EQUIPMENT TAGS:
SERVICE DESCRIPTION: POWER TRANSFORMERS
CLIENT: 0 PURCHASER:
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: XXXXX-XXXX-33017
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

1.0 GENERAL
1.1 Manufacturer - VTS
1.2 Manufacturer location - VTS
1.3 Model No. - VTS
1.4 Serial No. - VTS
1.5 Design standard AS2374/IEC60076
1.6 No. of years Power transformer type in service (local/overseas) Years VTS
1.7 Year of manufacture - VTS
2.0 SITE CONDITIONS
2.1 Site conditions specification - XXXXX-XXXX-GXXXX
2.2 Pollution level -
2.3 Atmospheric conditions
2.4 Altitude above sea level m
2.5 Adverse ambient temperature conditions o
C
2.6 Design ambient temperature o
C
2.7 Seismic activity hazard factor (Z) -
2.8 Geographical location -
2.9 Project area
2.10 Solar irradiance (maximum) W/m2
2.11 Design wind load m/s
2.12 Design life Years
3.0 SYSTEM PARAMETERS
3.1 Phases
3.2 Frequency Hz
3.3 Primary Winding system highest Voltage, Um kV
3.4 Secondary Winding system highest Voltage, Um kV
3.5 Tertiary Winding system highest Voltage, Um V
3.6 Insulation Level Primary winding line terminals - Impulse Voltage kVp
3.7 Insulation Level Secondary winding line terminals - Impulse Voltage kVp
3.8 Insulation Level Tertiary winding line terminals - Impulse Voltage kVp
3.9 Insulation Level Primary winding line terminals - Power Frequency kV rms
3.10 Insulation Level Secondary winding line terminals - Power Frequency kV rms
3.11 Insulation Level Tertiary winding line terminals - Power Frequency kV rms
3.12 Primary Winding system earthing
3.13 Secondary Winding system earthing
3.14 Tertiary Winding system earthing
3.15 Power Supply Voltage for Fan & Pump Motors, OLTC motor & OLTC controls V, phase, Hz
3.16 AVR secondary voltage V
3.17 Line drop Current transformer (Ratio/Class/Accuracy/Output)
3.18 Primary Connection Type (Bushing/Cable Box)
3.19 Secondary Connection Type (Bushing/Cable Box)
3.20 Tertiary Connection Type (Bushing/Cable Box)
4.0 TRANSFORMER SPECIFICATIONS
4.1 Location (Indoor/Outdoor)
4.2 Construction Core/Shell
4.3 Dry Type or Oil Immersed
4.4 Cooling Type (ONAN/ONAF)
4.5 Rated continuous max Power, Primary (ONAN/ONAF) MVA
4.6 Rated continuous max Power, Secondary (ONAN/ONAF) MVA
4.7 Rated continuous max Power, Tertiary (ONAN/ONAF) MVA
4.8 Sustained Emergency Loading (% of continuous ONAF rating) pu
4.9 Duration of sustained emergency rating Hour
4.10 Tap changer (On Load/Off load)
4.11 Tap voltage range -% +%
4.12 Number of Tap positions
4.13 Tapping step %
4.14 Type of Voltage Variation
4.15 Max. continuous over-voltage on any tapping at continuous max. current
4.16 Rated no-load voltages on principal tapping (Primary/Secondary/Tertiary) kV
4.17 Connection Symbol (vector group)
4.18 Impedance Voltage (HV-LV) (base MVA) %
4.19 Impedance Voltage (HV-TV) (base MVA) %
4.20 Impedance Voltage (TV-LV) (base MVA) %
Disc Project
REV DATE Prepared Checked DESCRIPTION
Approved Approved
0 12/30/1899 0 0 0 0 0

Copyright 2014 by Jacobs Engineering Group Inc. 473779459.xlsx.xls


Page 2 of 18
0

0 DOC NO REV

0 0 0
0
EQUIPMENT TAGS:
SERVICE DESCRIPTION: POWER TRANSFORMERS
CLIENT: 0 PURCHASER:
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: XXXXX-XXXX-33017
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

