SURVEY REQUEST FORM - INDUSTRIAL / COMMERCIAL

PROPOSER

Branch / Division Business Source


Proposed date Purpose of Survey

GENERAL

The Insured * Contact Person *


Phone No. * Intermediary Name/Ph
Address *

OCCUPANCY

Occupancy DAI
FALO Coverage

SUM INSURED

- Building - Stock / Content


- Material Damage - Business Interruption
- Machinery / Equipment - Others (specify)

CLAIM EXPERIENCE
Any claim experience(s) for over the past 5 years ?

NOTES :

Proposer * Date submitted *

* Compulsory
PT ASURANSI AXA INDONESIA
 (6221) 3005 9000
 (6221) 3005 9005
 axaindo@axa-insurance.co.id
 www.axa-insurance.co.id

SURVEY CHECKLIST - INDUSTRIAL / COMMERCIAL

GENERAL INFORMATION

The Insured
Situation
Occupancy
FALO DAI
Risk Category Category IV / V Survey Type
Conferred with Mr./Mrs./Ms. Business Source
Designation Proposer
- Building / Material Damage
- Machinery / Equipment / Bus. Interruption
Sum Insured
- Stock / Content / MB / Others
Total 0.00

THE INSURED

Business started
Type of final product(s
Type of production Brand
Designed Prod. Cap Actual capacity
Market orientation Local (%) Export (%)
Operating hours Number of workers

SURROUNDING EXPOSURES

Surrounding areas Perimeter / Fence

Front Exposure Distance from Risk


Rear Exposure Distance from Risk
Left Exposure Distance from Risk
Right Exposure Distance from Risk

Are Roads provided within and around premises for free moving of local fire truck?
CONSTRUCTION

Number of building Building status


Land Area (sq m/ha) Floor Area (sq m/ha)

If multiple buildings :
(a) Any Connection (canopy, basement, piping, electrical wirings, etc) between the buildings ?
(b) If NO, is distance * between the buildings adequately provided to prevent fire spreading ?

Building occupancy
Number of storey
Floor area (m2)
Age of building More than 20 Years
Roof
Wall
Floor
Construction class Class 1B
Fire extinguisher ?
Hydrant ?
Fire detector ?
Auto sprinkler ?

(a) Does the insured Occupy the entire buildings / areas ?


(b) If NO, are the section(s) not occupied by the insured Communicating with the insured section(s) ?
(c ) Is Lightning protection avalable on site ?

Worker/Labour quarters in the premises Yes

STORAGE ARRANGEMENT
Raw & Supporting Material (s) Form Quantity Location Storage Type Storage Height

Hazardous Material (s) Location Quantity Container Storage Type Storage Height

(a) Any Special * protection (safety measure) adopted for the above hazardous materials ?
(b) Is there adequate Ventilation for storage area ?

Safe Handling of Flammable Liquids Below Average


Finished Product (s) Location Quantity Flammable Storage Type Storage Height

Standard of Housekeeping Below Average

(a) Is the provision of Access (i.e. aisle, gangway, stairway, etc) adequately provided ?
(b) Is there any obstruction observed due to Improper storage arrangement ?
(c) Floor condition ?
(d) Is there any kind of Open storage ?

Waste Form Disposal Transport

Waste Handling Wastes* are disposed from designated areas risk on WEEKLY basis

PRODUCTION PROCESS
Brief description of main occupation or manufacturing process carried out *) :

OR

* Delete if not applicable


(a) Are there any Hazardous process carried out in the risk ?
(b) Is the above processing section segregated ?
(c) Is there any bottleneck at the above process ?
(d) Are there any special process * (e.g., spray painting, plastic crushing, battery charging, hydrogenation,
etc.) other than the above which are considered hazardous being carried out in the risk ?
SPRAY PAINTING ACTIVITY If (a) is Yes, please answer (b), (c) & (d)
(a) Is there any Spray Painting activities present within the premise ?
(b) Is the Spray Painting area isolated from other process area ?
(c) Is the Spray Painting area well-ventilated ?
(d) Is there adequate signage displayed at the Spray Painting area ?

Spray Painting / Inflammable Material or Processe Spray Painting / Inflammable Material or Process area Isolated, Well Vent

MACHINERY & UTILITY

PRODUCTION MACHINERY
Main Production Machinery Designed Cap. Quantity Mfg Year Fuel Condition

(a) Number of Production Lines ?


