You are on page 1of 8

Technical Paper

Cutler-Hammer Effective: June 2001 Page 1

Supersedes SA 199
pages 1-12, dated January 1996
David D. Roybal, P.E. Automatic
Cutler-Hammer
Fellow Application Engineer Transfer Switches
A Performance Comparison —
Molded Case Switch Versus
Contactor Type

Table of Contents Page Part I: Abstract application for mechanically held


About the Author . . . . . . . . . . . . . . . . 1 devices is for lighting control, where
Molded case switch type automatic using a latched device allows a user
Part I: Abstract. . . . . . . . . . . . . . . . . . 1 transfer switches with trip units and
Part II: “Circuit Breaker” to avoid having to reset all contactors
“contactor” type automatic transfer after a utility outage.
Versus “Contactor” switches protected by circuit breakers
Design Transfer Switches . . . 1 perform equally for various fault Transfer switches are also capable of
Part III: Time-Current Coordination . . 3 conditions. High withstand molded high endurance, but not nearly as great
Part IV: Transfer Switch case switch type automatic transfer as that of a motor starting/lighting
Performance During a Fault . 5 switches without trip units perform contactor. UL 1008 defines the mini-
Part V: Conclusions . . . . . . . . . . . . . . 8 exactly as “contactor” type automatic mum endurance of a transfer switch.
Part VI: References . . . . . . . . . . . . . . . 8 transfer switches, except that “contac- This is detailed in Table 1. Both “con-
tor” type designs have limited with- tactor” and “circuit breaker” designs
stand capabilities. Such “contactor” meet these minimum UL 1008 require-
About the Author type designs have potential problems ments as evidenced by their UL label.
in applications with upstream power Some transfer switch manufacturers
David D. Roybal received the Bachelor circuit breakers having short delay trip may publish endurance capabilities in
of Science degree in electrical engi- characteristics. excess of these minimums, especially
neering from Santa Clara University, for the larger ampacity units.
Santa Clara, California, in 1969. Part II: “Circuit Breaker”
Versus “Contactor” Design Transfer switches known as “contactor”
He is a Fellow Application Engineer with
Transfer Switches designs do not use motor starting/light-
Cutler-Hammer in Lafayette, California. ing type contactors. Rather, “contactor”
He previously was an engineer with A transfer switch is a device for trans- type transfer switches — along with
Westinghouse for more than 24 years. ferring one or more load conductor “circuit breaker” type transfer switches
connections from one power source — in fact use circuit breaker design
Mr. Roybal is a Senior Member of the to another.➀ Many engineers believe
Institute of Electrical and Electronics contacts, arc chutes, and arcing horns.
that there are two types of transfer Moreover, most “contactor” type
Engineers (IEEE) and presently an switch designs, “contactor” designs
officer of the San Francisco Chapter transfer switch manufacturers pur-
and “circuit breaker” designs. There are chase these parts from manufacturers
of the Industry Applications Society. indeed two different design concepts, of circuit breakers. Thus “contactor”
He is a member of the National Fire but this terminology is misleading. type transfer switches actually owe their
Protection Association (NFPA), the “Contactor” type transfer switches do design more to circuit breaker technol-
National Society of Professional not use motor starting/lighting contac- ogy than to contactor technology.
Engineers (NSPE), the International tors, and “circuit breaker” type transfer
Association of Electrical Inspectors switches do not use circuit breakers. Transfer switches known as “circuit
(IAEI), and the NEMA California Safety breaker” type use specially designed
Contactors are NEMA devices designed switching devices that are typically
Regulations Advisory Committee. for motor starting and lighting control
He is a registered professional engi- molded case switches; circuit breakers
which are capable of high endurance are an option. The contacts, arc chutes,
neer in the State of California. The (long-life switching capabilities). Their
Westinghouse Board of Directors and arcing horns are completely
no-load and full-load mechanical opera- enclosed in an insulated housing, as
awarded him the Westinghouse Order tions can number in the millions. They
of Merit in 1993. He was a recipient they were originally designed to be.
can be electrically held or mechanically The switching devices themselves
of the IEEE Third Millennium Medal held devices. Electrically held devices
in the year 2000. are further required to meet UL 1087
will drop out upon loss of control volt- (Molded Case Switches) or UL 489
age. A typical application is as part of (Molded Case Circuit Breakers)
a motor starter. Mechanically held requirements, as well as UL 1008
devices have mechanical latches or (Automatic Transfer Switches)
designs which inherently remain closed requirements. This means that “circuit
upon loss of control voltage. A typical breaker” type transfer switches are
Table 1 — ATS Endurance (UL 1008 Table 30.2)
Switch Ampere Rate of Number of Cycles of Operations
Rating Operation
With Current Without Current Total

0–300 1 per minute 6000 – 6000


301–400 1 per minute 4000 – 4000
401–800 1 per minute 2000 1000 3000
801–1600 1 per 2 minutes 1500 1500 3000
➀ NEMA ICS 10-1993, AC Automatic
Transfer Switches.
1601 and above 1 per 4 minutes 1000 2000 3000