5.0 GENERAL TECHNICAL REQUIREMENT


5.1 Number of Limbs
5.2 Radial winding arrangement from core
5.3 Separate Tapping Winding (Yes/No)
5.4 Stabilizing Winding (Yes/No)
5.5 No. of years Power transformer type in service (local/overseas)
5.6 Primary Winding Conductor Material
5.7 Secondary Winding Conductor Material
5.8 Tertiary Winding Conductor Material
5.9 Magnetising Inrush Current (xIn)
5.10 Primary Winding max current density
5.11 Secondary Winding max current density
5.12 Tertiary Winding max current density
5.13 Tapped winding max current density
5.14 Star Winding Insulation Graded (Yes/No)
5.15 Primary/Secondary/Tertiary Impedance on max ratio tapping @ 75deg C
5.16 Primary/Secondary/Tertiary Impedance on min ratio tapping @ 75deg C
5.17 Winding temperature Current transformer (Ratio/Class/Accuracy/Output)
5.18 Short Circuit Withstand of Primary Winding
5.19 Short Circuit Withstand of Secondary Winding
5.20 Short Circuit Withstand of Tertiary Winding
5.21 Top Oil Average Temperature Rise,ONAN rating
5.22 Average Winding Temperature Rise, ONAN rating
5.23 Top Oil Average Temperature Rise @ max current rating
5.24 Average Winding Temperature Rise @ max current rating
5.25 Max. Hot Spot Winding Temp Rise above ambient
5.26 Zero Sequence Impedance to HV winding @ principal tap position
5.27 3rd Harmonics in excitation current @ rated voltage
5.28 5th Harmonics in excitation current @ rated voltage
5.29 7th Harmonics in excitation current @ rated voltage
5.30 Max Sound Level (dBA at 1m) <82 dBA @ 1m
5.0 Auxiliaries control voltage V AC
5.1 Protection / control voltage V DC
6.0 BUSHINGS
6.1 HV & HV Neutral Bushings (Make & Type)
6.2 LV & LV Neutral Bushings (Make & Type)
6.3 Rated Current of HV Bushing
6.4 Rated Current of LV Bushing A
6.5 Rated Current of HV Neutral Bushing A
6.6 Rated Current of LV Neutral Bushing A
6.7 HV and HV Neutral Bushing Insulation Level (BIL) kVp
6.8 LV and LV Neutral Bushing Insulation Level (BIL) kVp
6.9 HV Bushing Minimum Creepage Distance
6.10 HV Neutral Bushing Minimum Creepage Distance mm
6.11 LV Bushing Minimum Creepage Distance mm
6.12 LV Neutral Bushing Minimum Creepage Distance mm
7.0 ON-LOAD TAP CHANGER
7.1 Manufacturer of OLTC
7.2 Type/Model of Tap Changer
7.3 Rated Current of Tap Changer A
7.4 Number of Tap Positions
7.5 Tap Position at Max. Full Load Loss
7.6 Linear/Coarse-Fine/Reversing Type

7.7 Expected number of tap-changes at full load before renewal of diverter switch
contacts
7.8 Make and Model of Automatic Voltage Regulator
7.9 Service Interval between OLTC Inspections
7.10 Service Interval between OLTC Contact Replacement
8.0 REGULATION AND EFFICIENCY
8.1 Regulation @ Rated Load and Unity P.F
8.2 Regulation @ Rated Load and 0.9 P.F
8.3 Regulation @ Rated Load and 0.8 P.F
8.4 Efficiency @ Rated Load and Unity P.F
8.5 Efficiency @ Rated Load and 0.9 P.F
8.6 Efficiency @ Rated Load and 0.8 P.F
Disc Project
REV DATE Prepared Checked DESCRIPTION
Approved Approved
0 12/30/1899 0 0 0 0 0

Copyright 2014 by Jacobs Engineering Group Inc. 473779459.xlsx.xls


Page 3 of 18
0

0 DOC NO REV

0 0 0
0
EQUIPMENT TAGS:
SERVICE DESCRIPTION: POWER TRANSFORMERS
CLIENT: 0 PURCHASER:
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: XXXXX-XXXX-33017
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