(b) Are production machineries well separated from Combustible Goods ?

Age of Machinery More than 10 Years

UTILITY
(a) Is there a Standby Power Supply (i.e., generator) available ?
(b) Is there a Boiler available ?

MAINTENANCE
(a) Type of Maintenance ?
(b) Maintained by

Good practice of maintenance reported but NO upkeep of record


Maintenance Management
schedules

ELECTRICAL INSTALLATIONS
(a) Are cables Properly run in conduit or metal trays or securely fastened in position ?
(b) Are cables, fixtures and equipment in Good condition ?
(c) Are there any Combustible goods near the electrical installations ?

Major Re-wiring Building more than 20 Year with NO Re-Wiring

BATTERY CHARGING ACTIVITY If (a) is Yes, please answer (b), (c) & (d)
(a) Is there any Battery Charging activities present within the premise ?
(b) Is the Battery Charger isolated from other goods (i.e. combustible etc) ?
(c) Is the Battery Charging area well-ventilated ?
(d) Is there adequate signage displayed at the Battery Charging area ?

Battery Charging (Heavy Electricity Usage) Charging area Not Isolated but Well Ventilated with Proper Signage

SMOKING CONTROL If (a) is Yes, please answer (b), (c) & (d)
(a) Is Smoking strictly-prohibited within the premise ?
(b) Is there any area designated for smoking within the non-smoking areas ?
(c) Is there any evidence of smoking within the non-smoking areas ?
(d) Is there adequate ‘No-Smoking’ signage display at non-smoking areas ?

Smoking Control Adequate signage with NO smoking evidence observed

HOT WORKS CONTROL (i.e. welding, cutting etc) If (a) is Yes, please answer (c) & (d)
(a) Is there any Hot Works implemented within the premise ?
(b) Is there any Engineering Workshop available within the premise ?
(c) Is Hot Work Permit Scheme established within the premise ?
(d) Is Hot Work Control practiced by the management satisfactory ?

Hotwork Control Hot Work without Hot Work Permit Scheme in place

SECURITY & SAFETY TEAM

SECURITY FEATURE

Sec Arrangement No of Guard Shifts Mean of Communication Armed ? Patrolling ? Any ALARM ?

Security Team Contracted Security Forces with more than 2 guards with patrolling

SAFETY COMMITTEE

Any Safety Committee ? Any Safety Officer ? Safety Meeting Frequency Type of Plans / Procedures Available

PRIVATE FIRE TEAM

Any Private Fire Team ? Nos of Member Fire Drill Conducted Fire Training Conducted Trained By :

Private Fire Team Fire Fighting Team with more than 6 members

PUBLIC FIRE BRIGADE

Location of Fire Brigade Distance from Risk Estimated Turn-Out Time

Public Fire Brigade Located between 5km to 10km from risk premises
FIRE PROTECTION SYSTEM

PORTABLE FIRE EXTINGUISHER

Portable Fire Extinguisher Nos of Unit Inspected ? Service ? Accessible ? Well-Displayed ?

Portable Fire Extinguisher Available and meet RFT requirements

HOSE REEL SYSTEM

Hose Reel Water Tank Pump Set Maintenance Maintained by

Hose Reel NOT AVAILABLE

FIRE HYDRANT (EXTERNAL)

Fire Hydrant Water Tank Pump Set Maintenance Maintained by

Fire Hydrant NOT AVAILABLE

RISER SYSTEM (WET/DRY) / INTERNAL HYDRANT

Riser System Water Tank Pump Set Maintenance Maintained by

Riser System NOT AVAILABLE

FIRE ALARM / FIRE DETECTION SYSTEM

Fire Alarm / Auto Fire Detector Installation Manning of Fire Alarm Panel Linked to Public Fire Brigade
Type of Detectors Available

