Professional Documents
Culture Documents
Calculation:
Differential Relay setting calculations of the Power transformer based on Typical Power
Transformer data as mentioned below:
Data:
1. Transformer:20MVA
Voltage rating: 66/11 KV
Taps: +5% to -15%
Connection: Dyn11
% Impedance: 14%
2. Current Transformers:
HV side: 200/1
LV side: 1600/5
Primary: Delta connected
Secondary: Star connected
Ratio error of all CTs: +/-3%
Primary Current
HV rated current = 20 MVA (66 * 1.732)
= 175 Amp.
LV rated current = 20MVA / (11* 1.732)
= 1050 Amp
Percentage bias of the relay has to be selected such that the relay remains stable for out-
zone three phase short circuit fault on 11KV side of the transformer.
While selecting this bias setting, following points needs to be considered
1. Tap-changing operation of the transformer
2. Possible CT saturation
3. Mismatching of CT saturation characteristic
4. CT ratio error.
Assuming Transformer operation at the highest tap on HV side, the fault current on
primary and secondary side for the three phase fault in Out-zone can be calculated on the
basis of % impedance of the transformer.
Assuming % impedance of transformer=14%
Ip= 7498.275*11000/56100=1470.25A
Differential Current=Ip1-Is2=1.09A
Bias Current=(Is2+Ip1)/2=6.80A
Is1=23.43*0.97=22.72 A
Ip1=7.35*1.03=7.57A
Is2=6.26*.97=6.072 A
Ip1-Is2=1.498 A
(Is2+Ip1)/2=6.82A
% Bias= Differential Current/ Bias Current=0.22
Initially based on our operational inputs and Specifications of the transformers
and CT’s Bias settings/First Slope of Differential Characteristics was kept as 20%
Which has proven insufficient and needs correction as mentioned above.
Considering safety margin 30% setting will suffice the Purpose.
30% bias setting is already been implemented in all Honeywell stations and will
be incorporated in ABB and Alstom stations.