9.0 NO LOAD LOSS / LOAD LOSS & NO LOAD CURRENT


9.1 Guaranteed No-load loss @ rated Voltage kW
9.2 No-load loss @ 105% excitation kW
9.3 No-load loss @ 110% excitation kW
9.4 No-load current @ rated voltage (% of full load current) %
9.5 No-load current @ 105% excitation (% of full load current) %
9.6 No-load current @ 110% excitation (% of full load current) %
9.7 No. of years Power transformer type in service (local/overseas) kW
9.8 Guaranteed Loss on Principal tapping @ 75 deg C kW
9.9 Load Loss on min. ratio tapping @ 75 deg C kW
9.10 Guaranteed Cooling Plant Loss on Principal tapping kW
10.0 FITTINGS & INDICATORS
10.1 Make & Type of Gas & Oil Actuated Relay
10.2 Make & Type of Pressure Relief Device
10.3 Make & Type of OLTC Pressure Relief Device
10.4 Make & Type of Oil Level Gauge
10.5 Make & Type of anti-vibration pads
10.6 Total Surface Area of Anti-Vibration Pads m2
10.7 Oil Temperature Indicator (OTI)
10.8 Winding Temperature Indicator (WTI)
11.0 CABLE AND CABLE BOX DETAILS
11.1 HV (Primary) Cable Box Details (LxWxH)
11.2 HV (Primary Winding) Cable Size
11.3 HV (Primary) No of Cable Per Phase
11.4 HV (Primary) Cable Box Min Clearance (ph-ph)
11.5 HV (Primary) Cable Box Min Clearance (ph-E)
11.6 HV (Primary) Cable Box Degree of Protection (IP)
11.7 LV (Secondary) Cable Box Details (LxWxH)
11.8 LV (Secondary Winding) Cable Size
11.9 LV (Secondary) No of Cable Per Phase
11.10 LV (Secondary) Cable Box Min Clearance (ph-ph)
11.11 LV (Secondary) Cable Box Min Clearance (ph-E)
11.12 LV (secondary) Cable Box Degree of Protection (IP)
11.13 TV (Tertiary Winding) Cable Size
11.14 TV (Tertiary) No of Cable Per Phase
11.15 TV (Tertiary) Cable Box Min Clearance (ph-ph)
11.16 TV (Tertiary) Cable Box Min Clearance (ph-E)
11.17 TV (Tertiary) Cable Box Degree of Protection (IP)
12.0 OIL & OIL PRESERVATION SYSTEM V
12.1 Type of System
12.2 Make & Type of Air Cell
12.3 Manufacturer (Supplier) of Oil
12.4 Oil Capacity (litres & kg)
12.5 Oil type & grade (mineral or synthetic)
12.6 Make & type of dehydrating breather
13.0 GAS MONITORING SYSTEM
13.1 Make
13.2 Model
13.3 Output Requirement - Alarm Contacts
13.4 Output Requirement - Analogue Output
13.5 Communication
14.0 PAINTING SYSTEM
14.1 Paint Specification
14.2 Paint System
14.3 Paint Colour
15.0 INSPECTION & TESTS
15.1 Temperature Rise Test (Yes/No)
15.2 Lightning Impulse Test (Yes/No)
15.3 Routine Tests
16.0 TRANSPORTATION AND INSTALLATION
16.1 Special Transportation Requirements
16.2 Special Installation Requirements
16.3 Mounting Type (Bidirectional Roller/Pad Mounted)
16.4
16.5
16.6
Disc Project
REV DATE Prepared Checked DESCRIPTION
Approved Approved
0 12/30/1899 0 0 0 0 0

Copyright 2014 by Jacobs Engineering Group Inc. 473779459.xlsx.xls


Page 4 of 18
0

0 DOC NO REV

0 0 0
0
EQUIPMENT TAGS:
SERVICE DESCRIPTION: POWER TRANSFORMERS
CLIENT: 0 PURCHASER:
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: XXXXX-XXXX-33017
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

17.0 THERMAL DATA, CTs AND SURGE ARRESTORS


17.1 Thermal Capacity kWh/deg C
17.2 Winding Thermal Time Constant min
17.3 Oil Time Constant min
17.4 Primary bushing current transformer per phase (Ratio/Class/Accuracy/Output)
17.5 Secondary bushing current transformer per phase (Ratio/Class/Accuracy/Output)
17.6 Tertiary bushing current transformer per phase (Ratio/Class/Accuracy/Output)
17.7 No. of years Power transformer type in service (local/overseas)
17.8 Secondary side Neutral bushing current transformer (Ratio/Class/Accuracy/Output)
17.9 Tertiary side Neutral bushing current transformer (Ratio/Class/Accuracy/Output)
17.10 HV Surge Arrestor (Manufacturer / model)
17.11
18.0 DIMENSIONS, MASS, INSTALLATION & TRANSPORTATION
18.1 Overall Length mm
18.2 Overall Width mm
18.3 Overall Height mm
18.4 Main Tank Transport Length mm
18.5 Main Tank Transport Width mm
18.6 Main Tank Transport Height mm
18.7 Mass of Complete Unit kg
18.8 Main Tank Transport Mass kg
18.9 Transport Condition (oil filled/Gas filled)
18.10 Quantity of Oil to be Shipped separate (litres & kg) L/kg
18.11
19.0 APPLICABLE SPECIFICATIONS & DRAWINGS
19.1
19.2
19.3
19.4
20.0 APPLICABLE STANDARDS
20.1 AS 60076 series Power Transformers General
20.2 AS 60044.1 Instrument Transformers - Current Transformers
20.3 AS 2374.1.2 Power Transformers - MEPS

20.4 AS 2374.2 Power Transformers - Temperature Rise

20.5 AS 2374.5 Power Transformers - Ability to withstand short circuit

20.6 AS 60529 Degrees of Protection by Enclosures


20.7 AS 60214.1 Tap changers performance requirements and test methods
21.0 LIST OF TERMS USED IN DATA SHEET
21.1 CT Current Transformer
21.2 AVR Automatic Voltage Regulator
21.3 TBA To Be Advised
21.4 VTS Vendor To Specify
21.5 NER Neutral Earthing Resistor
21.6
21.7
21.8
21.9
21.10
21.11
21.12
21.13
21.14
21.15
21.16
21.17
21.18
21.19
21.20
21.21
21.22
Disc Project
REV DATE Prepared Checked DESCRIPTION
Approved Approved
0 12/30/1899 0 0 0 0 0