Fire Alarm / Auto Fire Detection System NOT AVAILABLE

AUTOMATIC SPRINKLER SYSTEM

Sprinkler System Water Tank Pump Set Maintenance Maintained by

Fire Sprinkler NOT AVAILABLE

PERILS

FLOODING

Exposure No incident of flood at locality for the past 10 years


IMPACT DAMAGE

Exposure No reported loss due to impact damage for the past 5 years

STORM & TEMPEST

Exposure No reported loss due to storm & tempest for the past 5 years

FIRE, EXPLOSION & SELF COMBUSTION

Exposure No reported loss due to explosion & SC for the past 5 years

RSMD

Exposure No reported loss due to RSMD for the past 5 years

SUBSIDENCE / LANDSLIP

Exposure No incident of subsidence/landslip at locality for the past 10 years

AIRCRAFT DAMAGE

FALLING TREES

EARTHQUAKE

BURGLARY/THEFT

CLAIM EXPERIENCE

Any claim experience(s) for the last 5 years? No

Amount
Desciption of Loss Date Remedial Action Taken after Loss
USD IDR

0.00 $ -

Management interest in loss control Yes

Any major issue to block acceptance of this risk ? No

Major Issues BLOCKING the Risk Acceptance


1 Extreme Exposure to Perils (i.e. landslide zone, flood prone area, lightning etc)
Comment:

2 Extremely Poor Standard of Housekeeping / Maintenance


Comment:

3 OTHERS
Comment:

REMARKS / SURVEYOR COMMENTS

Management
- Company history, nature of business/trade, ownership, year of establishment, expansion plans for the future, state of business

Construction
- Comment on compartmentation and segregation of utility buildings
- Condition of the buildings

Occupancy
- Name the main production machinery and building facilities in the risk
- Condition of the above machinery
- Comment on cleaning, servicing, maintenance, overhaul and statutory inspection

Protection
- Comment on the physical and working condition of fire protection equipment
- Any deficiency/defect in the system
- Described any other firefighting facilities provided (e.g. private fire truck, portable pumps, alternate water source, etc.)

Exposures
- External (surrounding buildings and natural perils)
- Internal (Inflammability process/activity or materials)

Findings /Abnormal conditions


- Evidence of smoking
- Poor housekeeping
- Poor handling of flammable materials
- Poor fire protection system
Findings /Abnormal conditions
- Evidence of smoking
- Poor housekeeping
- Poor handling of flammable materials
- Poor fire protection system

Any recommendations ?

Next survey 1 - 2 Years

Surveyed by: Date

PT ASURANSI AXA INDONESIA


 (6221) 3005 9000
 (6221) 3005 9005
 axaindo@axa-insurance.co.id
 www.axa-insurance.co.id

SUMMARY - INDUSTRIAL / COMMERCIAL

The Insured 0 FALO


Situation 0 0
Occupancy 0 DAI
Date of Visit 30-Dec-99 Survey Type Surveyed by 0 0
Bus. Source 0 0 Proposer 0

- Building / Material Damage 0 0.00


- Machinery / Equipment / Bus. Interruption 0 0.00
Sum Insured (IDR/USD)
- Stock / Content / MB / Others 0 0.00
Total 0 0.00

General Technical Risk Appraisal


Age of Building More than 20 Years Occupancy / Process Hazard 44%

Construction Class Class 1B Physical Building Condition 59%

Handling of flammable Below Average Goods & Storage Arrangement 34%

Standard of housekeeping Below Average Control of Human Elements 47%


Fire Protection Fire & Safety Organization 84%

Fire extinguisher Available and meet RFT Fire Protection System 17%

Hydrant system NOT AVAILABLE Perils 100%

Fire alarm / detector NOT AVAILABLE

Private fire team Fire Fighting Team with Previous Losses No

Loss Experience No Overall Rating


IDR 0.00
Loss Amount 48% BELOW AVERAGE
Loss Amount
USD 0.00
48% BELOW AVERAGE

Recommendation 0 Next Survey 1 - 2 Years

Perils *
Flooding 0 Landslide / Landslip 0
Impact Damage 0 Aircraft Damage 0
Storm & Tempest 0 Falling Trees 0
Fire, Explosion & Self Combustion 0 Earthquake 0
RSMD 0 Burglary / Theft 0
* (High - Moderate - Minimal - Negligence)
/ RISK APPRAISAL GUIDE
Last Revised : 15 Dec 09

