Professional Documents
Culture Documents
SW (-) 1
8V Equals
Red (+) 2
R > 7 KΩ
R=α
SW (-) 1
8V
Red (+) 2
Operating temp – 25 to 70 o C
*Advantages of inductive system
Long service life by means of non contact sensor.
Very little effect on gauge accuracy.
Fully suitable in corrosive or hazardous atmosphere.
Components of the inductive system
Line transformer
Amplifier Circuit
Relay to switch external circuit
T
Air
Let X equal the vertical distance between the minimum and max. measurable level.(100 in)
Let SG equal SG of fluid (1.1)
Let h equal the max. head press. to be measured in inches of water
Let Range equal Zero to h
Then h = (X) (SG)
= 100 x 1.1
= 110 inH2O
Range = 0 ~ 110 inH2O
20
MA DC
4
0 110
Open Vessels:
A pressure transmitter mounted near a tank bottom measures the press. to the liquid above.
Make connection to high pressure side of the transmitter and vent low press. to the atmosphere press.
head equal the liquid S. G. multiply by the liquid height above the tap.
Zero range suppression is required if the transmitter lies below the Zero point of the desired level
range figure show liquid level measurement.
Example:
2
X
Y
T
Let X equal the vertical distance between the mini & max measurable level (500 in).
Let Y equal the vertical distance between trans. datum line & min. measurable level (100 in).
Let SG equal the SG of the fluid (0.9)
Let h equal the max head press to be measure in inches of water
Let e equal the head pressure produced by Y expressed in inch of water
20
Zero
Suppression
MA DC
4
0 90 540
Closed Vessels:
Pressure above a liquid affects the press. measured at the bottom of closed vessels. The liquid’s S.G.
multiply by the liquid height plus the vessel pressure equals the press. at the bottom of the vessel.
The measure true level the vessel pressure must be subtracted from the vessel bottom pressure to do
this make a pressure tap at the top of the vessels and connect this to low side of DPT. Vessels press. is than
equally applied to both high & low side of transmitter the resulting D.P. is proportional to liquid height
multiplied by the liquid’s S. G.
3
(Low side for Vessels Pressure balance)
X Z
Y
LT
H L
Let X equal the vertical distance between the min & max measurable level (500in).
Let Y equal the vertical distance between the transmitter Datum line and mini measurable level (50in).
Let Z equal the vertical distance between the top of the liquid in the wet leg and trans. datum line (600in)
Let SG1 equal the S.G. of the fluid (1.0)
Let SG2 equal the S.G. of the fluid in the wet leg (1.1)
Let equal the max head press. to be measured in inH2O
Let e equal the head press. produced by Y exposed in inches of water
Let S equal the head press. produced by Z expressed in inches of water
Let Range equal = e – S to h + e – S
Than h = (X) (SG)
= 500 x 1 = 500 inH2O
e = (Y) (SG)
= 50 x 1 = 50 inH2O
S = (Z) (SG2)
= 600 x 1.1 = 660 inH2O
Range = e – S to h + e – S
= 50 – 660 to 500 + 50 – 660
= -610 to -110 inH2O
Zero elevation
20
4
-610 -110
8 Cell Sensors:
4
Isolating Diaphragm
Lead wire
Capacitor plates
Sealing Diaphragm
Rigid insulation
Oil fill
(1) 8 cell sensor
(2) Demodulator
(3) Oscillator control Amplifier
(4) Oscillator
(5) Current control Amplifier
(6) Current control & current Detector
(7) Current µ meter
(8) Reverse polarity protection
(9) Voltage regulator
(10) Zero elevation & suppression
(11) Damping Adjustment
(12) Span Adjustment
(13) Linearity Adjustment
The capacitance between the sensing diaphragm & either capacitor plate is approx 150 PF
20
8 Cell Sensors:
5
The 8 Cell is a variable capacitance Sensing module in the Rosemount model 1151 Series Alpha line
Pressure transmitter.
This sensor is complete sealed module that allows direct electronic sensing of pressure induced
diaphragm deflection Diff. capacitance between the sensing diaphragm & capacitor plates is electronically
converted to a two wire 4-20 or 10-50 ma dc signal.
This approx is based on following concepts.
C1 – C2
P=K
C1 + C2
Where:
P- is the process Diff. Pressure.
K- is a constant.
C1- Capacitance between the high pressure side & sensing Diaphragm.
