A. BATTERIES
1.0 SITE CONDITIONS
1.1 Location : *
1.2 Installation : *
1.3 Design Ambient Temperature : as per general design criteria
1.4 Altitude : as per general design criteria
1.5 Relative Humidity : as per general design criteria
1.6 Presence of H2S in atmosphere : No

2.0 TECHNICAL PARTICULARS


2.1 Tag No : *
2.2 Make/type :
2.3 Terminal voltage of battery bank
i) Nominal (open ckt. voltage) :
ii) Maximum (at the end of :
boost discharge)
iii) Minimum (at the end of :
discharge)
2.4 Capacity at 5 hr rate of discharge
(at 16°C/27°C/40°C) :
2.5 Number of cells in the Bank :
2.6 Type of construction-
i) Positive Plate :
ii) Negative Plate :
2.7 No. of Positive Plates per cell :
2.8 No. of Negative Plates per cell :
2.9 Type, material & thickness of :
separators
2.10 Internal resistance of each cell :
2.11 Electrolyte-
i) Quantity :
ii) Specific gravity (at full charge :
& at end of discharge
2.12 Charging rate for each cell-
a) Float voltage/current :
b) Boost voltage/current :
c) Equalise voltage/current :
2.13 Time for Boost charging : 10 hours
(0 to 100% capacity)
SPEC. No. DS 4023
OFFSHORE DATA SHEET FOR
BATTERY & BATTERY Rev. No. 0
DESIGN
CHARGER
SECTION Discipline Elect
Pages 2 of 6

2.14 Permissible ripple content : < 5%


in charging voltage
2.15 Maximum permissible
Electrolyte temperature-
i) Continuous :
ii) Short time :
2.16 Temperature correction factor :
for charging voltage
2.17 Cycle life of cell :
(for 70 and 100% DOD)
2.18 Temp. sensor provided inside the cell: Yes/No
2.19 No. of cells in which temp. sensor :
provided
2.20 Size of each cell (LxWxH) :
2.21 Weight of each cell with Electrolyte :
2.22 Battery rack-
a) No. of rows & tiers :
b) Dimensions (LxWxH) :
c) Weight (Rack & Batteries) :
2.23 Inter cell/ Inter row connectors-
a) Numbers :
b) Material :

B. BATTERY CHARGERS

1.0 SITE CONDITIONS


1.1 Location : *
1.2 Installation : SWITCHGEAR ROOM
1.3 Design Ambient Temperature : as per general design criteria
1.4 Altitude : as per general design criteria
1.5 Relative Humidity : as per general design criteria
1.6 Presence of H2S in atmosphere : NO

2.0 TECHNICAL PARTICULARS


2.1 Tag Nos : *
2.2 Make/type :
2.3 Mains input :
i) Voltage & frequency : 415V + 5%, TPN, 50 Hz + 3%
ii) Fault Level : *KA
iii) Current :
iv) Make /Type of MCCB :
SPEC. No. DS 4023
OFFSHORE DATA SHEET FOR
BATTERY & BATTERY Rev. No. 0
DESIGN
CHARGER
SECTION Discipline Elect
Pages 3 of 6

2.4 Output details:-


2.4.1 Float charger-
i) Voltage range :
ii) Current Range :
iii) Method of voltage control :
2.4.2 Boost charger-
i) Voltage range :
ii) Current range :
iii) Method of voltage control :
2.4.3 Load bus-
i) Voltage regulation from full
load to no load (for mains
variation of + 10%) :
ii) Harmonic content at rated load
with & without battery connected.: ----------- 1%

2.4.4 Circuit breaker


i) Make/Type/Rating :
ii) Float charger output :
iii) Boost charger output :
iv) Battery input :
v) Load output :
vi) Bus Tie :
2.5 Efficiency of-
i) Float charger (at 20% to :
100% load)
ii) Boost charger (at 20%, :
100% load)
2.6 Power factor of-
i) Float charger (at :
0%,20%,100% load)
ii) Boost charger (at
0%,20%,100% load) :
2.7 Annunciator details
i) Audio-visual annuciation points : D.C under voltage,
D.C over voltage,
charger failure,
A.C input failure,
earth fault,
load C.B trip.
SPEC. No. DS 4023
OFFSHORE DATA SHEET FOR
BATTERY & BATTERY Rev. No. 0
DESIGN
CHARGER
SECTION Discipline Elect
Pages 4 of 6

ii) Push Button : Acknowledge, test & reset


iii) Remote annunciation provision : Required
iv) Make/Type of annunciator :

2.8 Indication Lamps : A.C power ON


(one per phase)
Float charger ON,
Boost charger ON.

