You are on page 1of 3

Detailed Calculations of Differential Relay for meeting Operational Requirement

and preventing Unwanted tripping on the account of Harmonics.

Subject: Investigation of recent trippings of power transformer on Harmonics in


differential relay for taking corrective action to prevent further trippings.

Calculation:

Differential Relay setting calculations of the Power transformer based on Typical Power
Transformer data as mentioned below:

Data:
1. Transformer:20MVA
Voltage rating: 66/11 KV
Taps: +5% to -15%
Connection: Dyn11
% Impedance: 14%

2. Current Transformers:
HV side: 200/1
LV side: 1600/5
Primary: Delta connected
Secondary: Star connected
Ratio error of all CTs: +/-3%

3. Relay: Biased differential relay


Rating: 1 A /5 A
Initial setting:
Bias setting:
Instantaneous High set unit:
2nd Harmonic Restraints: Operation is prevented when 2nd harmonic contents
in the differential circuits exceeds 10% ( which is a best possible setting
available in relay)
5th Harmonic Restraints: This is provided to avoid possible maloperation
under over excited condition.

Primary Current
HV rated current = 20 MVA (66 * 1.732)
= 175 Amp.
LV rated current = 20MVA / (11* 1.732)
= 1050 Amp
Percentage bias of the relay has to be selected such that the relay remains stable for out-
zone three phase short circuit fault on 11KV side of the transformer.
While selecting this bias setting, following points needs to be considered
1. Tap-changing operation of the transformer
2. Possible CT saturation
3. Mismatching of CT saturation characteristic
4. CT ratio error.

Assuming Transformer operation at the highest tap on HV side, the fault current on
primary and secondary side for the three phase fault in Out-zone can be calculated on the
basis of % impedance of the transformer.
Assuming % impedance of transformer=14%

S.C fault current on 11 KV side Is= 1050/0.14=7498.21A

S.C fault current on 66 KV side taking -15% tap into consideration


LV Voltage-11000 Volts
HV Voltage-56100 Volts

Ip= 7498.275*11000/56100=1470.25A

Secondary equivalent on 11KV side Is1= 7498.275*5/1600=23.43A

Secondary equivalent on 66 KV side Ip1= 1470.25*1/200=7.35A

After delta formation Secondary equivalent on 11KV side


Is2=23.43*1.732=40.58A

Correction factor for HV/LV CT Ratio-(1200/.578)/ (1600/5) =6.48

Corrected Is2 = 40.58/6.48=6.26 Amps.

Differential Current=Ip1-Is2=1.09A

Bias Current=(Is2+Ip1)/2=6.80A

% Bias= Differential Current/ Bias Current=0.16107

Taking 3% CT Error into consideration

Is1=23.43*0.97=22.72 A
Ip1=7.35*1.03=7.57A
Is2=6.26*.97=6.072 A
Ip1-Is2=1.498 A
(Is2+Ip1)/2=6.82A
% Bias= Differential Current/ Bias Current=0.22
Initially based on our operational inputs and Specifications of the transformers
and CT’s Bias settings/First Slope of Differential Characteristics was kept as 20%
Which has proven insufficient and needs correction as mentioned above.
Considering safety margin 30% setting will suffice the Purpose.

Conclusion: In NDPL generally power transformer are charged on full load


during supply failure from DTL.

Recently we have started operating most of the transformer in auto mode


keeping their tap changer in operation. A combined effect of higher tap position &
higher harmonics level due to Charging current of 33/11KV cables, starting
current mismatch (differential current of Tx) is reaching on higher side.( more
than 20% and causing differential tripping)

Recalculation of protection settings were done to meet our new operational


requirements and 30% bias settings will appropriately prevent harmonics
trippings.

30% bias setting is already been implemented in all Honeywell stations and will
be incorporated in ABB and Alstom stations.

You might also like