TP.15A.01.T.E
Technical Paper Automatic Cutler-Hammer
Page 2 Effective: June 2001 Transfer Switches

held to a more rigorous testing stan- current protection and those using normally have much higher withstand
dard than “contactor” type switches. molded case switches without over- and endurance ratings than the
The main contact assemblies in “circuit current protection. Smaller ampacity “contactor” type transfer switches.
breaker” type transfer switches are designs use molded case switches with
subject to periodic UL 489 and UL 1087 fixed instantaneous trip units set high to “Contactor” type transfer switches and
follow-up testing versus the one-time- allow the maximum withstand of the “circuit breaker” type transfer switches
only UL 1008 design test for “contac- device. Other molded case switches, using molded case switches with
tor” type automatic transfer switches. such as the Cutler-Hammer Type SPB instantaneous trip elements perform
Typically, the switching devices in a Insulated Case Switch, can be provided identically when applied in systems
“circuit breaker” type transfer switch without trip units. These are switches with molded case circuit breakers.
are oversized for the ampacity of the that have extremely high withstand and When the upstream breaker is a power
transfer switch. For example, an 800 endurance ratings, often greater than circuit breaker with no instantaneous
ampere “circuit breaker” type transfer those of a comparable “contactor” type trip element, it may have a short delay
switch uses 1200 ampere switching switch. Typical ratings are shown in time setting for coordination with other
devices, as shown in Table 2. Thus Table 3. As an alternate design, the devices under high fault conditions.
the contacts used in a “circuit breaker” transfer switches can be provided When a downstream fault occurs, the
type transfer switch are likely to be with molded case switches having power circuit breaker can delay tripping
larger than the contacts used in a overcurrent and ground fault trip units. in order to allow the downstream
“contactor” type of equal rating These are used where integral over- device to selectively clear the fault.
because of this oversizing. current protection is desired, such as
in service entrance applications. If the power circuit breaker short delay
There are actually two types of “circuit time setting is set high, fault current
breaker” transfer switch designs: those Since “contactor” type transfer may flow in excess of the limited time
using molded case switches with over- switches do not use contactors and and current withstand ratings of a
both “contactor” and “circuit breaker” “contactor” type transfer switch. A
Table 2 — Molded Case Switch ATS type automatic transfer switches use “circuit breaker” type transfer switch
With Instantaneous Trip Elements circuit breaker parts, what is their using molded case switches without
difference in performance? Under trip units can be selected to withstand
UL 1008 UL 1087/UL 489 UL 1087/UL
Switch Cutler-Hammer 489 Frame most downstream fault conditions, the short delay time, while a transfer
Ampere Molded Case Frame Ampacity both designs will perform identically, switch design using molded case
Rating i.e., the upstream breaker will trip and switches with instantaneous trip ele-
the switch logic will initiate the trans- ments would merely trip and reset. In
100 F 150 fer sequence to the alternate source.
150 K 225 some situations the high-magnitude
150 K 400 “Contactor” type transfer switches fault may cause a drop in voltage
and “circuit breaker” type transfer which could initiate a transfer
225 K 400 sequence for either the “contactor”
300 K 400 switches using molded case switches
without trip units perform identically type transfer switch or the “circuit
400 L 600
under all circumstances. However, it breaker” type transfer switch. When
600 M 800 this occurs, the transfer switch will
should be noted that these “circuit
800 N 1200 attempt to interrupt the fault current.
1000 N 1200 breaker” type transfer switch designs
The engineer may find that the limited

Table 3 — Transfer Switch Withstand Ratings (Time and Current)


Transfer UL 1008 3 Cycle Rating Extended Rating
Switch
Cutler-Hammer Cutler-Hammer Manufacturer Manufacturer Manufacturer Cutler-Hammer Manufacturer Manufacturer
Ampere
Transfer Switch Transfer Switch “A” “R” “Z” Transfer Switch “R” “A”
Rating
with Molded with Type SPB Transfer Transfer Transfer with Type SPB Transfer Transfer
Case Switches➀ Switches➁ Switch➀ Switch➀ Switch➀ Switches➁ Switch➀ Switch➀