C2- is the capacitance between low pressure side & sensing diaphragm.
Convert to 4 ~ 20 ma to 1 ~ 5 V Dc
I = V/R
20 = 5/R
5 x 10 x 10 x 10
R= = 1ma = 10-3
20
R = 250 Ω
o
o
F o
o
C 100o K o
R
212 373.2o 671.7o Steam Point
Rt = Ro (1 + α t)
= 100 (1 + 385/100000 x 100oC)
Rt = 100 (1 + 0.385)
Rt = 100 x 1.385
Rt = 100 x 1385/1000 = 138.5 Ω
100 oC = 138.5 Ω
CV Stame Desided:
(Alkaline) 14 PH
(Basic) |
|
Neutral 7 PH
|
|
Acidic 0 PH
Question – Answers:
Q GP
∆P
No of US gallon/ min of H2O which pass through a fully open valve at pressure drop of 1 PSI at 60 oF.
8
B
R2
R1
G C
D
A
R3
Note: install the transmitter so that the minimum level is at least 45mm above the center axis of the
transmitter.
Mini
See Note
9
Maxi Span = XGL
Zero Suppression = YGL + ZGS
GL = SP. Gravity of liquid in Tank
GS = SP. Gravity of liquid in connecting line
Example:
h X h=X h X = 80 inches
e=Y e Y = 5 inches
s=Z s Z = 10 inches
(GL) SP. Gravity of tank = 0.8
Mini
Range = e + s ~ h + e(GS)
+ s SP. Gravity of connecting line = 0.9
e Y h Span = X GL
= 80 x 0.8
= 64 inH2O
Zero Supp. = Y GL + Z GS
s Z = 5 x 0.8 + 10 x 0.9
LT =4+9
= 13 inH2O
Range = 13 To 64 +13
= 13 To 77 inH2O
10
Span = X GL
Maxi Dry leg
Zero Supp. = Y GL + Z GS
Span = 80 x 0.8 = 64 inH2O
Zero Supp. = 5 x 0.8 + 10 x 0.9
X =4+9
= 13 ~ 64 inH2O
Mini
Z
LT
Span = X GL
Wet leg
Zero Supp. = Y GL – d GS
Maxi Span = 80 x 0.8 = 64 inH2O
Zero Elev. = 120 x 0.9 – 20 x 0.8
= 108 – 16
X = -92 inH2O
d
-92 To – 92 + 64 = -28
Mini -92 ~ -28 inH2O
Y
LT
11
Differential Range with close Tank (capalary Type):
LO Span = X GL
Zero Elev. = d GS – Y GL
Maxi Span = 80 x 0.8 = 64 inH2O
Zero Elev. = Y GL – d GS
= 20 x 0.8 – 120 x 1.07
X = 16 – 128.4
d = -112.4
Mini Range = Zero To Zero + Span
HI = -112.4 ~ -112.4 + 64
Y = -112.4 ~ -48.4 inH2O
LT
Calculate the output current as a function of Pressure using the formulas below DC output between 4~20ma.
Reference Pressure. – Lower Range Limit+ 4
O/P(ma) 16 x
Upper Range Limit – Lower Range Limit
50 - 30
O/P(ma) 16 x +4
150 – 30
= 16 x 50 – 30 / 150 – 30 +4
= 16 x 20 / 120 + 4
= 16 / 6 + 4
= 6.67 ma Dc
12
-2 – (-2)
O/P(ma) 16 x +4 0 – (-2)
10 – (-2) O/P(ma) 16 x +4
10 – (-2)
= 16 x 0 / 123 + 4
=4x0+4 = 16 x 20 / 12 + 4
=0+4 =8x1/3+4
= 4 ma =8/3+4
2
-2 kg/cm = 4 ma = 2.66 + 4
= 6.66 ma
0 kg/cm2 = 6.66 ma
1 – (-2)
O/P(ma) 16 x +4
10 – (-2) 7 – (-2)
O/P(ma) 16 x +4
= 16 x 3 / 12 + 4 10 – (-2)
=4x1+4
=4+4 = 16 x 9 / 12 + 4
2
1 kg/cm = 8 ma =4x3+4
= 12 + 4
= 16 ma
7 kg/cm2 = 16 ma
13
N
FLOW
Model 1151 14
Samart P. T.
