Design Basis Report for fire alarm Adani Mormugao Port terminal
system (P) Ltd., At Mormugao ,Goa
CONTENTS
R E V - 01 S h e e t 2 of 5
Design Basis Report for fire alarm Adani Mormugao Port terminal
system (P) Ltd., At Mormugao ,Goa
1.0 Introduction
The intent of this document is to give a detailed description about fire alarm system
envisaged for the Proposed Adani Mormugao Port terminal (P) Ltd., at Mormugao Port,
Goa. The fire safety design objective for the facility is to provide a level of fire and safety
consistent with recognized fire safety standards.
The following areas will be covered by Analogue addressable fire detection and alarm
system:
Control Room
Server Room
Office area
UPS Room
PLC Panel Room
Battery Room
Canteen
Wagon loading Control room
Truck loading Control room
Master control Area
MCC room
Electrical substation
Transfer towers and drive houses are covered with surveillance cameras whose
signals / imagery is connected to control room.
Linear Heat Sensing Cables will be laid for complete length of tunnel, end to end,
with a small overlap at both ends of tunnel.
Machines will be manned round the clock and as such fire hazard can be detected by
operators.
System Description:
Fire alarm control panel loop configuration is sized, based on the requirement of detectors
and devices in the building. Mater & salve panel shall be proved as per requirement in
camps. Master & salve panel shall be connected in loop. Master & salve panel are give alarm
of entire system.
Fire Detection & Alarm System is a key element of the fire protection system. It is designed
to detect the presence of fire to initiate action. The type of fire alarm system considered is
Analogue Addressable Fire Detection & Alarm System.
R E V - 01 S h e e t 3 of 5
Design Basis Report for fire alarm Adani Mormugao Port terminal
system (P) Ltd., At Mormugao ,Goa
The fire alarm system will monitor and display the activation of each device in the system,
including any heat detector, smoke detector, manual call point and all other input device.
Fire Alarm Control Panel (FACP) shall have its own microprocessor, software and memory.
Detectors:
Under fire condition, presence of smoke will trigger the circuit of the detector and will send
a signal to the control panel.
The detector will be vibration and shock proof. When disassembling for cleaning purposes,
its components must not be damaged by static over voltage.
An alarm release will not affect a detector’s good functioning. After resetting the alarm,
the detector will resume operations without readjustments of any kind.
Devices, which take their address from their position of the circuit, are unacceptable
because if devices are later added, existing address descriptors and commands must be
reprogrammed.
Each sensor will be capable of being tested for alarm via command from the Fire Alarm
Control panel (FACP). Each sensor will respond to FACP scan for information for its type
identification.
A Heat Detector is a device that detects heat and can be either electrical or mechanical in
operation. The most common types are the thermocouple and the electro-pneumatic, both
respond to changes in ambient temperature. Typically, if the ambient temperature rises
above a predetermined threshold, then an alarm signal is triggered.
R E V - 01 S h e e t 4 of 5
Design Basis Report for fire alarm Adani Mormugao Port terminal
system (P) Ltd., At Mormugao ,Goa
Manual Call Point shall be Pull Station Type. The Manual Pull station is operated by
pushing in the top bar and pulling the handle on the front of the station as far down as it will
go. At this point, the handle locks into place and is easily visible from 15m. Opening the
station with key, placing the handle in the normal upright position and relocking the
station, resets the pull station.
Heat Detectors are considered in Pantry, UPS Room, Battery room and Kitchen areas.
Manual call points & Hooter shall be located near the stairways, lobbies and exit.
The fire alarm panel one loop shall accommodate Maximum of 125 detectors and 125
devices.
The number of loop for respective fire alarm panels shall be decided as per the number of
floors and number of detector / devices.
*******
R E V - 01 S h e e t 5 of 5