30/40 65 kA N/A 10 kA➂ N/A 10 kA➂ N/A N/A N/A


70/80 65 kA N/A 10 kA➂ N/A 10 kA➂ N/A N/A N/A
100 65 kA N/A 10 kA➂ 42 kA 10 kA➂ N/A N/A N/A
150 65 kA N/A 10 kA➂ 42 kA 10 kA➂ N/A N/A N/A
225/260 65 kA N/A 35 kA 42 kA 35 kA N/A 40 kA 10 cycles N/A
300 65 kA N/A N/A N/A 35 kA N/A N/A N/A
400 65 kA N/A 35 kA 42 kA 35 kA 35 kA➃ 60 cycles 40 kA 10 cycles N/A
600 50 kA➅ 100 kA 50 kA 65 kA 50 kA 35 kA➃ 60 cycles 40 kA 10 cycles N/A
800 50 kA➅ 100 kA 50 kA 65 kA 50 kA 35 kA➃ 60 cycles 40 kA 10 cycles N/A
1000 50 kA➅ 100 kA 85 kA 85 kA 50 kA 35 kA➃ 60 cycles 50 kA 10 cycles 65 kA 30 cycles
1200 N/A 100 kA 85 kA 85 kA 50 kA 35 kA➃ 60 cycles 50 kA 10 cycles 65 kA 30 cycles
1600 N/A 100 kA 100 kA 100 kA 100 kA 51 kA 60 cycles 50 kA 10 cycles 65 kA 30 cycles
2000 N/A 100 kA 100 kA 100 kA 100 kA 51 kA 60 cycles N/A 65 kA 30 cycles
3000 N/A 100 kA 100 kA 100 kA 100 kA 51 kA 60 cycles N/A 65 kA 30 cycles
4000 N/A 100 kA 100 kA 100 kA 100 kA 85 kA 60 cycles N/A 65 kA 30 cycles
➀ Symmetrical rms amperes at 480 volts and breakers are tested at a more severe 15% ➃ Also available with a rating of 51 kA at
20% short circuit power factor (X/R ratio of 4.9). short circuit power factor (X/R ratio of 6.6) 60 cycles.
➁ Symmetrical rms amperes at 480 volts and which results in a higher fault duty. ➄ Contact Cutler-Hammer for availability.
15% short circuit power factor. Power circuit ➂ 1.5 cycles only. ➅ 4-pole units rated 35 kA.

TP.15A.01.T.E
Cutler-Hammer Automatic Technical Paper
Transfer Switches Effective: June 2001 Page 3

interrupting rating of “contactor” type


transfer switches is not adequate for 10000

the system design and may select the 5000


self-protecting “circuit breaker” type
design instead. The use of “contactor”
type transfer switches in these cases 1000
would be a misapplication.
500
The electrical engineer must deter-
MAXIMUM
mine which design characteristics
are preferable based on the system T 100
requirements and the performance of I
M 50
the transfer switch to be applied. This E MINIMUM
paper provides information that can be
I
used in making that choice. N
10
Part III: Time-Current Coordination S
E 5
C
To better understand the operation of O
molded case switches used in transfer N
D NOMINAL
switch applications, it is necessary S 1 MAXIMUM
to review their time-current characteris- INSTANTANEOUS
.5 NOMINAL SETTING
tics and their coordination with other MINIMUM
devices in a power distribution system. INSTAN-
TANEOUS
Molded case circuit breakers are avail- SETTING
.1
able with both thermal-magnetic and
solid state trip units. Typically, smaller .05
molded case circuit breaker frame sizes
are provided with thermal-magnetic trip
units and larger frame sizes (approxi- .01
mately 400 amperes and above) are .5 1 5 10 50 100 500 1000
CURRENT IN MULTIPLES OF CIRCUIT BREAKER RATING
provided with solid state trip units.
Examining a typical circuit breaker time- Figure 1 — Typical Time-Current Curve for Adjustable Instantaneous Thermal-Magnetic
current curve, we can discuss the pro- Molded Case Circuit Breakers (NEMA AB3)
tection provided by the various portions
of the curve. Figure 1 shows a time-
10000
current curve for an adjustable instanta-
neous thermal-magnetic molded case 5000
AMPERE RATING OR
circuit breaker. The long time portion of LONG TIME PICKUP
the curve provides overload protection
for the circuit, while the instantaneous 1000 TYPICAL TIME-CURRENT CURVE
portion provides short circuit protection. ADJUSTMENTS FOR SOLID STATE TRIP
500 UNIT WITH ADJUSTABLE GROUND FAULT
The long time response is usually pro- PICKUP AND DELAY SETTINGS.
vided by a thermal element where the
delay is in seconds, with shorter time
LONG TIME DELAY
delays as the current increases. This T 100 10
8
I
“inverse-time” characteristic is typical M 50 T
6

of thermal-magnetic breakers. The E I 4 GROUND FAULT


3 PICKUP
M
instantaneous pickup is normally adjust- I E 2
able for frames rated 225 amperes and N
I2 T RAMP
10 I 1
higher. Since instantaneous elements S
.8
N .6
5
operate with no intentional time delay, E
SHORT TIME .4
GROUND FAULT
C S .3 TIME DELAY
only the magnitude of the fault current PICKUP
O E
determines which circuit protective N C .2
D O
devices in series will trip. S 1 N .1
.08
SHORT TIME D .06
.5
Figure 2 shows the time-current curve DELAY S
.04
adjustments for a solid state trip unit .03
.2 .3 .4 .6 .8 1 2 3 4 6 810
with adjustable phase current settings. GROUND FAULT PICKUP
The long time pickup and delay provide .1 CURRENT IN MULTIPLES OF
FRAME OR SENSOR RATING
overload protection. The short time .05
INSTANTANEOUS
PICKUP
pickup and delay are adjusted to coor-
dinate with other circuit breakers and
to allow acceptable overloads, such as
.01
motor or transformer inrushes, to .5 1 5 10 50 100 500 1000 5000 10000
occur without tripping the circuit CURRENT IN MULTIPLES OF RATING PLUG OR CURRENT SENSOR
breaker. The instantaneous portion
of the curve protects against high- Figure 2 — Typical Time-Current Curve for Solid State Trip Unit with Adjustable Phase
magnitude faults such as short circuits. Current Settings (NEMA AB3)

