full load.
• With unit off line and voltage control regulator at
reduced frequency (without overexcitation
limiter), overexcitation can occur.
Overexcitation protection
1000
• 24 provides V/Hz
protection.
• 24 and voltage
100
GEN
regulators should
be provided with
CONDS
XFMR
separate ac
TIME IN SEC
INVERSE-SQUARED
CURVE IN RELAY potential sources.
10
• Curve indicates
24 characteristic
DEF. TIME
ALARM
and generator
withstand
1
capability.
100% 110% 120% 130% 140% 150%
EXCITATION - V/Hz
Negative Sequence Overcurrent Protection
CAUSE:
Negative sequence currents could result from:
- Unbalanced loads
- Asymmetrical faults
- Open phase conditions
DAMAGES:
Negative sequence current induces double
frequency current in rotor winding.
-> overheats the iron surface, retaining rings, slot
Wedges
Negative Sequence Overcurrent Protection
46
ALARM TRIP
500
300
200
“K” SETTING
100
ADJUSTABLE OVER
50 RANGE 2-40
30
20
MINIMUM PICK-UP
.04 PU 10
40
5
TIME IN SECONDS
3
2 10
1
5
.5
2
.3
.2
.1
.01 .02.03.05 .1 .2 .3 .5 1 2 3 5 10
PER UNIT I2
Student exercice
Generator K factor = 10
Generator nominal current In
Negative sequence current I2 = 30% of In
64F
ALARM 1 ALARM 2
DC Power Supply
RL
GROUND
ROTOR
EXCITER
FAULT
+ -
V
BIAS
A 55VDC
51N
64F
51
60
87G
REG
24 47 87T
62 27 81U
51
59 81O
50
32-1 32-2 40 51V 46
IE
59N 27-
3N
51-
GN
Questions?