1 Electrical datasheets
20.2 Generator
SL. NO. ITEM UNIT TECHNICAL PARTICULARS
1.0 Prime Mover for Generator - Governor
2.0 Location - STG building
3.0 Indoor or Outdoor - Indoor
4.0 Quantity Nos. 1
5.0 Rated MVA (MVA) 8.375
6.0 Rated MW (MW) 6.7
7.0 Rated Lagging Power Factor - 0.8
8.0 Rated Frequency (Hz) 50
9.0 Rated Speed (RPM) 1500
10.0 Rated Voltage (kV) 11
11.0 Number of Phases 3
12.0 Stator Winding Connection - Star
13.0 Type of cooling
` a) Stator Winding CACW
b) If water cooled No of DDE
exchanges
c) Rotor Winding and Stator DDE
Core
14.0 Class of Insulation
a) Stator Winding Class F
b) Rotor Winding Class F
15.0 Power Frequency withstand (kV) 28
voltage
16.0 Basic Impulse Level of Stator (kVp) 75
Winding
17.0 Short Circuit Ratio (Pu) 0.5
18.0 Minimum Direct Axis Saturated (Pu) DDE
Sub-transient Reactance
19.0 Maximum Direct Axis Unsaturated (Pu) DDE
Transient Reactance
20.0 Nominal response of Excitation DDE
system
21.0 Frequency Variation Expected in % DDE
Operation as percentage of rated
frequency
22.0 Voltage Variation Expected in % DDE
Operation as percentage of rated
voltage
23.0 Generator unbalance operating
condition
a) Continuous negative DDE
sequence current withstand
capability I2/In
b) Maximum Negative (Sec) DDE
sequence withstand current

Waste to Energy Project at Deonar Volume 2C General Electrical Specification


under fault condition (
I2/In)^2 x t
24.0 Degree of Protection for the
enclosure of :
a) Turbo-Generator IP54
b) Main Exciter (if provided) IP54
c) Permanent Magnet DDE
Generator (if provided)
25.0 Parallel Operation of Generator YES
Envisaged
26.0 Line Terminals :
a) Number of Line Terminals to 3
be brought out
b) Where to be brought out Side
(Top / Bottom / Side)
27.0 Neutral Terminals
Number of Neutral Terminals to 3
be brought out
Where to be brought out (Top / Side
Bottom / Side)
28.0 Minimum Ambient Air 0C DDE
Temperature
29.0 Maximum Ambient Air Temperature 0C DDE
30.0 Maximum Inlet Temperature of 0C DDE
Cooling Water available for
Hydrogen / Air coolers
31.0 Type of cooling water available for Water cooler
Hydrogen coolers / Air coolers /
water coolers (ordinary water /
sea water)
32.0 Maximum continuous output of DDE
Generator with one cooler out of
service
33.0 Whether Following Features /
Equipment required
a) Field Earth Fault Monitor and DDE
its type
b) Diode Fuse Failure Monitor DDE
c) End winding vibration DDE
monitoring system
d) On line partial discharge DDE
monitoring system
e) Rotor flux monitoring DDE
system
f) Power System Stabilizer in Not offered
AVR
g) Starters for AC / DC motors DOL
34.0 Generator Control Panel
a) List & description of breakers Refer enclosed SLD
requiring synchronization
b) Auto-synchronizer requirements

Waste to Energy Project at Deonar Volume 2C General Electrical Specification


i) Locations from where DDE
Auto-synchronizer can be
initiated
ii) Contact rating for closing DDE
contact
iii) Output for issuing raise / lower DDE
commands for speed and
voltage
iv) Feature for advancing closing DDE
command based on breaker
closing time
v) Facility for local and DDE
remote lockout reset
35.0 Online Condition monitoring
system (if provided)
a) Temperature range DDE
b) Power supply DDE
c) Distance between the DDE
Generators, generator and the
remote computer:
d) Insulation class DDE
e) Withstand ability of sensors DDE
for voltage surges: to be
designed to withstand high
voltage surges likely to be
encountered in service.