Risk Elements Risk Scoring

1.0 OCCUPANCY / PROCESS HAZARD


1.1 Category I 5
Category II 4
Category III 3
Category IV / V 2
Category VI / Referred / Declined 1
1.2 SPRAY PAINTING / INFLAMMABLE MATERIAL OR PROCESS
NO Spray Painting / Inflammable Material or Process Activities 5
Spray Painting / Inflammable Material or Process area Isolated, Well Ventilated with Proper
4
Signage
Spray Painting / Inflammable Material or Process area Not Isolated but Well Ventilated with
2
Proper Signage
Spray Painting / Inflammable Material or Process area Not Isolated, Poorly Ventilated with
1
Proper Signage
Spray Painting / Inflammable Material or Process area Not Isolated, Poorly Ventilated with No
0
Signage
1.3 BATTERY CHARGING (Heavy Electricity Usage)
NO Battery Charging Activities 5
Charging area Isolated, Well Ventilated with Proper Signage 4
Charging area Not Isolated but Well Ventilated with Proper Signage 2
Charging area Not Isolated, Poorly Ventilated with Proper Signage 1
Charging area Not Isolated, Poorly Ventilated with No Signage 0

2.0 PHYSICAL BUILDING CONDITION


2.1 CLASS OF CONSTRUCTION
CLASS 1A 5
CLASS 1B 4
CLASS 2 3
CLASS 3 / Unknown 1

2.2 AGE OF BUILDING


Less than 1 Year 5
1 - 6 Years 4
7 - 15 Years 3
16 - 20 Years 2
More than 20 Years 1

3.0 GOODS & STORAGE ARRANGEMENT


3.1 STANDARDS OF HOUSEKEEPING *
GOOD 5
ABOVE AVERAGE 4
AVERAGE 3
BELOW AVERAGE 2
POOR 1
VERY POOR 0

GOOD housekeeping where :


- provision of access (i.e. aisle, gangway etc) is adequately provided
- NO goods obstruction to fire fighting appliances are observed
- Goods congestion are NOT sighted at ALL areas
ABOVE AVERAGE housekeeping where :-
- provision of access (i.e. aisle, gangway etc) is adequately provided
- NO goods obstruction to fire fighting appliances are observed
- Congestion of goods are sighted at <50% of the whole area
AVERAGE housekeeping where :-
- provision of access (i.e. aisle, gangway etc) is adequately provided
- FEW goods obstruction to fire fighting appliances are observed Back
- Congestion of goods are sighted at <50 of the whole areas
BELOW AVERAGE housekeeping where :-
- provision of access (i.e. aisle, gangway etc) is adequately provided
- FEW goods obstruction to fire fighting appliances are observed
- Congestion of goods are sighted at >50% of the whole areas
POOR housekeeping where :-
- provision of access (i.e. aisle, gangway etc) is NOT adequately provided
- FEW goods obstruction to fire fighting appliances are observed
- Congestion of goods are sighted at ALL areas
VERY POOR housekeeping where :-
- provision of access (i.e. aisle, gangway etc) is NOT adequately provided
- Goods obstruction to fire fighting appliances are observed at MOST areas
- Congestion of goods are sighted at ALL areas

3.2 WASTE HANDLING


Wastes** are disposed from designated areas on DAILY basis 5
Wastes** are disposed from designated areas risk every three (3) days 3
Wastes** are disposed from designated areas risk on WEEKLY basis 1
Waste designated area cannot be established at the risk 0
Collection of wastes observed outside their waste designated areas 0
** Wastes are located at designated areas which are well isolated and/or segregated from the production areas and other
key facility buildings

3.3 SAFE HANDLING OF FLAMMABLE LIQUIDS


NO Presence of Flammable Liquids 5
GOOD 4
AVERAGE 3
BELOW AVERAGE 2
POOR 1
Presence of Flammable Liquids with Unknown Handling Practise 0

GOOD Handling of Flammable Liquids where :


- storage of flammable liquids are isolated or separated from main plant
- erection of containment bunds at ALL flammable liquids storage area
- storage of flammable liquids at main plant for Day Use quantities only
- flammable liquids storage area are well ventilated* with good signages
AVERAGE Handling of Flammable Liquids where :
- storage of flammable liquids are isolated or separated from main plant
- erection of containment bunds at ALL flammable liquids storage area Back
- storage of flammable liquids at main plant for more than Day Use quantities
- flammable liquids storage area are well ventilated* with proper signages
BELOW AVERAGE Handling of Flammable Liquids where :
- storage of flammable liquids are isolated or separated from main plant
- containment bunds are NOT erected at flammable liquids storage area
- storage of flammable liquids at main plant for more than Day Use quantities
- flammable liquids storage area are poorly ventilated with NO signages
POOR Handling of Flammable Liquids where :
- storage of flammable liquids are NOT isolated or separated from main plant
- containment bunds are NOT erected at flammable liquids storage area
- storage of flammable liquids at main plant for more than Day Use quantities
- flammable liquids storage area are poorly ventilated with NO signages

A well ventilated area has natural ventilation (i.e. open sided wall, or with window opening etc) or mechanical/forced
ventilation (i.e. installation of ventilation fan) to ensure good air movement/circulation.