TP.15A.01.T.E
Technical Paper Automatic Cutler-Hammer
Page 4 Effective: June 2001 Transfer Switches

In many power system designs where and personnel, while minimizing the to the fault is the first to clear it. Each
devices with high withstand ratings outage of the remainder of the system. upstream circuit protective device has
are available, the instantaneous trip is the backup capability to isolate and clear
deleted in order to achieve improved During the design of the power distribu- the fault in the event of the misoperation
coordination. Instantaneous trips set tion system, the various protective or nonoperation of the downstream
below the available fault current can- devices are evaluated in a series circuit device, so that the damage to the
not be fully coordinated because the from the power source to the load. faulted circuit and the effect of the
magnitude of the fault current cannot The object is to localize the power disturbance on the rest of the power
be controlled. All breakers in series interruption so that the device closest distribution system are minimized.
with instantaneous trips respond to
the fault current and try to clear the Table 4 — Electrical Characteristics of Magnum DS Power Circuit Breakers
fault with no intentional time delay.
Magnum DS Frame Trip UL Listed Interrupting Capacity at 480 Volts
Typically, time delay is used to allow Model Size Ampere rms Symmetrical Amperes (kA)
devices to selectively coordinate. Range With Instantaneous Trip Without Instantaneous Trip
All molded case circuit breakers are (30 cycle maximum delay)
designed to NEMA standards and MDS-408 800 80 – 800 42 42
have instantaneous trips. Typically, MDS-608 800 80 – 800 65 65
the maximum setting is 10 to 13 times MDS-808 800 80 – 800 85 85
the frame rating. Special designs — MDS-C08 800 80 – 800 100 85
called insulated case circuit breakers MDS-616 1600 80 – 1600 65 65
by the industry — such as the Cutler- MDS-816 1600 80 – 1600 85 85
Hammer Type SPB Insulated Case MDS-C16 1600 80 – 1600 100 85
Breaker, may have higher than normal
MDS-620 2000 80 – 2000 65 65
instantaneous settings. These designs MDS-820 2000 80 – 2000 85 85
allow use of the short time pickup and MDS-C20 2000 80 – 2000 100 85
delay to achieve improved coordina-
tion and selectivity. MDS-632 3200 1000 – 3200 65 65
MDS-832 3200 1000 – 3200 85 85
Power circuit breakers are designed to MDS-C32 3200 1000 – 3200 100 85
ANSI standards, and their interrupting MDS-840 4000 1280 – 4000 85 85
rating equals their short time rating. MDS-C40 4000 1280 – 4000 100 100
This means that they can be applied MDS-850 5000 1280 – 5000 85 85
without instantaneous trip elements MDS-C50 5000 1280 – 5000 100 100
to achieve true coordination between
devices. A typical power circuit breaker
is the Cutler-Hammer Magnum DS. Its
interrupting and short time ratings are 1000
shown in Table 4. Power circuit break-
500 100 MVA
ers allow the engineer the most flexibil- M 1600A
B AMP SETTING 1.0
ity in designing a truly coordinated 100A TM LONG DELAY 4160V
system. Both the power circuit breaker NON- 2.0 SEC. @ 6X
ADJUSTABLE SHORT TIME P.U.
and the switchgear that incorporates it 100 3X
are designed and tested to withstand, SHORT DELAY A
0.2 SEC.
without damage, the high magnitude
T 50 139A 1000kVA
fault currents that flow through the I F 1203A 5.75% Z
equipment for up to 30 cycles. M 600A
AMP SETTING 17,800 SCA
E 1.0
Current limiting breakers as well as 10 LONG DELAY
M
switches with current limiting fuses I 2.0 SEC. @6X
SHORT TIME
can substantially reduce the available N 5 P.U. 480V
22.6kA
fault current. Fuses selectively 4X
S SHORT DELAY
coordinate when devices in series 0.1 SEC. F
E A
are selected in ratios that allow the C 200A 17.5kA
downstream fuse to clear for a given FG CURRENT
O 1 GFPU LIMITING
current before the melting level of the N 400A FUSE
upstream fuse is reached. D .5 GFTD
0.1 SEC. B
S
An overcurrent in a power system can
MG LTG.
occur as a result of normal conditions GFPU LOAD
such as motor inrush during starting or .1 800A
GFTD
transformer inrush upon energization. 0.3 SEC.
.05
It can also occur as a result of abnormal
conditions such as overloads, short MG
ZONE INTERLOCK
circuits, or ground faults. The circuit NO DELAY
protective devices in a system sense .01
abnormal conditions and protect .5 1 5 10 50 100 500 1000
against them by opening the power cir-
CURRENT IN AMPERES X 100 AT 480 VOLTS
cuit. In a properly designed system, they
will have been chosen to operate selec-
tively to protect equipment, property, Figure 3 — Typical System — Selectively Coordinated (NEMA AB3)