Waste to Energy Project at Deonar Volume 2C General Electrical Specification


20.3 Generator Transformer

SL.NO DESCRIPTION UNIT TECHNICAL PARTICULARS


1. Type Oil immerged
2. Number of transformers 1
3. Rated output MVA 8/10
4. No-load voltage ratio kV / kV 11/33
5. Frequency Hz 50
6. Impedance (nominal pos.) at max. 8
rating
7. Winding connection Star – Delta
8. Vector group Ynd11
9. Earthing of H.V Neutral Yes
10. Termination detail Cable for both side
11. Type of cooling ONAN/ONAF
12. Impulse & power frequency 75 & 28 for LV side
withstand voltages 170 & 70 for HV side
13. Tap changer OLTC
14. OLTC Range ±10% in step of 1.25%
15. Maximum temperature rise of oil Deg C 50
at110% of full load for 24 hrs above
ambient 50 degree cent.
16. Maximum temperature rise of Deg C 55
winding at 110% of full load for 24
hrs above ambient 50 degree cent....
17. Voltage class of bushings As per IS
18. Creepage distance Mm/kV 25
19. Over fluxing capability 1.8

Waste to Energy Project at Deonar Volume 2C General Electrical Specification


20.4 MV Switchgear

SL. NO. ITEM UNIT TECHNICAL PARTICULARS


1.0 SWITCHGEAR RATINGS
1.1 Nominal System Voltage Phases VOLTS, PH 11KV, 3 Ph, 50hz
& Frequency HZ
1.2 System neutral earthing Resistance earthed (STG NGR
earth)
1.3 Maximum system voltage Volts 12KV
1.4 Power frequency withstand kV (rms), 1 28
voltage min
1.5 1.2/50 µ sec. Impulse withstand kV 75
voltage (peak),
1.6 Short circuit withstand 1 Sec.
Short time (1 sec.) At rated voltage 40KA
1.6.1 kA (rms)
1.6.2 Dynamic rating kA (peak) DDE
Reference site ambient 50°
1.7
temperature
Continuous current rating of bus DDE
1.8 bars under reference site ambient
temp.
Maximum temperature of bus bars DDE
and droppers/connectors under
1.9
conditions specified
sr. Nos. 1.7 and 1.8 above
2.0 SWITCHGEAR
2.1 Ratings 11KV
Bus bars Aluminium
2.2
2.3 Cable entry Bottom
Total no. Of cubicles per As per SLD
2.4
switchgear
3.0 Switchgear Constructional
Requirements
3.1 Clearance in air Phase to phase Mm As per IS
3.2 Bus bar insulation DDE
3.3 Degree of protection IP4X
3.4 Earthing bus material Aluminium / GI
3.5 Colour finished shade
3.5.1 Interior RAL 7032
3.5.2 Exterior RAL 7032
4.0 CIRCUIT BREAKERS
4.1 BREAKER PARTICULARS
4.1.1 Circuit breaker type VCB
4.1.2 Voltage, frequency, & no.of ph. 11KV, 50hz, 3 Ph
Rated operating duty
4.1.3 0-0.35-CO-MIN-CO
4 . 1.4 Rated breaking current kA (rms) DOE
4.1.5 Rated making current kA(peak) ODE
4.1.6 Short time current withstand for 1 kA (rms) 140
sec. Duration.

Waste to Energy Project at Deonar Volume 2C General Electrical Specification


4.1.7 Asymmetrical breaking current
(a) AC COMPONENT kA (rms) DDE
(b) D.C. COMPONENT kA DDE
4.1.8 Total opening time cycle I ODE
msec
4.1.9 Total closing time cycle / DDE
msec
4.1.10 Operating mechanism, Type Spring charge motor
4.1.11 Minimum no. Of auxiliary conta
(a) For Closing/Tripping Coil VOLTS l lOV DC
(b) For Spring Charging Motors VOLTS 110V DC / 230V AC
(c) For Space Heaters & Lightin VOLTS 230V AC
4.1.12 Breaker application
(A) transformer control IYes
(B) motor control IYes (If a pplicable)
(C) furnace control NA
(D) capacitor control NA
4.2 MECHANISM
4.2.1 Spring charging Yes
4.2.2 Type Universal motor
4.2.3 Rating voltage v l lOV DC I 230V AC
4.2.4 Rating kW DDE
5.0 CURRENITTRANISFORMER
5.1 Type Cast resin
5.2 Class of insulation Class H
5.3 Accuracy class & burden
Metering DDE
Protn. DDE
5.4 Short time 1 sec. Current rating kA (rms) DDE
& dynam ic rating kA peak
6.0 VOLTAGE TRANSFORMERS
6.1 Type Cast resin
6.2 Rated voltage factor 11000/110/l OV
6.3 Class of insulation Class H
Provision of pt & alarm on !Yes
6.4
eathing trolley
7.0 METERS
7.1 Type Analog
T.2 Accuracy Class m 0.2
8.0 Relays Type Flush Mounted