Poor standard of housekeeping attributed by badly congestion of goods obstructing fire protection & electrical appliances, high
accumulation of dusts, poor handling practise of flammable / hazardous materials & poor management of waste disposal leading to an
increased in the overall risk exposure. Recommendation to decline risk acceptance can be exercised at discretion of the risk engineer upon
consultation with the underwriters.

4.0 CONTROL OF HUMAN ELEMENTS


4.1 SMOKING CONTROL
Adequate signage with NO smoking evidence observed 5
Adequate signage with smoking evidence observed - Non CRITICAL Ind 3
Adequate signage with smoking evidence observed - CRITICAL Ind 0
Smoking is NOT RESTRICTED in the premises 0
4.2 HOT WORK CONTROL
NO Hot Work Activities or restricted to Engineering Workshop*** 5
Hot Work with Hot Work Permit Scheme in place 3
Hot Work without Hot Work Permit Scheme in place 1
*** Designated area for engineering workshop must be isolated and/or segregated from the main production area

4.3 MAINTENANCE STANDARD


4.3.1 Age of Machineries
Less than 1 Year 5
1 Year to 5 Years 4
5 Years to 10 Years 2
More than 10 Years 1
4.3.2 Maintenance Management
Good practice of maintenance with proper upkeep of record schedules 5
Good practice of maintenance reported but NO upkeep of record schedules 3
Maintenance on breakdown basis only 1
NONE or No Information 0
4.3.3 Major Re-Wiring
Building less than 6 Year with NO Re-Wiring 5
Building between 6 to 10 Year with NO Re-Wiring 4
Building more than 10 Year with NO Re-Wiring 3
Building more than 15 Year with NO Re-Wiring 1
Building more than 20 Year with NO Re-Wiring 0
No Information 0

Poor maintenance standard of electrical appliances / wirings attributed by extremely old wiring system (i.e. >25 years) with no regular
maintenance, upkeep & inspection by qualified electrician leading to an increased in the overall fire exposure. Recommendation to decline
risk acceptance can be exercised at discretion of the risk engineer upon consultation with the underwriters.

5.0 FIRE & SECURITY ORGANISATION


5.1 PRIVATE FIRE FIGHTING TEAM
Fire Fighting Team with more than 6 members 5
Fire Fighting Team with less than 6 members (or unknown nos of member) 3
NO Fire Fighting Team 0
5.2 SECURITY TEAM
In House Security Forces with more than 2 guards with patrolling 5
In House Security Forces with more than 2 guards with no patrolling 4
In House Security Forces with less than 2 guards with patrolling 3
In House Security Forces with less than 2 guards with no patrolling 2
Contracted Security Forces with more than 2 guards with patrolling 4
Contracted Security Forces with more than 2 guards with no patrolling 3
Contracted Security Forces with less than 2 guards with patrolling 2
Contracted Security Forces with less than 2 guards with no patrolling 1
No Security Team 0

5.3 PUBLIC FIRE FIGHTING TEAM


Located less than 5km from risk premises 5
Located between 5km to 10km from risk premises 3
Located between 10km to 20km from risk premises 1
Location of nearest Public Fire Brigade Not Known 0

6.0 FIRE PROTECTION SYSTEM


6.1 PORTABLE FIRE EXTINGUISHERS
Available and meet RFT requirements 5
Available but did not meet RFT requirements 3
NOT AVAILABLE 0
6.2 HOSE REEL SYSTEM
Available and meet RFT requirements 5
Available but did not meet RFT requirements 3
NOT AVAILABLE 0
6.3 FIRE HYDRANT
Available and meet RFT requirements 5
Available but did not meet RFT requirements 3
NOT AVAILABLE 0
6.4 RISER SYSTEM (WET/DRY)
Available and meet RFT requirements 5
Available but did not meet RFT requirements 3
NOT AVAILABLE 0
6.5 FIRE ALARMS & AUTO FIRE DETECTOR (i.e. Heat & Smoke detector)
Available and meet RFT requirements 5
Available but did not meet RFT requirements 3
NOT AVAILABLE 0
6.6 AUTOMATIC FIRE SPRINKLER SYSTEM
Available and meet RFT requirements 5
Available but did not meet RFT requirements 3
NOT AVAILABLE 0