Copyright 2014 by Jacobs Engineering Group Inc. 473779459.xlsx.xls


Page 5 of 18
0

0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS: 300-SG-009 530-SG-007 P2


SERVICE DESCRIPTION: Vertical Riser 1 (VR-1) 11kV HV Switchboard
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

1.0 GENERAL
1.1 Manufacturer - STS
1.2 Manufacturer Location - STS
1.3 Model - STS
1.4 Design Standard - STS
1.5 Switchboard Technical Specification - 11442-0000-E0710
1.6 Wiring Identification Specification - 11442-0000-E0710
1.7 Single Line Diagram - Refer to Requisition
1.8
2.0 SITE CONDITIONS
2.1 Site Conditions Specification - 11442-0000-G0713
2.2 Altitude Above Sea Level m <1000
2.3 Design Ambient Temperature o
C 0-40
2.4 Seismic Condition - NA -
2.5 Location - Indoor
2.6 Environment - Indoor
2.7
3.0 SYSTEM PARAMETERS
3.1 System Voltage kV 11, +10% to -11%
3.2 Supply Frequency Hz 50, +/- 1Hz
3.3 No. of Phases - 3
3.4 System Prospective Short Circuit Current (Symmetrical RMS) kA/s 31.5kA / 3s
3.5 System Short Circuit Peak Current kA 60 70 - TBC P2
3.6 System Earthing - Resistance - TBA
3.7
4.0 SWITCHBOARD GENERAL
4.1 Rated Voltage kV 12
4.2 Rated Frequency Hz 50
4.3 Insulation Medium AIS / GIS AIS
4.4 Rated Short Circuit Withstand Current and Duration kA/s 31.5kA / 3s
4.5 Rated Peak Withstand Current kA 70
4.6 Rated Short Time Power Frequency Withstand kV 28
4.7 Rated Impulse Withstand Voltage kV 75
4.8 Type Test Certificate Number - STS
4.9 Type Testing Authority - STS
4.10 Arc Fault Containment Required Y/N Y
4.11 Duration of Arc Fault Test s STS
4.12 Name of Arc Testing Authority - STS
4.13 Total Switchboard Heat Loss at Full Load W STS
5.0 SWITCHBOARD BUSBARS
5.1 Busbar arrangement / Busbars per phase - STS
5.2 Busbar Material - Fully Insulated Cu
5.3 Main Busbar Size mm2 STS
5.4 Main Busbar Current Rating A 630A
5.5 Main Earth Busbar Size mm2 STS
5.6 Main Earth Busbar Current Rating A STS
5.7 Main Earth Bar Location - STS
5.8 Busbar Earth Switch (with Mechanical Interlock) Yes/No Yes
REV DATE BY CHK APPR AUTH DESCRIPTION
P1 7/28/2011 BR CJC CJC JR Issue for Client Review
P2 8/23/2011 BR CJC CJC JR Issue for Client Approval

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 6 of 18


473779459.xlsx ABN: 56 004 239 972
0

0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS: 300-SG-009 530-SG-007 P2


SERVICE DESCRIPTION: Vertical Riser 1 (VR-1) 11kV HV Switchboard
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

6.0 AUXILIARY VOLTAGE


6.1 Auxiliary Voltage - Protection & Tripping Internal / External External
6.2 -Auxiliary Voltage Supply Rating (Switchboard Demand) W STS
6.3 -Voltage / Tolerance V/% 48V dc / 10%
6.4 -Peak Demand A STS
6.5 -Load per Circuit Breaker Trip Coil A STS
6.6 Auxiliary Voltage - Closing, Motor and spring charging Internal / External External
6.7 -Voltage / Tolerance V/% 48V dc / 10%
6.8 -Peak Demand A STS
6.9 -Load per Circuit Breaker Close Coil A STS
6.10 -Load per Circuit Breaker Charging A STS
6.11 Auxiliary Voltage - Heaters Internal / External External
6.12 Auxiliary Voltage Supply - Tolerance V/% 230V ac
6.13 -Peak Demand W STS
6.14 -Motor Heater Voltage V 230V ac
7.0 SWITCHBOARD - CONSTRUCTION
7.1 Future Extension - Both ends
7.2 Total Number of Tiers - 6
7.3 Incomer Sections - 1
7.4 Bus Tie Sections - None
7.5 Feeder Sections - 1
7.6 Motor Feeder Sections - 1
7.7 Switchboard Type - Partition Metallic
7.8 Enclosure IP Rating IP 42 41 P2
7.9 Enclosure Material - Steel 2mm
7.10 Module Type Withdrawable / Fixed Withdrawable
7.11 Power Cables - Cable Entry Top / Bottom Bottom
7.12 Control Cables - Cable Entry Top / Bottom Top
7.13 Gland Plate Material and Size - Al, 6mm
7.14 Surface Finish - Supplier standard
7.15 Colour Internal - Supplier standard
7.16 Colour External - RAL 7035
8.0 SWITCHBOARD - DIMENSIONS AND WEIGHTS
8.1 Overall Dimension (L x W x H) mm STS
8.2 Minimum Clearance Required at Front of Switchboard mm STS
8.3 Minimum Clearance Required at Rear of Switchboard mm <100mm typ
8.4 Minimum Clearance Required at Side of Switchboard mm <100mm typ
8.5 Minimum Clearance Required Above Switchboard mm <100mm typ
8.6 Lifting Arrangement - STS
8.7 Total Installed Weight kg STS
8.8 Total Shipping Weight kg STS
8.9 Shipping Section (L x W x H) and Qty mm / ea STS
8.10 Maximum Shipping Section Weight kg STS
9.0 ACCESSORIES AND OPTIONS
9.1 Circuit Breaker Trolley Y/N Y
9.2 CB Racking Handles Y/N Y
9.3 CB Charging Handles Y/N Y
9.4 Special Tools Y/N Y
9.5 Earth Switch Charging Handle Y/N Y
9.6 Remote Switchboard Control Panel Y/N Note 3
9.7 Remote PCS Control Y/N Y
9.8 Load Shedding Panel Y/N N -
9.9 Switchboard Monitoring and Control System Y/N Part of PCS -
9.10 Anticondensation Heaters Y/N Y
9.11 Fire Detection Y/N N -
9.12 Fire Suppression Y/N N -