2.9 Meters : A.C input ammeter &


Voltmeter with four
Position selector switch,
output voltmeter with
selector switch for float,
boost, battery & load
voltage, battery
charge/discharge ammeter,
load ammeter.
2.10 Construction details-

i) Type of cooling : Natural/Forced


ii) Cable entry : Bottom
iii) Access : * Front/Rear/Both
iv) Enclosure degree of protection : IP-51(minimum)
v) Dimensions (LxWxH) :
vi) Weight :
vii) Earth bus material & size :
viii) Space heater (Watts/Voltage) : *W/240V 1 Phase, 50Hz, AC

2.11 Static component selection


PTRV : (Each component shall be rated for
(Peak Transient reverse voltages) not less than 2.5 times the line to
line voltage.)

NOTES
1. DATA MARKED WITH ASTERISK (*) SHALL BE FILLED UP BY
CONTRACTOR.ALL OTHER DATA SHALL BE FILLED UP BY VENDOR
AND FURNISHED ALONGWITH THE BID.

2. FOR LOAD DETAILS, REFER ATTACHED LOAD LIST


SPEC. No. DS 4023
OFFSHORE DATA SHEET FOR
BATTERY & BATTERY Rev. No. 0
DESIGN
CHARGER
SECTION Discipline Elect
Pages 5 of 6

3. BATTERY CHARGER RECTIFIER SHALL BE FULL WAVE, BRIDGE


CONNECTED, CONTROLLED TYPE.

4. THE OUTPUT OF 24 VOLT D.C SYSTEM SHALL BE (-) VE GROUNDED


THROUGH AN ISOLATING LINK. ALL THE LOADS CONNECTED TO
THE 24 VOLT D.C SYSTEM I.E COMPRESSOR CONTROL PANELS, C.P.
MONITORING SYSTEM, PACKAGE INSTRUMENT LOADS ETC. SHALL
BE DESIGNED ACCORDINGLY.

5. DETAILED TECHNICAL PARTICULARS FOR EACH OF THE BATTERY


AND CHARGER SET SHALL BE PROVIDED SEPARATELY.

6. AH CAPACITY OF BATTERY SHALL BE SELECTED CONSIDERING A


DESIGN AMBIENT TEMPERATURE OF 16 °C.
SPEC. No. DS 4023
OFFSHORE DATA SHEET FOR
BATTERY & BATTERY Rev. No. 0
DESIGN
CHARGER
SECTION Discipline Elect
Pages 6 of 6

INDICATIVE LOAD LIST

Sl No Description of Load Rating Duration

A 110 V DC

1 Swgr. & Generator Control * 2 Hrs

2 Emergency lube oil pumps * *

3 Emergency Lighting * 8

B 24 V DC

1 Local control panel * 30 minutes

2 Fire & Gas detection panel * 6 hours

3 CP monitoring Panel * 30 minutes

4 Radio System * 24 Hours

NOTES:
1. DATA MARKED WITH ASTERISK (*) SHALL BE DECIDED BY
CONTRACTOR & FURNISHED TO VENDOR.

2. EXCEPT FOR RADIO SYSTEM, ALL OTHER D.C SYSTEM LISTED


ABOVE SHALL CONSIST OF 2 NOS. OF BATTERY BANKS AND 2 NOS.
OF CORRESPONDING CHARGERS, EACH RATED FOR 50% CAPACITY.

3. THE D.C SYSTEM FOR RADIO EQUIPMENT SHALL HAVE 1 NO.


BATTERY BANK & SINGLE CHARGER RATED FOR 100% CAPACITY.

4. EACH BATTERY BANK SHALL HAVE 10% SPARE CAPACITY FOR


FUTURE LOAD GROWTH.