7.0 PERILS
7.1 FLOOD EXPOSURE
No incident of flood at locality for the past 10 years 5
No incident of flood at locality for the past 5 years 3
One (1) incident of flood at locality for the past 5 years 1

Flood loss in excess of RM1mil or 50% of the Sum Insured within the past 5 years, can be regarded as high exposure. Recommendation to
decline risk acceptance can be exercised at discretion of the risk engineer upon consultation with the underwriters.

7.2 STORM AND TEMPEST


No reported loss due to storm & tempest for the past 5 years 5
One (1) reported loss due to storm & tempest for the past 5 years 3
More than one reported loss due to storm & tempest for the past 5 years 1
7.3 IMPACT DAMAGE
No reported loss due to impact damage for the past 5 years 5
One (1) reported loss due to impact damage for the past 5 years 3
More than one reported loss due to impact damage for the past 5 years 1
7.4 EXPLOSION & SPONTENOUS COMBUSTION (SC)
No reported loss due to explosion & SC for the past 5 years 5
One (1) reported loss due to explosion & SC for the past 5 years 3
More than one reported loss due to explosion & SC for the past 5 years 1
7.5 RIOT, STRIKE AND MALICIOUS DAMAGE (RSMD)
No reported loss due to RSMD for the past 5 years 5
One (1) reported loss due to RSMD for the past 5 years 3
More than one reported loss due to RSMD for the past 5 years 1
7.6 SUBSIDENCE AND LANDSLIP
No incident of subsidence/landslip at locality for the past 10 years 5
No incident of subsidence/landslip at locality for the past 5 years 3
One (1) incident of subsidence/landslip at locality for the past 5 years 1
Recommendation to decline risk acceptance due to high exposure from subsidence & landslip can be exercised at discretion of the risk
engineer upon consultation with the underwriters.

FIRE EXTINGUISHING APPLIANCES

General requirements I - Portable Extinguishers


Back
(1)   Portable fire extinguishers to be installed complying with UBBL, MS1539 or any other equivalent Sta
(2)   The combined A rating of all portable fire extinguishers on each storey/floor must not be less than 0
(3)   This minimum may be reduced to 13A from one portable fire extinguisher for upper floors with area
(4)   For area where Carbon Dioxide extinguishers are more suitable, such as in electrical rooms, the equ
(5)   Portable fire extinguishers must be maintained in a fully charged and operating condition, and kept
(6)   Portable fire extinguishers must be located in such a way that they are readily accessible in the eve
(7)   Portable fire extinguishers must not be obstructed or obscured from view. Where visual obstruction
(8)   Portable fire extinguishers may be installed on hangers/brackets, mounted in cabinets, or set on she
(9)   Each portable fire extinguisher must be securely attached with a valid certificate from the fire autho

General requirements II - Hydraulic Hose Reels and Internal Hydrants with small bore hose atta
Back
(1)   The hydraulic hose reels and/or internal hydrants must be sited in prominent and easily accessible p
(2)   The flow rate at the most hydraulically remote hose reel or internal hydrant must not be less than 2
(3)   The hoses for hydraulic hose reels must be of reinforced rubber and that for internal hydrants must
(4)   The hoses must not exceed 45 metres (148 feet) in length.
(5)   The hydraulic hose reels and/or internal hydrants must be permanently connected to a constant wat
(6)   Where the hydraulic hose reel and/or internal hydrant system is connected to a suction tank, the tan
(7)   Where stationary pumps are provided the pumps must be capable of discharging at a rate of not les
(8)   Each pump must be housed in an easily accessible position where it will not be liable to be damaged
(9)   Each pump must be so arranged that it will start automatically in the case of automatic pumps; or c
(10) There must be kept on hand at all times sufficient fuel to run the pumps at full load for not less than

General requirements III - Internal Hydrants.