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 7 of 18


473779459.xlsx ABN: 56 004 239 972
0

0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS: 300-SG-009 530-SG-007 P2


SERVICE DESCRIPTION: Vertical Riser 1 (VR-1) 11kV HV Switchboard
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

10.0 SWITCH BOARD AUXILIARY CONTROL EQUIPMENT MAKES AND MODELS


10.1 Miniature Circuit Breakers - -
10.2 Make / Type - STS
10.3 Rated Voltage kV STS
10.4 Control Voltage Transformer - -
10.5 Make / Type - STS
10.6 Voltage Ratio V/V STS
10.7 Rating VA STS
10.7 Load Capacity Calculation Basis - STS
10.8 DC Power Supply - External , By Others
10.9 Make / Type - NA
10.10 Vin / V Out V/V NA
10.11 Amps Continuous A NA
10.12 AC Control Relays - -
10.13 Make / Type - STS
10.13 Rated Voltage V ac 230V ac
10.14 Auxiliary Contacts - 1 N/O + 1 N/C (Spare)
10.15 Auxiliary Contact Rating V/A 230V ac, 10A
10.16 DC Control Relay - -
10.17 Make / Type - STS
10.18 Rated Voltage V dc 48
10.19 Auxiliary Contacts - 1 N/O + 1 N/C (Spare)
10.20 Auxiliary Contact Rating V/A 48V dc, 5A
10.21 Control Switches - Make / Type - STS
10.22 Control Switches - Voltage V STS
10.23 Pushbuttons - Make / Type - STS
10.24 Power Terminals Make / Type - STS
10.25 Control Terminals Make / Type - STS
11.0 SWITCHBOARD TIER - CURRENT TRANSFORMERS
11.1 Protection CT Manufacturer - STS
11.2 Protection CT Burden and Class - STS
11.3 Protection CT Ratio A/A As per Single Line Diagram
11.5 Differential Protection CT Manufacturer - STS
11.7 Differential Protection CT Burden and Class - STS
11.6 Differential Protection CT Ratio A/A As per Single Line Diagram
11.8 Earth Leakage Toroid Manufacturer - STS
11.9 Earth Leakage Toroid Ratio A/A As per Single Line Diagram
11.10 Earth Leakage Toroid Class - STS
11.11 Transformer Neutral CT Manufacturer - By Others -
11.12 Transformer Neutral CT Ratio A/A By Others -
11.13 Transformer Neutral CT Burden and Class - By Others -
12.0 SWITCHBOARD TIER - VOLTAGE TRANSFORMERS
12.1 Voltage Ratio V/V 11kV / 110V
12.2 Power / Class VA STS
12.3 Fixed / Withdrawable - STS
12.4 Primary Fuse Rating A STS
12.5 Secondary Fuse Rating A STS

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 8 of 18


473779459.xlsx ABN: 56 004 239 972
0

0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS: 300-SG-009 530-SG-007 P2


SERVICE DESCRIPTION: Vertical Riser 1 (VR-1) 11kV HV Switchboard
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

