Project Name: SPREADER BEAM DESIGN Reference No: RMG18-01

Project Location: - Designer: RMGarcia


Client Name: FRONTKEN PHILIPPINES INC.
Address: - Date: 22-Feb-18
Subject: DESIGN CHECK OF SPREADER BEAM (PADEYE)
Reference: ASTM , AISC

Data:
Max. Working Load (each side) := 15.00 MT := 33.07 kips
Spreader Beam pipe φ := 203.20 mm := 8.00 in
Spreader Beam Total Lenth, LT := 8000 mm := 314.96 in
Weight of Beam (Pipe), w := 43.43 lbs/ft
Pipe Wall Thickness := 0.50 mm

Solving for beam selfweight := w * LT


:= 1.14 kips
Load from Beam weigth, V := 0.57 kips

AISC Manual Total Working Load (each side) := 33.64 kips


Table I-A & I-D
Checking Adequacy of 8" diameter Spreader Beam

Reference for values to be used in calculations to follow.


Calculated properties of Pipe 8" in diameter;

RESULT: SPREADER BAR IS ADEQUATE!!