399oC = 248.69 Ω
- 1oC = 99.61 Ω
- 10oC = 96.09 Ω
- 30oC = 88.22 Ω
- 50oC = 80.31 Ω
- 100oC = 60.28 Ω
- 200oC = 18.48 Ω
75
Quick
Opening
50
Linear
25
Equal
Percentage
0
0 25 % 50 % 75 % 100 %
Lift (Valve Opening)
15
Step No.
Comments
SignalAction SignalCondition
% DI – 1 Start P. B. Y Y
% DI – 2 Switch A N Y Y
% DI – 3 Switch B N N
% DI – 4
% DI – 5
% DO – 1 Valve A Y N
% DO – 2 Valve B Y N
% DO – 3
% DO – 4
% DO – 5
Sequence Table Entry Exam:
Start MFCD
PB
Valve A
Switch A
Tank
Switch B
Valve B
Control Valve:
Single Seated Valves:
A Single seated valve should always be installed with flow tending to open to insure dynamic
Stability of the trim (High press. drop).
Double Seated Valves:
For higher pressure drop and large valve size (Tight shut off).
Type of Body Design:
16
Globe valve: Single or double seated.
Angle valve: Butterfly valve
Three way valve
Pinch valve
Saunders valve
Ball valve
Angle valve
Que: Why transmitter out put signal start from 3 ~ 15 PSI or 4 ~ 20 ma?
Ans: Linear and can check up whether it’s “Live Zero” or dead band.
Que: Why is ma signal preferred for signal transmission?
Ans: noise Reduction and no current drop for long transmission line.
Que: Why is flow measured in square root?
Ans: flow varies directly as the square root of DP. Since this flow varies directly the open does not indicate
flow directly the flow can be determined by taking the square of the pen F α √DP.
Linear:
The valve opening to flow rate is a linear cure.
Equal percentage :
Equal increment of valve opening it will give equal in flow rate range at small opening the
flow will also be small.
Quick opening:
At small opening the increment in flow rate higher opening the rate becomes stead.
Use of valve positnor:
1. Quick action & positioning of control valve.
2. Valve hysterics.
3. Valve used on viscous liquid.
4. Split Range.
5. Line pressure changes on valve.
6. Valve bench set not STD.
7. Reversing & direct action
8. Spring legs actuator.
9. Changing valve characteristics.
Ratio Control loop:
Flow A
17
FT
FY
FY × or ÷
(Ratio Station)
Set Point
FIC
FY I
P
FT
Flow B
Mainly Used for blending application. System maintaining flow B to wild flow B
18
Set
FT
Steam Turbine
FIC
P&R
Steam Flow Out
I
P
FT FIC
P&R
BFW LT
P3 = R (P2 – P1 – K) + P4 + K0
R = gain
K1 = Adj. Suppression
K0 = Adj. BAIS
Cascade Control (Two Distinct Advantages):
1. Disturbance affecting the secondary variable can be corrected by the secondary controller
before a pronounced influence is fell by the primary variable.
2. Closing the control loop around the secondary part of the process reduces the phase lag seen by
the primary controller resultant in increased speed of response.
19
Que: what type bonnet use on high temp. & low temp.?
Ans: High temp.: With Radiating fin low temp.
Low temp.: Extended bonnet.
TYPE OF THERMOCOUPLE:
TYPE RANGE
Iron constantan (J) -210 – 1200oC
Chromel Alumal (K) -270 – 1900oC
Chromel constantan (E) -270 – 1000oC
Cupper constantan (T) -270 – 400oC
Platinum pt-Rhodium 10% (S) -50 – 1700oC
Platinum pt- Rhodium 13% (R) -50 – 1700oC
PV
Cascade means two controller in series, one of them is master or primary & secondary is the secondary slave,
the O/P of the slave controller operates the final control elements.
20
T:1 T:2
TON
T:1 (EN)
DN Preset. 0.35 (DN)
DN Acc…….
T:1
TON
T:2 (EN)
DN Preset. 0.35
Acc……. (DN)
T:2
(0.25 Flash)
TT
Abnormal
T:2 output
( )
TT
Lamp blinking indication leader logic.