TP.15A.01.T.E
Cutler-Hammer Automatic Technical Paper
Transfer Switches Effective: June 2001 Page 5

The time-current coordination of a rated operating current. Overloads are transfer switch is a “circuit breaker”
power system is normally evaluated usually low level and cause thermal type or a “contactor” type, with either
on a log-log plot of time versus current. damage. Short circuits are usually high design yielding the same end result.
Manufacturers provide time-current level, with the only limiting factors
curves for their circuit breakers, and the being the source kVA and the circuit Faulted Source
engineer plots the appropriate device, impedance. The damage due to short As shown in Figure 4, with either
with the chosen adjustments and indi- circuits can be catastrophic. Ground design of transfer switch when the
cated operating limits, to reflect its oper- faults are currents that flow through an fault (F1) is on the normal source (line)
ation in the power system. Also included unintended path (ground). They require side of the switch, the upstream circuit
special consideration because they are breaker (CB1) will trip. If this occurs,
on the time-current coordination curve the most common type of fault and there is a loss of the voltage source to
are a one-line diagram showing all the may be below the operating level of the the switch and the transfer sequence is
protective devices, their interconnection, protective device ampacity or may initiated. If the alternate source is a
and the major distribution or utilization quickly increase to a higher level. All generator, the generator will be given
apparatus (motors, generators, trans- three types of faults can cause damage, a start signal. When the voltage and
formers, etc.); indication of the available but each has unique characteristics that frequency of that source are within an
fault current at important points in the must be addressed. acceptable range, the switch will trans-
power system; inrush and damage char- fer the load. In this case there is no
acteristics of motors and transformers; “Contactor” type transfer switches sub- difference in performance between the
and other appropriate information. jected to a fault are designed to remain “contactor” and “circuit breaker” type
in the position they were in prior to the transfer switches.
A typical example of time-current fault unless the fault conditions cause
coordination is shown in Figure 3. the voltage-sensing relays to operate. Overload
The 100 ampere circuit breaker B pro- “Circuit breaker” type transfer switches When the system problem is an over-
tects the load and the load conductors using high withstand molded case load, the performance of both designs of
and selectively coordinates with switches without instantaneous trip transfer switch is again identical. Neither
upstream devices for overload and elements, such as the Type SPB Insu- transfer switch design inherently has
short circuit conditions. Selective coor- lated Case Switch, perform identically overload protection, although this fea-
dination for low level ground faults on to “contactor” type transfer switches. ture can be provided as a design option
branch circuit B is not possible since They also remain in the position they in a “circuit breaker” type transfer
circuit breaker B is not provided with were in prior to a fault. An alternate switch. For an overload of the transfer
ground protection. Circuit breaker F “circuit breaker” type transfer switch switch circuit (F2), the upstream circuit
is rated 600 amperes and selectively design, using molded case switches protective device (CB1) will trip and the
coordinates with upstream and down- that contain high instantaneous trip switch will respond to the power outage
stream devices. Circuit breaker M is elements, will trip if the fault is down- by transferring to an alternate source
the 1600 ampere main breaker and stream and of sufficient magnitude. At when available. If the overload is down-
coordinates with the downstream cir- this point the transfer switch will seek stream on one of the emergency feeders
cuit breaker F as well as with the 200 the next available power source, with (F3), the corresponding feeder breaker
ampere primary fuse A for all faults the normal source being the preferred (CB2) will trip and the load will be shed.
on the load side of the circuit breaker. source. Note, however, that during Typically, no transfer of the switch
The primary fuse provides short circuit such a high-magnitude fault the occurs with either design.
protection for the transformer, while upstream protective device will also
the secondary main breaker provides trip, causing any type of transfer switch Ground Fault
the overload protection. to operate. This occurs whether the When the system problem is a ground
Part IV: Transfer Switch fault, the performance of both designs
Performance During a Fault of transfer switch is once again identi-
UTILITY GENERATOR cal. The only exception is when a high-
Proper power system design requires magnitude ground fault (F3) occurs
consideration of both normal and downstream of a “circuit breaker” type
abnormal operating conditions. transfer switch with instantaneous
Normal operating conditions require CB1
trip elements. In this case, the system
consideration of system voltage, load disturbance is similar to that of a short
flow, effects of motor starting, service F1 circuit (described below), yielding the
continuity, and reliability. Abnormal ATS same end result for either design of
conditions require consideration of switch. But, in general, ground faults
system and apparatus protection and are low-level faults because of the high
minimization of service interruption. impedance of the ground return circuit.
This is why special relaying is provided
Several types of faults are possible: to sense and protect against ground
F2
3-phase bolted faults, phase-to-phase faults. If an upstream device (CB1)
faults, double line-to-ground faults, trips due to a ground fault (F1 or F2),
single line-to-ground faults, line-to- the switch will respond to the power
neutral faults, and so on. outage by transferring to the alternate
CB2
Three types of operating conditions source when available. If the ground
are typically evaluated for purposes fault is downstream (F3) and one of
F3 the emergency feeders (CB2) trips, the
of equipment protection and system
operation: overloads, short circuits, and load will be shed. Typically, no transfer
ground faults. Both overloads and short of the switch occurs with either design.
circuits involve currents in excess of Figure 4 — ATS Response to Faults