13.0 SWITCHBOARD TIER


13.1 Service - Incomer
13.2 Device Type - Circuit Breaker
13.3 Device Model / Manufacturer - STS
13.4 Switching Device Insulation Type SF6 / Vacuum STS
13.5 Continuous Rating A 630A
13.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s
13.7 Rated Short Circuit Breaking Current rms kA 31.5
13.8 Rated Short Circuit Making Current rms kA STS
13.9 Earth Switch Required and Location (with mechanical interlock) Y/N Y, Cable Side
13.10 Earth Switch Making Current Capacity kA STS
13.11 Protection and Metering Relay Y/N Y (Refer to sections 17 and 18)
13.12 Spring Charging Manual Y/N Y
13.13 Spring Charging Motorized Y/N Y
13.14 Operation Duty - STS
13.15 Number of Operations per Annum - STS
13.16 Opening Time ms STS
13.17 Protection Scheme - Refer Single Line Diagram
13.18 Shunt Trip Coil Y/N Y
13.19 Shunt Trip Coil - Minimum Voltage to Activate %V Min. 90%
13.20 No Voltage Coil Y/N N -
13.21 Amp Metering Switch & Ammeter Y/N N -
13.22 Volt Metering Switch & Voltmeter Y/N N -
13.23 Key Interlocking System Description - None
13.24 Surge Arrestor Y/N Y
13.25 Cable Type - Cu, XLPE/SWA/XLPE
13.26 Cable Entry - Bottom
13.27 Max Cable Size mm2 1 x 3C 95mm2
13.28 Live Cable Indication Y/N Y
13.29 Tier Section Dimensions (L x W x H) mm STS
14.0 SWITCHBOARD TIER
14.1 Service - Bus Tie
14.2 Device Type - Circuit Breaker
14.3 Device Model / Manufacturer - STS
14.4 Switching Device Insulation Type SF6 / Vacuum STS
14.5 Continuous Rating A 630A
14.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s
14.7 Rated Short Circuit Breaking Current rms kA 31.5
14.8 Rated Short Circuit Making Current rms kA STS
14.9 Spring Charging Manual Y/N Y
14.10 Spring Charging Motorized Y/N Y
14.11 Operation Duty - STS
14.12 Number of Operations per Annum - STS
14.13 Opening Time (Full Load) ms STS
14.14 Protection Scheme - NA
14.15 Shunt Trip Coil Y/N N -
14.16 Shunt Trip Coil - Minimum Voltage to Activate %V NA -
14.17 No Voltage Coil Y/N N -
14.18 Key Interlocking System Description - None
14.19 Tier Section Dimensions (L x W x H) mm STS

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 9 of 18


473779459.xlsx ABN: 56 004 239 972
0

0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS: 300-SG-009 530-SG-007 P2


SERVICE DESCRIPTION: Vertical Riser 1 (VR-1) 11kV HV Switchboard
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

15.0 SWITCHBOARD TIER


15.1 Service - Typical Feeder
15.2 Device Type - Circuit Breaker
15.3 Device Model / Manufacturer - STS
15.4 Switching Device Insulation Type SF6 / Vacuum STS
15.5 Continuous Rating A 630A
15.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s
15.7 Rated Short Circuit Breaking Current rms kA 31.5
15.8 Rated Short Circuit Making Current rms kA STS
15.9 Earth Switch Required and Location (with mechanical interlock) Y/N Y, Cable Side
15.10 Earth Switch Making Current Capacity kA STS
15.11 Protection and Metering Relay Y/N Y (Refer to sections 17 and 18)
15.12 Spring Charging Manual Y/N Y
15.13 Spring Charging Motorized Y/N Y
15.14 Operation Duty - STS
15.15 Number of Operations per Annum - STS -
15.16 Opening Time ms STS -
15.17 Protection Scheme - Refer Single Line Diagram
15.18 Shunt Trip Coil Y/N Y
15.19 Shunt Trip Coil - Minimum Voltage to Activate %V Min 90%
15.20 No Voltage Coil Y/N Motor Starter only
15.21 Amp Metering Switch & Ammeter Y/N N -
15.22 Volt Metering Switch & Voltmeter Y/N N -
15.23 Key Interlocking System Description - None
15.24 Surge Arrestor Y/N Y
15.25 Cable Type - Cu, XLPE/SWA/XLPE
15.26 Cable Entry - Bottom
15.27 Max Cable Size mm2 1 x 3C 95mm2
15.28 Live Cable Indication Y/N Y
15.29 Tier Section Dimensions (L x W x H) mm STS
16.0 SWITCHBOARD TIER
16.1 Service - Typical Motor Starter
16.2 Device Type - Circuit Breaker
16.3 Device Model / Manufacturer - STS
16.4 Switching Device Insulation Type SF6 / Vacuum STS
16.5 Continuous Rating A 630A
16.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s
16.7 Rated Short Circuit Breaking Current rms kA 31.5
16.8 Rated Short Circuit Making Current rms kA STS
16.9 Earth Switch Required and Location (with mechanical interlock) Y/N Y, Cable Side
16.10 Earth Switch Making Current Capacity kA STS
16.11 Protection and Metering Relay Y/N Y (Refer to sections 17 and 18)
16.12 Spring Charging Manual Y/N Y
16.13 Spring Charging Motorized Y/N Y
16.14 Operation Duty - STS
16.15 Number of Operations per Annum - STS -
16.16 Opening Time ms STS -
16.17 Protection Scheme - Refer Single Line Diagram
16.18 Shunt Trip Coil Y/N Y
16.19 Shunt Trip Coil - Minimum Voltage to Activate %V STS
16.20 No Voltage Coil Y/N Y
16.21 Amp Metering Switch & Ammeter Y/N N -
16.22 Volt Metering Switch & Voltmeter Y/N N -
16.23 Key Interlocking System Description - None
16.24 Surge Arrestor Y/N Y
16.25 Cable Type - Cu, XLPE/SWA/XLPE
16.26 Cable Entry - Bottom
16.27 Max Cable Size mm2 1 x 3C 95mm2
16.28 Live Cable Indication Y/N Y
16.29 Tier Section Dimensions (L x W x H) mm STS