Waste to Energy Project at Deonar Volume 2C General Electrical Specification


20.5 LV Switchgear

SL.
ITEM UNIT TECHNICAL PARTICULARS
NO.
1.0 SWITCHGEAR & BUSBAR
RATINGS
Rated voltage, phases & frequency l415V,3 Ph,50Hz
1.1
1.2 System neutral earthing Solid earthing
Maximum system voltage l440V
1.3
One minute power frequency 2.5
1.4 voltage
POWER CIRCUITS
CONTROL CIRCUITS VOLTS 415V
AUX. CIRCUITS CONNECTED TO VOLTS 230V
SEC. OF CTS VOLTS
230V
Continuous Current Rating Of DOE
1.5 Busbars Under Site Reference
Amb ient Temperature
Reference Amb ient Temperature c S0°C
1.6
0
Maximum Temperature Of DOE
Busbars, Droppers And Contacts c
1.7 At Continuous Current Rating
Under Site Reference Ambient 0
Temperature
Short Circuit Withstand For SOKA for 1sec.
Busbars And Droppers KA
1.8 A) short time (1 sec.) at 415v (RMS)
B) Dynamic Rating KA
(PEAK)
SWITCHGEAR PARTICULARS
2.0
415 V, AlUMINIUM, TPN, LT Yes
Switchgear.
SWITCHGEAR CONSTRUCTIONAL
3.0 REQUIREMENTS
3.1 Thickness of sheet steel
Cold rolled mm 1.6
Hot rolled mm 2.0
3.2 Degree of enclosure protection Upto 1250A:IP52 & above
1250A: IP42
Degree of enclosure protection Yes
3.3 against external mechanical
impacts
Colour finish shade as per is:5 RAL 7032
3.4 INTERIOR

Waste to Energy Project at Deonar Volume 2C General Electrical Specification


EXTERIOR
Aluminium / GI & DDE
3.5
Earthing material & size mm
Form of separation as per IEC DDE
3.6
60439-1
4.0 STARTERS
4.1 Type DOL / SD
4.2 Contactor rated duty DDE
4.3 Utilisation category DDE
4.4 Control transformer : Provided

4.5 Single phasing preventor required YES/ NO Yes for SD feeders


5.0 CIRCUIT BREAKER
5.1 Circuit breaker type ACB
5.2 Voltage, frequency & no. Of 415V, 50hz, 3 Ph
phases
5.3 Rated breaking duty DDE
Rated Breaking Capacity DDE
5.4
(a) a) MVA
(b) b) kA(RMS) AT 415V 0.25 P.F.
5.5 Short circuit withstand current for 1 kA 50KA
sec. Duration
5.6 Rated Making Current kA DDE
(PEAK)
5.7 Type Of Operating Mechanism Spring charge
5.8 Shunt Trip Required DDE
5.9 Minimum No of Auxiliary Contacts 2NO + 2NC
5.10 Control Voltage
(a) For Spring Charging Motor V 230V AC / 110V DC
(b) FOR CLOSING/TRIPPING V 110V DC
5.11 Annunciator Required DDE
6.0 MCB’s

6.1 Voltage, frequency & no of phases 415V, 50hz, 3 Ph


6.2 Rated operating duty DDE
6.3 Rated Breaking Capacity (AT 415V kA DDE
0.25 P.F.) (RMS)
6.4 Rated Making Current kA DDE
(Peak)

Waste to Energy Project at Deonar Volume 2C General Electrical Specification


20.6 LV Transformer

SL.NO DESCRIPTION UNIT TECHNICAL PARTICULARS


1. Type Oil immerged
2. Number of transformers 2 (2x100%)
3. Rated output MVA 2
4. No-load voltage ratio kV / kV 11/0.433
5. Frequency Hz 50
6. Impedance (nominal pos.) at 6.25
max.rating
7. Winding connection Delta-star
8. Vector group Dyn11
9. Earthing of H.V Neutral Yes
10. Termination detail Cable for HV and bus duct
for LV
11. Type of cooling ONAN
12. Impulse & power frequency 75 & 28 for HV and 2.5 & -
voltages for LV
13. Tap changer OCTC
14. OCTC Range ±5% instep of 2.5%
15. Voltage class of bushings 1.1KV
16. Creepage distance Mm/kV 25
17. Over fluxing capability 1.8
18. Degree of Protection DDE

Waste to Energy Project at Deonar Volume 2C General Electrical Specification