TP.15A.01.T.E
Technical Paper Automatic Cutler-Hammer
Page 6 Effective: June 2001 Transfer Switches

Short Circuit switch senses a loss of voltage and instantaneous trip setting is much
The only system disturbance in which initiates a transfer to the alternate higher than that of the upstream
“contactor” and “circuit breaker” type source. Because the downstream breaker (CB1) protecting the transfer
transfer switches may differ in response breaker has cleared the fault, a normal switch, as seen in Figure 5. If the mag-
is a high-magnitude downstream fault transfer occurs. When the normal nitude of the downstream fault current
(short circuit) when the “circuit breaker” supply is restored, the transfer switch (F3) is above the instantaneous setting
type switch contains instantaneous trip returns to the normal supply. The key of the upstream breaker (CB1) and
elements. If the “circuit breaker” type point to note is that the transfer switch below the instantaneous setting of
transfer switch uses molded case operates only for a downstream fault the molded case switch in the transfer
switches without instantaneous trip in excess of about 10 times the switch, the “circuit breaker” type
elements (for example, the Type SPB switch rating. transfer switch will operate in the
Insulated Case Switch), there is no same manner as described above for
Let us examine a “circuit breaker” type the “contactor” type transfer switch.
difference in performance from that transfer switch under such a distur-
of a “contactor” type transfer switch. bance (high-magnitude downstream If the magnitude of the downstream
For a high-magnitude downstream fault) and follow its performance. As fault current (F3) is above the instanta-
fault, a “contactor” design transfer mentioned previously, there are two neous trip setting of both the upstream
switch does not change operating designs of “circuit breaker” type trans- breaker (CB1) and the molded case
position unless signaled by the under- fer switches. The first are devices with switch in the “circuit breaker” type
voltage relays. Upstream of the trans- no instantaneous trip elements, such transfer switch, both devices will open,
fer switch is a power circuit breaker, as the type SPB design. These are along with the downstream breaker
molded case circuit breaker (CB1), or switches with extremely high with- (CB2). The transfer switch will be in
fused switch protecting the transfer stand ratings, and they perform exactly a position with both switches open.
switch and downstream circuit. The the same as the “contactor” type There is no power source available on
upstream device has an overload trip switch for all operating conditions. the normal side, since the upstream
rating sized to protect the ampacity The second type uses circuit breakers normal source breaker (CB1) has
of the transfer switch. If the upstream classified as molded case switches. tripped. At this point both a “contac-
device opens, the transfer switch These have nonadjustable instanta- tor” type transfer switch and a “circuit
will sense a loss of voltage and neous trip elements set at 10 to 13 breaker” type transfer switch sense
initiate a transfer. times the frame rating of the device. a loss of voltage, start the generator,
To meet the UL requirements for and initiate a transfer sequence to
Short Circuit: Upstream Breaker (CB1) transfer switches, the molded case the alternate source. When a “circuit
With Instantaneous Trip Elements switches are sized approximately one breaker” type automatic transfer
Let us first consider the situation size larger than expected. For instance, switch transfers to the alternate
where the upstream power circuit an 800 ampere transfer switch uses source, it automatically resets the
breaker or molded case circuit breaker 1200 ampere molded case switches, as normal switch from the tripped-open
feeding the transfer switch has an shown in Table 2. This means that the position to the normal-open position.
instantaneous trip. In general, circuit
breaker instantaneous trip elements
that are adjustable have an adjustment 1000
range of five to 10 times the overload UTILITY GENERATOR
500
trip rating. Molded case switches 800A
with nonadjustable instantaneous CB1 800A CB1
trip elements are designed to trip at F1
approximately 10 to 13 times the frame 100 800A
200A ATS
rating. Lower-magnitude overcurrent CB2
T 50
conditions are protected by other trip I
elements (long time, short time, and M F2 480 VOLTS
ground fault) of the upstream or E
10
downstream circuit breaker after a I 200A CB2
time delay. The instantaneous trip N 5
F3
elements act with no intentional time S
delay and cause an immediate outage E
of the circuit when the device opens. C
O 1
This means that if the short circuit fault N
current magnitude is below the instan- D .5
taneous trip setting of the device (CB1) S
feeding the transfer switch, the down-
stream circuit breaker (CB2) should .1
clear the fault and no loss of power to
.05
the switch should occur. If the magni- 800A ATS
INST. TRIP
tude of the fault current is above the
instantaneous trip setting of the device
(CB1) feeding the transfer switch, .01
.5 1 5 10 50 100 500 1000
both the downstream circuit breaker
(CB2) and the upstream circuit breaker CURRENT IN AMPERES X 100 AT 480 VOLTS
(CB1) will trip. At this point the transfer
Figure 5 — System Response to Downstream Overcurrent at F3