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 10 of 18


473779459.xlsx ABN: 56 004 239 972
0

0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS: 300-SG-009 530-SG-007 P2


SERVICE DESCRIPTION: Vertical Riser 1 (VR-1) 11kV HV Switchboard
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

17.0 SWITCHBOARD TIER - PROTECTION RELAYS


17.1 Protection Relay Model - Motors <1MW - STS
17.2 Protection Relay Model - Motors ≥1MW - STS
17.3 Protection Relay Model - Transformer - STS
17.4 Protection Relay Model - Incomer - STS
17.5 Protection Relay Model - Generators - STS
17.6 Protection device Open, Voltage Free Contact - 4 N/O
17.7 Protection device Closed, Voltage Free Contact - 4 N/O
17.8 Protection device Status, Voltage Free Contact - 2 N/O for each position
17.9 Protection device Spring Charged, Voltage Free Contact - 2 N/O
17.10 Protection Relay Trip, Voltage Free Contact - 2 N/O + 2 N/C
17.11 Protection Relay Alarm, Voltage Free Contact - 2 N/O + 2 N/C
17.12
18.0 SWITCHBOARD TIER - METERING
18.1 Metering Type Make / Type Part of protection relay
18.2 -Amp Meter Y/N Part of protection relay
18.3 -Volt Meter Y/N Part of protection relay
18.4 -kW, kVAr, kVA Meter Y/N Part of protection relay
18.5 -kW/hr, kVAr/hr, kVA/hr Meter Y/N Part of protection relay
18.6 -Power Factor Y/N Part of protection relay
18.7 -Hours Run Meter Y/N Part of protection relay
18.8 -Frequency Y/N Part of protection relay
18.9 -%THD Y/N Part of protection relay
18.10 -Communication Protocol - Profibus DP - TBC
18.11
19.0 NOTES & ABBREVIATIONS
19.1 1. Supplier to complete all empty fields or where noted as "STS" (Supplier to State)
19.2 2. Refer 11442-0000-E0710 Clause 8.24 and functionality shown in Single Line Diagram
19.3
19.4
19.5 Abbreviations
19.6 NA = Not Applicable
19.7 STS = Supplier to State
19.8 TBC = To be Confirmed
19.9
0

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 11 of 18


473779459.xlsx ABN: 56 004 239 972
0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS:
SERVICE DESCRIPTION:
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

1.0 GENERAL
1.1 Manufacturer - STS
1.2 Manufacturer Location - STS
1.3 Model - STS
1.4 Design Standard - STS
1.5 Switchboard Technical Specification - 11442-0000-E0710
1.6 Wiring Identification Specification - 11442-0000-E0710
1.7 Single Line Diagram - Refer to Requisition
1.8
2.0 SITE CONDITIONS
2.1 Site Conditions Specification - 11442-0000-G0713
2.2 Altitude Above Sea Level m <1000
2.3 Design Ambient Temperature o
C 0-40
2.4 Seismic Condition - NA -
2.5 Location - Indoor
2.6 Environment - Indoor
2.7
3.0 SYSTEM PARAMETERS
3.1 System Voltage kV 11, +10% to -11%
3.2 Supply Frequency Hz 50, +/- 1Hz
3.3 No. of Phases - 3
3.4 System Prospective Short Circuit Current (Symmetrical RMS) kA/s 31.5kA / 3s
3.5 System Short Circuit Peak Current kA 70 - TBC
3.6 System Earthing - Resistance - TBA
3.7
4.0 SWITCHBOARD GENERAL
4.1 Rated Voltage kV 12
4.2 Rated Frequency Hz 50
4.3 Insulation Medium AIS / GIS AIS
4.4 Rated Short Circuit Withstand Current and Duration kA/s 31.5kA / 3s
4.5 Rated Peak Withstand Current kA 70
4.6 Rated Short Time Power Frequency Withstand kV 28
4.7 Rated Impulse Withstand Voltage kV 75
4.8 Type Test Certificate Number - STS
4.9 Type Testing Authority - STS
4.10 Arc Fault Containment Required Y/N Y
4.11 Duration of Arc Fault Test s STS
4.12 Name of Arc Testing Authority - STS
4.13 Total Switchboard Heat Loss at Full Load W STS
5.0 SWITCHBOARD BUSBARS
5.1 Busbar arrangement / Busbars per phase - STS
5.2 Busbar Material - Fully Insulated Cu
5.3 Main Busbar Size mm2 STS
5.4 Main Busbar Current Rating A Refer Single Line Diagram
5.5 Main Earth Busbar Size mm2 STS
5.6 Main Earth Busbar Current Rating A STS
5.7 Main Earth Bar Location - STS
5.8 Busbar Earth Switch (with Mechanical Interlock) Yes/No Yes
REV DATE BY CHK APPR AUTH DESCRIPTION
P1 6/10/2011 BR CJC CJC JR Preliminary review