Bit = 0 or 1
Byte = 8 bit
Kilobyte = 1024 bytes/bit
Mega byte = 1024 KB
Giga byte = 1024 MB
Reset PB
R1 Accept PB
R1
R1
Hooter
21
MMHg 0.001359 1 0.00133 1.3332 13.5951 0.01934 0.13332
Bar 1.01972 750.062 1 1000 10197.16 14.5038 100
M.Bar 1.01972x10-3 0.7501 0.001 1 10.197 0.0145 0.1
MMWC 0.0001 0.07355 0.000098 0.098 1 0.00142 9.8067x103
PSI 0.7031 51.715 0.6895 68.950 703.07 1 6.8947
KPA 0.0101972 7.50662 10-2 10 101.9716 0.145338 1
Sensor
Valve Positnor:
Working Principle: positnor is pneumatic force balance device. Which ensures the control valve
plug position is always directly proportional to the valve of the controller signal pressure.
SIOM communication cable
23
PH indicator
PH
Amplifier
RTD
Glass
(PH)
Reference
PH Measurement:
The measurement of PH requires the use of specially designed electrodes two electrodes are used for
each installation one produces a change in voltage as the PH of the Solution the other electrodes maintains a
constant voltage the most common ph sensitive electrodes is the glass electrodes and the most common
reference electrodes is the calomel electrodes.
Together these electrodes form an electrolytic cell whose O/P equal the some of voltage produced by
the two electrodes this voltage is applied as the input to a null balance mill volt potentiometer similar to that
used with a thermocouple included in the circuit is temperature compensating resister this is immersed in the
solution its resistance changes with temperature of the solution so that the ph measurement is correct at the
operating temperature.
PH means Percentage of hydrogen, Ions, Ph is useful of given solution as acidic basic.
Conductivity:
All ions in a solution however affect its ability to pass an electric current measurement of the ability
(conductivity) useful in many industrial process, such a measurement can be made by immersing a pair of
electrodes of know area a certain distance apart and then measuring the resistance between them,
conductivity is expressed in mhos measured between two electrodes each having are of 1squre centimeter and
place 1cm apart.
A mho equals 1/1ohm
The conductivity cell can be used with an A. C. Wheatstone bridge as with PH measuring system a
temperature compensating resistor is used in the circuit to correct for variation in temp. of the solution.
Meter
Electrodes
1cm
1cm 1cm
Conductivity: means to ability to pass of current from the solution the conductivity is used in plant for
defined the dissolved gases in the water specially NO2 & CO2.
24
Flow control: normally equal percentage valve is used.
Pressure control: normally linear valve is used to constant pressure drop.
Temp. control: normally equal percentage use.
Level: normally linear valve used.
Que: What is the used of single seated valve?
Ans: The single seated valve use on smaller size & in valves of larger size where an absolute shut- off is
required the use of single seated valve is limited by pressure drop across the valve in the almost closed
position.
Que: What is used of double seated valve (size: 150mm To 400mm Single & double seated Valve)
Ans: Double seated valve always give some leakage but splits the flow between is balanced across the two
plugs hence good for high pressure drop. It is used on bigger size valve & high pressure system.
Que: What is the use of angle valve?
Ans: Very high pressure drop required.
Que: What is use of butter fly valve? (size 50mm ~ 800mm)
Ans: Small pressure drop across the valve is allowed the butter fly fully open when the dies rotates by 90o a
drawback of this valve that even a very small angular displacement produced a big change in flow.
Que: What is the three way valve used?
Ans: Where a dividing or mixing of flows according to a controlled ration is required.
-Saunders (Rubber lined valve) on corrosive materials.
Que: What are the different type of plug?
Ans: V port plug, contoured plug.
V port plug: used on double seated valve have a more constant off balance are.
Contoured plug: single seated valve with small trim size.
V Port
Contoured
Pe
RVDT mod CA2 Q
+
Osci
lator
Zero
Span
Ans: The variation in buoyancy resulting level varies the net all of the displacer increasing or decreasing the
load on the torque arm this changes is directly proportion to the change in level and Sp. Gravity of the liquid
the resulting torque tube movement varies the angular motion of the rotor in the RVDT (Rotary Variable Diff.
Transformer) providing a voltage change proportional to the rotor displacement which is contorted and
amplified to a D. C. current.
Different types of temp. measurement.
- Mercury in glass thermometer
- Bimetallic thermometer
- Pressure spring thermometer
- Thermocouple
- RTD
- Pyrometer: Radiation / Optical
Different types of pressure measurement.