TP.15A.01.T.E
Cutler-Hammer Automatic Technical Paper
Transfer Switches Effective: June 2001 Page 7

Since the downstream breaker has Table 5 — ATS Response to Faults


cleared the fault, a normal transfer
Location of Type of CB1 CB2 Instantaneous SPB Contactor
occurs. When the normal supply is Disturbance Disturbance Response Response Trip Molded ATS Type ATS
restored, both designs of transfer Case Switch Response Response
switch return to the normal supply. ATS Response
Note that under the above circum-
stances the same end result occurs F1 Overload Trip No Start Start Start
with a “contactor” type switch and Change Generator Generator Generator
Transfer Transfer Transfer
a “circuit breaker” type switch. The
transfer switch operated only for Short Trip No Start Start Start
a downstream fault in excess of about Circuit Change Generator Generator Generator
10 times the switch rating. Both the Transfer Transfer Transfer
upstream and downstream devices Ground Trip No Start Start Start
opened, causing the transfer switch Fault Change Generator Generator Generator
to initiate a transfer sequence. A sum- Transfer Transfer Transfer
mary of this discussion is shown in F2 Overload Trip No Start Start Start
Table 5 and Table 6. Change Generator Generator Generator
Short Circuit: Upstream Breaker (CB1) Transfer Transfer Transfer
Without Instantaneous Trip Elements Short Trip No Start Start Start
and With Short Time Delay Circuit Change Generator Generator Generator
Let us now consider the situation where Transfer Transfer Transfer
the upstream device is a power circuit Ground Trip No Start Start Start
breaker with no instantaneous trip ele- Fault Change Generator Generator Generator
ment or an insulated case circuit breaker Transfer Transfer Transfer
with a high fixed instantaneous trip set- F3 Overload No Trip No No No
ting above the available fault current. Change Transfer Transfer Transfer
These devices have exceptionally high
withstand ratings with short delay time Short Circuit No Trip No No No
capabilities of up to 30 cycles. (Low Magnitude) Change Transfer Transfer Transfer
Short Circuit Trip➀ Trip Start Start Start
Withstand ratings indicate the ability of (High Magnitude) Generator Generator Generator
a device to withstand the available fault Transfer Transfer Transfer
current without damage. They are nor-
mally expressed as a function of time, Ground Fault No Trip No No No
because the device must withstand the (Low Magnitude) Change Transfer Transfer Transfer
fault current until the fault is cleared. For Ground Fault Trip➀➁ Trip Start Start Start
a passive device, such as cable, the fault (High Magnitude) Generator Generator Generator
is cleared by an external operation. This Transfer Transfer Transfer
may be the opening of an upstream or
➀ Does not trip if it is a power circuit breaker with no instantaneous trip.
downstream circuit breaker or fuse. The ➁ Operates instantaneous pickup of molded case circuit breaker CB1.
fault may also be cleared by the failure
of the power source or by some other Table 6 — Transfer Switch Response to Downstream Overcurrent at F3 (Figure 5)
means. For an active device, such as an
instantaneous trip circuit breaker, the Current CB2 CB1 Molded Case Switch Contactor
withstand rating is the same as the inter- Amperes Response Response Type ATS Response Type ATS Response
rupting rating since the circuit breaker is 100 No Change No Change No Transfer No Transfer
intended to clear the fault with no inten-
tional delay. Some circuit breakers, such 500 Trip No Change No Transfer No Transfer
1,000
as ANSI rated power circuit breakers
2,500
and some insulated case circuit break-
5,000
ers, have extended time withstand rat-
ings. This allows them to selectively 10,000 Trip Trip Transfer Transfer
coordinate while other devices clear 15,000
the fault. Products applied in electrical
Note: CB1 — 800 ampere molded case breaker feeding the transfer switch
systems have withstand ratings associ-
CB2 — 200 ampere molded case breaker fed by the transfer switch
ated with their design or the standards ATS — 800 ampere transfer switch
applicable to the product. Withstand F3 — Fault on load side of CB2
ratings for each product are expressed
in time and current.
expected to interrupt fault current and the fault. The overload relay provides
Interrupting ratings indicate the abil- generally have low interrupting rat- overload protection by opening the
ity of a device to safely interrupt fault ings. Contactors are designed to inter- contactor. The contactor normally
current. Some devices, such as circuit rupt load current and locked rotor interrupts only motor load current.
breakers, are inherently designed to current. For example, in a combina- Its interrupting rating, based on its
interrupt current and thus have high tion motor starter, the motor circuit ability to interrupt fault current, is
interrupting ratings. Other devices, protector or fused switch provides the extremely low, typically 5000
such as contactors, are not normally short circuit protection by interrupting amperes for a smaller contactor.