Back
Internal hydrants as in item 1C constitute hydrants installed inside buildings of not more than 30.5 metres (100 feet) a

(1)   The internal hydrants must be positioned in such a way that no portion of the building floor is more
(2)   The internal hydrant system can be fed from an independent water supply having a minimum capac
(3)   The internal hydrant mains and hose for use in connection therewith must have a clear waterway of
(4)   Every internal hydrant must be provided with a canvas / rubberised hose of at least 30 metres (100
(5)   The internal hydrants must be protected against mechanical impact damage.
(6)   A trained private fire brigade complying with General requirements IX must be available at all times

General requirements IV - Wet Riser.


Back
(1)   The wet riser landing valves must be provided inside the building at each level above the groun
(2)   The number and disposition of the wet riser landing valves must be such that one is provided f
(3)   Wet risers must have a clear waterway of at least 150 mm (6 inch) diameter and the outlet mu
(4)   Each wet riser landing valve shall comprise at least 30 metres (100 feet) of canvas hose, 1 noz
(5)   The wet riser system must be provided with supply of water from tank having a minimum capa
(6)   A trained private fire brigade complying with General requirements IX must be available at all t
(7)   Each pump connected to the wet riser system must be capable of discharging at a rate of not l
(8)   Each pump must be housed in an easily accessible position where it will not be liable to be dam
(9)   Each pump must be so arranged that it will start automatically in the case of automatic pumps
(10) There must be kept on hand at all times sufficient fuel to run all the pumps at full load for not l

General requirements V - Automatic Fire Alarm and Detection Systems.


Back
(1)   The spacing of the detectors shall be as follows:
                         i.      For open areas, the horizontal distance from any point in the area to the det
                        ii.      In corridors less than 5 metres (16 feet) wide, the horizontal distance given
(2)   The detectors must be connected to a central fire control panel which in turn, must be linked directl
(3)   The central fire control panel must be manned 24 hours a day. If the central fire control panel is con
(4)   The detectors and central fire control panel must be maintained in proper working order.
(5)   The detector head must be of the types approved by the Standard & Industrial Research Institute of
General requirements VI - External Hydrants.
Back
(1)   External hydrants must be positioned not more than 23 metres (75 feet) away from the extern
(2)   There must be at least one hydrant for every 76 metres (250 feet) of external wall measureme
(3)   There must be at least one opening for every 76 metres (250 feet) of external wall measureme
(4)   The external hydrant system can be fed from an independent water supply having a minimum
(5)   The hydrant mains and hose for use in connection therewith must have a clear waterway of at
(6)   Every hydrant must be provided with at least 1 canvas/rubberized hose of at least 30 metres (1
(7)   The hydrants must be protected against mechanical impact damage.
(8)   A trained private fire brigade complying with General requirements IX must be available at all t
(9)   Requirements for hydrant pumps
a.    Each pump connected to the hydrant system must be capable of discharging at a
b.    Each pump must be housed in an easily accessible position where it will not be lia
c.    Each pump must be so arranged that it will start automatically in the case of auto
d.    There must be kept on hand at all times sufficient fuel to run all the pumps at full
9 or any other equivalent Standards/Rules approved by the fire authority.
floor must not be less than 0.065 x area of floor (square metre) of the storey/floor with an absolute minimum of 26A supplied by 2 porta
her for upper floors with areas less than or equal to 100 square metres in single-occupancy buildings.
s in electrical rooms, the equivalent A rating required for the room, should be calculated based on (2). As a guide, 2kg of Carbon Dioxide
perating condition, and kept at their designated locations at all times when they are not being used.
readily accessible in the event of a fire. They should preferably be located along normal paths of travel including exits from an area.
ew. Where visual obstruction cannot be completely avoided, means must be provided to indicate the location of the extinguishers.
ted in cabinets, or set on shelves unless the extinguishers are of the wheeled type. Cabinets housing extinguishers must not be locked.
certificate from the fire authority.

ith small bore hose attached.

minent and easily accessible positions at each floor level in such a way that no part of the floor is more than 6 metres (20 feet) from a ho
drant must not be less than 24 litres (5 gallons) of water per minute through a nozzle and capable of achieving a water throw of not less
at for internal hydrants must be rubber lined. The hoses must not be less than 19.05 mm (0.75 inch) nor more than 31.75 mm (1.25 inch

connected to a constant water supply.


cted to a suction tank, the tank must be constantly filled with water. The minimum capacity of the tank must be 3,600 litres (800 gallons
ischarging at a rate of not less than 90.92 litres per minute (20 gallons per minute).
ll not be liable to be damaged by fire or otherwise.
ase of automatic pumps; or can be readily started by one person.
ps at full load for not less than four (4) hours and power must always be available for each stationary pump.