- U Tube manometer
- Diaphragm
- Bellows
- Capsule
- Bourdon tube
- Spiral and Helix
Used of Posinor:
1. Speed up valve response, specially for long pneumatic signal line and large volume actuator.
2. Over comes valve hysteresis.
3. Over come high forces on steam e.g. High pressure in line gland packing friction etc.
4. “Bench set” i.e. to mach valve spring range to controller output signal e.g. valve spring may be
0.3 ~ 1.1, 6.30 PSI etc. positnor give O/P to valve to 0.3 ~ 1.1, 6 ~ 30 PSI as required for input
of 3 ~ 15PSI.
5. Split range
6. Reverse action
7. After valve characteristic with came
26
Que: What is interface level? How do you calibrate it?
Ans: When a vessel in filled with two liquid of tag different specific gravities the level measurement refers to
as interface level
DP = H (D – d)
On a level set different of tag Sp gravity
Que: How will you calibrate a level troll in the field?
Ans: 1. first close both the primary Isolation valve and drain the liquid inside the chamber.
2. Adjust the Zero.
3. Connect a PVC tube to the drain point as show in hook up.
4. Fill it to the center if the top flange.
5. Adjust the SP. Gravity or span adjustment.
6. Fill up to 50% check linearity.
Que: How will you calibrate an interface level troll?
Ans: on an interface level troll there are two liquid of two different SP. Gravity.
1. The level will be Zero when it is full of lighter liquid
Zero % level = H & D.
= 500 x 1
2. the level will be 100% when it is full of heavier liquid
100% level = H x D
Que: What is Absolute Pressure?
Ans: Absolute Pressure is the total pressure present in system
Absolute press = Gauge Press + Atmospheric press. ?
Que: What is Abs. Zero Pressure?
Ans: The abs. Zero = 760mmhg.
Que: What is maximum Vacuum?
Ans: the maximum vacuum = 760mmhg.
Que: What is the Vacuum?
Ans: any pressure below Atm. Pressure is Vacuum.
Set point
Manual
Deviation
M
Σ To final
Amplifier Element
A
P D
+
Gain
Reset
input from measurement Transmitter is compared with the set point. Voltage is produce a deviation
signal the deviation signal is combined with a characterized feedback signal to provide the input for the
27
function generator amplifier. This amplifier output is delivered to the feed back network and this final output
this is 4 ~ 20ma dc signal for actuator of final operator. (PID detail page no.)
Que: What is the type of tap used orifice plate?
Ans: Flange Tap: those are most commonly used on pipe size of 2 inches or larger. They are located in the
orifice flange which from up stream and 1 inches down steam from the flange of orifice plate.
Corner Tap: on pipe size less than 2” common tap located directly at the flange of the orifice plate.
Vana Contract: located at 1 pipe diameter up steam and at point of minimum pressure down steam these most
widely used for measurement of steam.
Que: What is the use of link connector of the valve position?
Ans: The link service as the feedback to the valve any valve movement is sensed by this link some time due
to line pressure changes on H. P. service the valve position may be change the link in turn senses this change
& the positnor will produced an output which will operate the valve to the original position.
Que: What is emergency shutdown system in boiler and furnaces?
Ans: Boiler: 1. High, low level
2. Fuel low pressure
3. At. Steam low pressure
4. Drum pressure high
5. Return oil pressure high
6. Fan trip
7. Flame failure
Furnaces: 1. Fuel pressure high, low
2. Feed low
3. Flame failure
4. Fan trip
Que: What does a transmitter output start from 4 ~ 20ma?
Ans: the transmitter output start from what knows as “live Zero” this system has specific adjustment.
1. The system automatically alarm when the signal system becomes inoperative.
2. the output curve in linear (Ratio 1:5)
Que: Why do you have small hole some times above or below the orifice plate?
Ans: 1/8” hole in orifice plate installed in horizontal lines, bottom of line gas or hydrocarbon liquids contain
traces of meter, top of line for liquid traces of vapors as non condensable.
Hole
Diaphragm
Supply Steam
Valve
Ball Valve
Output
Spring
Exhaust
29
Amplifier
TC
Motor
Unknown Signal
Signal
Slide wire
Measuring
CKt
Constant
Voltage
Signal
(Known Signal)
Resistance Thermometer: At the temperature of the resistance bulb Rt rises, it resistance rises because of this
bridge Un-balance. This unbalance is detected by the mill voltmeter cell sing it to defect third wire to a point
that will used to compassion restore balance to of lead wire the circuit when calibration to the circuit precision
resistor is substituted for the temperature bulb and the battery voltage is adjust by varying Rb until the meter
reads the correct temperature for this resistance for instance if a platinum bulb is to be used a press ion of 100
ohms would require that the meter reading 32o F (0oC).