TP.15A.01.T.E
Technical Paper Automatic
Page 8 Effective: June 2001 Transfer Switches
Cutler-Hammer

Automatic transfer switches have the fault current is within the published UL 1087
published withstand and interrupting rating of the transfer switch or (b) the Molded Case Switches
ratings that must be complied with short delay time of the upstream power Underwriters Laboratories, Inc.
for safe application. Their application circuit breaker can be set low enough to 333 Pfingsten Road
requires an understanding of the protect the “contactor” design transfer Northbrook, IL 60062
operation of other devices in the switch within its withstand rating.
system that can affect their ability ANSI/IEEE C37.16
to safely withstand or interrupt faults. Part V: Conclusions Low Voltage Power Circuit Breakers
For instance, if an upstream power and AC Power Circuit Protectors —
In all the scenarios described above — Preferred Ratings, Related
circuit breaker is applied with a setting overloads, ground faults, and short
utilizing the withstand capabilities of the Requirements, and Application
circuits — “circuit breaker” type trans-
device (short delay time with no instan- Recommendations
fer switches and “contactor” type
taneous trip elements), the transfer Institute of Electrical and
transfer switches perform equally.
switch must be rated for the fault current Electronics Engineers
However, the performance of “circuit
that the device will allow to flow. This 445 Hoes Lane
breaker” type transfer switches is
P.O. Box 1331

TP15A01TE
application of power circuit breakers typically superior for applications with
is common in health care facilities and Piscataway, NJ 08855-1331
upstream power circuit breakers.
data centers, where continuity of service Systems Pow-R-Breaker with
is paramount. Circuit protective devices “Circuit breaker” type transfer
Digitrip RMS Trip Unit
without instantaneous trip elements are switches can be provided with over-
current and ground fault trip elements
Cutler-Hammer Descriptive
applied to achieve coordination. The Bulletin 29-850
ANSI standards for the power circuit in a variety of configurations. They
can be service entrance labeled and Cutler-Hammer
breakers and switchgear ensure that this 1000 Cherrington Parkway
is a safe and appropriate application. are available in fixed mounted or
drawout construction. When the Moon Township, PA 15108-4312
In these cases, the withstand rating power switching devices are provided Transfer Switch Equipment
of transfer switches must be carefully with integral overcurrent protection, Cutler-Hammer Technical Data 29-925
considered. In fact, the 3-cycle minimum they can be used in the power system Cutler-Hammer
withstand required by the UL 1008 stan- for feeder protection, often eliminating 1000 Cherrington Parkway
dard may not be adequate for a given the need for upstream breakers feed- Moon Township, PA 15108-4312
application. In such cases, “circuit ing the switch. For safety purposes,
breaker” type transfer switch designs this option is provided with a lock- Zenith Bulletin O-5064-1,1993
offer some unique advantages because out function that prevents further Zenith Controls, Inc.
of their inherent interrupting capability automatic transfer operation until the 830 West 40th Street
and consequent withstand rating. appropriate source is manually reset. Chicago, IL 60609
Some circuit breaker designs, such Part VI: References Withstand and Closing Ratings for
as the Cutler-Hammer Type SPB Insu- Transfer Switch Equipment
lated Case Breaker, are available as NEMA ICS 10 ASCO Engineering Application
molded case switches without trip Industrial Control and Systems Information
units (nonautomatic switches) and have AC Transfer Switch Equipment Automatic Switch Company
extremely high withstand ratings. The National Electrical Manufacturers 50-60 Hanover Road
SPB Insulated Case Switch is available Association Florham Park, NJ 07932
with the ratings shown in Table 3 and 1300 North 17th Street, Suite 1847
Rosslyn, VA 22209 Russelectric Automatic Transfer
is applied in transfer switch designs
Switches
having those same ratings. These 60 NEMA AB3 Type RMT, 1993
cycle withstand ratings allow proper Molded Case Circuit Breakers and Russelectric Inc.
application of the transfer switch in Their Application South Shore Industrial Park
high-magnitude fault applications National Electrical Manufacturers Hingham, MA 02043
with upstream power circuit breakers. Association
1300 North 17th Street, Suite 1847 Russelectric Engineering Newsletter 478
Other “circuit breaker” type transfer
Rosslyn, VA 22209 Russelectric Inc.
switch designs have molded case
South Shore Industrial Park
switches with instantaneous trip UL 489
elements and are inherently self- Hingham, MA 02043
Molded Case Circuit Breakers and
protecting. They can also be safely Circuit Breaker Enclosures
applied in systems with upstream Underwriters Laboratories, Inc. © 2001 Eaton Corporation,
power circuit breakers that have 333 Pfingsten Road All Rights Reserved
extended short time delays. Northbrook, IL 60062
“Contactor” type transfer switch UL 1008
designs must therefore be carefully Automatic Transfer Switches
applied in systems with upstream Underwriters Laboratories, Inc.
power circuit breakers. Their use 333 Pfingsten Road
should be considered only when either Northbrook, IL 60062
(a) the upstream power circuit breaker
has instantaneous trip elements and

Cutler-Hammer
TP.15A.01.T.E
Printed in U.S.A. / Z01807

You might also like