han 30.5 metres (100 feet) above fire appliance access level (usually ground level).

of the building floor is more than 15 metres (50 feet) from a hose nozzle when the hose is fully extended.
pply having a minimum capacity of 54,552 litres (12,000 gallons) of water with manual or automatic pumps complying with General requ
ust have a clear waterway of at least 63.5 mm (2½ inch) diameter.
se of at least 30 metres (100 feet) length and a nozzle permanently connected to the internal hydrant or kept under cover in a convenien

must be available at all times in the premises to operate the system.

t each level above the ground level.


such that one is provided for every 900 square metre (9,700 square feet), or any part thereof, of the floor area at each level othe
diameter and the outlet must be at least 63.5 mm (2½ inch) in diameter.
feet) of canvas hose, 1 nozzle and 1 coupling kept under cover in a convenient place.
ank having a minimum capacity of 54,552 litres (12,000 gallons).
IX must be available at all times in the premises to operate the system.
discharging at a rate of not less than 1,500 litres per minute (330 gallons per minute) of water.
t will not be liable to be damaged by fire or otherwise.
he case of automatic pumps; or can be readily started by one person.
e pumps at full load for not less than 4 hours and power must always be available for each pump.

y point in the area to the detector nearest to that point should not exceed 5.3 metres (17 feet) for heat detectors or 7.5 metres (25 feet)
he horizontal distance given in (1)a above may be increased by half the difference between 5 metres (16 feet) and the width of the corri
n turn, must be linked directly to a Fire Services Department (BOMBA) station or alternatively the central fire control panel may be conne
ntral fire control panel is connected to the BOMBA station via a remote central monitoring station, the remote central monitoring station
per working order.
dustrial Research Institute of Malaysia (SIRIM).
feet) away from the external wall of the building.
of external wall measurement of the building.
of external wall measurement of the building for purpose of fire fighting.
r supply having a minimum capacity of 54,552 litres (12,000 gallons) of water with manual or automatic pumps complying with G
have a clear waterway of at least 63.5 mm (2½ inch) diameter.
hose of at least 30 metres (100 feet) length, 1 nozzle and 1 coupling kept under cover in a convenient place. However, there must

IX must be available at all times in the premises to operate the system.

capable of discharging at a rate of not less than 900 litres per minute (200 gallons per minute) of water.
sition where it will not be liable to be damaged by fire or otherwise.
matically in the case of automatic pumps; or can be readily started by one person.
to run all the pumps at full load for not less than 4 hours and power must always be available for each pump.
f 26A supplied by 2 portable fire extinguishers.

de, 2kg of Carbon Dioxide is equivalent to 1kg of dry powder.

ng exits from an area.


the extinguishers.
hers must not be locked. Where extinguishers are subjected to malicious use, locked cabinets with emergency access may be used.

metres (20 feet) from a hose nozzle when the hose is fully extended.
a water throw of not less than 6 metres (20 feet).
han 31.75 mm (1.25 inch) internal diameter.

3,600 litres (800 gallons).


mplying with General requirements VIII(9) or permanently connected to an adequate constant supply of water from the public mains.

nder cover in a convenient place nearby the internal hydrant.

r area at each level other than the ground floor.

rs or 7.5 metres (25 feet) for smoke detectors. For line or beam detectors, the distance should be taken as the distance to the nearest p
and the width of the corridor, e.g. in a corridor of 3 metres (10 feet) wide the distance may be increased by 1 metre (3 feet). A corridor w
ntrol panel may be connected to a remote central monitoring station which must be directly linked to a BOMBA station. Under both circu
entral monitoring station must also be manned 24 hours a day and the Insured must obtain a certification to this effect.
umps complying with General requirements VIII(9) or permanently connected to an adequate constant supply of water from the p

ce. However, there must be a minimum of 4 hoses of 30 metres (100 feet) length each, 2 nozzles and 2 couplings for each protect
access may be used.
om the public mains.

distance to the nearest point on the line or beam.


metre (3 feet). A corridor wider than 5 metres (16 feet) should be treated as an open area as in (1)a above.
station. Under both circumstances the Insured must obtain a certification from the BOMBA or the remote central monitoring station cert
pply of water from the public mains.

ouplings for each protected premises.


al monitoring station certifying that their automatic fire alarm system is so connected.