The resistance bulb has there leads. This is necessary so that the same amount of lead wire is used in
both branches of the bridge this arrangement is generally preferred because the lead length may be lengthened
or shortened with out affecting the meter reading.
RY
R1
V
Rb
Rt1 R2
Rt1 = Rt2
Rt
30
On the absolute pressure scale the zero point is at the absolute zero pressure point.
The vacuum scale has its zero at atmospheric pressure and its maximum point at absolute zero.
The pressure scale in figure notice that the absolute pressure scale includes the gauge pressure scale &
vacuum scale thus a pressure of 10” of mercury absolute may also be expressed as vacuum of 20in/Hg or
Gauge pressure -20in/Hg.
20
To maximum
15
Gauge Pressure
10
5
0
Negative
0 Vacuum
20” 5
vacuum 10 Pressure
or 20” 15
Gauge 20
Press.
‘X’ 10” 25
30 0
Orifice Plate: The orifice plate is quite simple & inexpensive. It is the easy to install & replace. There is a
much data available for calculation of correct size. The orifice plate not so accurate as either the venture or
flow normally and does not have as good recovery. It cannot be used with high beta ratios functionally the
orifice plate is subject to erosion & damage, but it is easy replacement offset this hence it is most avidly used
for primary flow element.
VENTURI TUBE: The venture tube is most expensive & accurate. High beta ratios above (0.75) can be used
with good results the pressure recovery of the venture tube is excellent which means that there is little
pressure drop through it functionally the venture tube is good since it does not obstruct abrasive sediment in
fact because of its shape it resists wear effectively.
Venture tube is used for large pipelines it is more accurate than the orifice plate but considerably more
expansive & difficult to install.
FLOW CALCULATION: Rate of flow =
Q = EAo √2gh
Where: Q = flow rate (volume/units of inch)
E = efficiency Factor
Ao = area of orifice in square feet
31
g = acceleration due to gravity
h = diff. pressure across orifice in feet
TURBINE METER: The pulse generating turbine flow meter consist of precision turbine wheel mounted on
bearings inside a length of pipe and an electromagnetic coil mounted on the pipe at the right angle to the
turbine wheel fluid passing through the pipe causes the turbine wheel to turn at the speed which varies with
the velocity of the flowing as each blades of turbine wheel pass the coil it interrupts the magnetic field of the
coil producing of an electrical pulse the frequency of the pulse very with the velocity of the fluid flow.
Orifice Plate:
Concentric: The concentric orifice plate is used for ideal liquid as well as gases & steam service, this orifice
plate has a hole concentric hence know as a concentric orifice plate
.
Eccentric Orifice Plate: The use of this is made in viscous & slurry flow measurement
Segmental Orifice Plate: The segmental orifice plate has the hole in the form of segment of a circle. This is
use for colloidal & slurry flow measurement.
32
P + I + D: Derivate action help the controller overcome system inertia and result in faster, more precise
control derivation action occur when ever the measurement signal changes. Under steady conditions the
derivate action does not act, Derivate allows the controller to inject more corrective action.
Use: on temperature control.
How do you carry out piping for DPT, on liquid, Gas, Steam service?
Liquid line on liquid line transmitter mounted below the orifice plate since liquid have a properly of self
draining.
_
+
Gas Service: on Gas service the transmitter mounted above the orifice plate because gas have property self
venting & secondary condensate formation.
_
+
Steam Service: On steam service the transmitter is mounted blow the orifice plate with condensate pot the
pot should be at the same level.
33
H L
PD
T
Suction Remote Discharge
Line Set Ratio Line
FRC
FT FY
Ratio controller
When the suction pressure drops and discharge up the compressor start surging the PDT sensor
this & give the signal to the FRC which will open the by pass valve.
Que: What is SQ root extractor why it is used?
Ans: Sq root extractor extracts the square root of the input signal & produce and output signal.
Use: Flow measurement signal are normally SQ root which a produced from DPT so convert these in to linear
signal.
An operator tells you that a control valve is struck up flow will you checking?
1. First of all get the control valve by passed from operations.
2. Check tight to the diaphragm of the control valve.
3. Disconnect if possible the actuator steam & from control valve steam.
34
4. Stroke the actuator & see whether the actuator operates or not if not then the diaphragm may be
punctured.
5. if the actuator operates connect it back to the plug steam stroke the control valve if it doesn’t operate
loosen the glands nut & bolt & see. If it operates, if it doesn’t then the control valve has to be removed
from the line to w/s(work shop).
Que: Where is an air to close & air to open control valve used?
Ans: Air to closed 1. Reflux line
2. Cooling water
3. Relit service
Air to Open: 1. Feed line
2. Steam Service
Que: What is intrinsically safe system?
Ans: Intrinsic safety is a technique for designing electrical equipment for safe use in location made hazardous
by the pressure of flammable gas or vapors in air.
Defn: Intrinsically safe circuit in one in which any spark or thermal effect introduced either normally or under
specified fault condition is incapable of causing ignition of a specified gas or Vapors in air mixture at the most
easily ignited concentration.
Displacer type level measurement: The level troll is one of most common instrument used for
measurement level in closed tanks this instrument works on ARCHIMEDES principle the loss in weight of
a body immersed in a liquid is equal to amount of liquid displaced.
Draw & Explain flow Closed loop:
O/P
5D
O/P
Impulse line I
A/ P
S
FT O/P
+ FIC A/C Supply
_ I/P
Equalizing
Valve
36
Derivative Action: The connection of the derivative capacitor across the feed back circuit delays feed back
until the capacitor is charged to a value approaching amplifier value of derivate resister. The resister is
variable and constitutes derivative adjustment.
Short of Derivative Action: The derivative action have bad go to proportional controller so where the
process leg is high at that time the derivate controller is used generally the derivative controller is used in
temp. measurement.
The temp. measurement the sensing element sense the temp. of vessel but sometime is taken by it in
some process these lagging feature is not effective so the at that time the derivate controller is use.
Conductivity meter: The conductivity meter have a hole tube made of plastic in which there ring is
provided the generally the ring are made of carbon so the maintenance is minimum. Two terminal is taken
out from the cash from which the supply is given no when fluid passes through the two ring the electrical
circuit is completed & the current is passes which is proportional at the conductivity of liquid.
Turbine Supervisory System: Main three Section of system.
1. Vibration measurement
2. Axial shift measurement
3. Eccentricity measurement
h h h h h
h
Genra
HP IP LP tor
4
1 2 3 7
5 6 V
V V V
1. Horizontal Vibration
2. Horizontal Vibration
3. Horizontal Vibration
4. Horizontal Vertical Vibration
5. Horizontal Vertical Vibration
6. Horizontal Vertical Axial Vibration
7. Horizontal Vibration
Measuring Unit = Micro ohms
Vibration Measurement mi> measuring pickup slestnic velocity p\kir ni[ hi[y C[. j[mi>
cylindrical houring n) a>dr permanent magnet n) rcni kr[l) hi[y C[. ai permanent magnet siY[
moving coil j[iD[l) hi[y C[. Set frequency 14HZ riKvimi> aiv[ C[. jyir[ vibration aiv[ Ryir[
permanent magnet move Yiy C[. aiY) EMF measuring coil n) a>dr uRpn Yiy C[. ai pick up ni[
output vibration ni smp\miN mi> hi[y C[.
Chemtrol level troll Weight calibration:
Displacer length = 650mm
Diameter = 48.6mm
Weight = 26489mg
Volume = πr2h
= 22/7 x 24.3 x 24.3 x 650
= 1205m3
37
Loss of weight = 1205 x 0.75 SPG
= 879.65
Vent Plug
Drain Plug
1. The top plug is a vent plug for venting the air entrapped side the cell.
2. The bottom is a drain plug for draining the liquid accumulated inside the cell.
Valve Sizing:
FL = CLd2 = √(P1 – P2) Liquid
W
FG = CGd 2 = [√ (P1 – P2) (P2)]
2TQ
FS = CSd2 = √ (P1 – P2)
V
Where: FL = flow of liquid gal/hrs.
FG = flow of gas cu ft/hrs
FS = flow of Vapor lb/hrs
Cl, CG, CS the appropriate discharge co-efficient.
P1 = up stream pressure in PSIG
P2 = down stream pressure in PSIG
d = valve diameter in inches
W = density of liquid lb/w ft
V = specific volume of the vapor cu ft/w at the down stream condition.
T = absolute temp. of the following gas
Q = Specific gravity of dry gas relative to air in the same temp. & pressure.
39