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 12 of 18


473779459.xlsx ABN: 56 004 239 972
0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS:
SERVICE DESCRIPTION:
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

6.0 AUXILIARY VOLTAGE


6.1 Auxiliary Voltage - Protection & Tripping Internal / External External
6.2 -Auxiliary Voltage Supply Rating (Switchboard Demand) W STS
6.3 -Voltage / Tolerance V/% 48V dc / 10%
6.4 -Peak Demand A STS
6.5 -Load per Circuit Breaker Trip Coil A STS
6.6 Auxiliary Voltage - Closing, Motor and spring charging Internal / External External
6.7 -Voltage / Tolerance V/% 48V dc / 10%
6.8 -Peak Demand A STS
6.9 -Load per Circuit Breaker Close Coil A STS
6.10 -Load per Circuit Breaker Charging A STS
6.11 Auxiliary Voltage - Heaters Internal / External External
6.12 Auxiliary Voltage Supply - Tolerance V/% 230V ac
6.13 -Peak Demand W STS
6.14 -Motor Heater Voltage V 230V ac
7.0 SWITCHBOARD - CONSTRUCTION
7.1 Future Extension - Both ends
7.2 Total Number of Tiers - As per Single line Diagram
7.3 Incomer Sections - As per Single line Diagram
7.4 Bus Tie Sections - As per Single line Diagram
7.5 Feeder Sections - As per Single line Diagram
7.6 Motor Feeder Sections - As per Single line Diagram
7.7 Switchboard Type - Partition Metallic
7.8 Enclosure IP Rating IP 41
7.9 Enclosure Material - Steel 2mm
7.10 Module Type Withdrawable / Fixed Withdrawable
7.11 Power Cables - Cable Entry Top / Bottom Bottom
7.12 Control Cables - Cable Entry Top / Bottom Top / Bottom
7.13 Gland Plate Material and Size - Al, 6mm
7.14 Surface Finish - Supplier standard
7.15 Colour Internal - Supplier standard
7.16 Colour External - RAL 7035
8.0 SWITCHBOARD - DIMENSIONS AND WEIGHTS
8.1 Overall Dimension (L x W x H) mm STS
8.2 Minimum Clearance Required at Front of Switchboard mm STS
8.3 Minimum Clearance Required at Rear of Switchboard mm <100mm typ
8.4 Minimum Clearance Required at Side of Switchboard mm <100mm typ
8.5 Minimum Clearance Required Above Switchboard mm <100mm typ
8.6 Lifting Arrangement - STS
8.7 Total Installed Weight kg STS
8.8 Total Shipping Weight kg STS
8.9 Shipping Section (L x W x H) and Qty mm / ea STS
8.10 Maximum Shipping Section Weight kg STS
9.0 ACCESSORIES AND OPTIONS
9.1 Circuit Breaker Trolley Y/N Y
9.2 CB Racking Handles Y/N Y
9.3 CB Charging Handles Y/N Y
9.4 Special Tools Y/N Y
9.5 Earth Switch Charging Handle Y/N Y
9.6 Remote Switchboard Control Panel Y/N Note 3
9.7 Remote PCS Control Y/N Y
9.8 Load Shedding Panel Y/N N -
9.9 Switchboard Monitoring and Control System Y/N Part of PCS -
9.10 Anticondensation Heaters Y/N Y
9.11 Fire Detection Y/N N -
9.12 Fire Suppression Y/N N -

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 13 of 18


473779459.xlsx ABN: 56 004 239 972
0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS:
SERVICE DESCRIPTION:
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

10.0 SWITCH BOARD AUXILIARY CONTROL EQUIPMENT MAKES AND MODELS


10.1 Miniature Circuit Breakers - -
10.2 Make / Type - STS
10.3 Rated Voltage kV STS
10.4 Control Voltage Transformer - -
10.5 Make / Type - STS
10.6 Voltage Ratio V/V STS
10.7 Rating VA STS
10.7 Load Capacity Calculation Basis - STS
10.8 DC Power Supply - External , By Others
10.9 Make / Type - NA
10.10 Vin / V Out V/V NA
10.11 Amps Continuous A NA
10.12 AC Control Relays - -
10.13 Make / Type - STS
10.13 Rated Voltage V ac 230V ac
10.14 Auxiliary Contacts - 1 N/O + 1 N/C (Spare)
10.15 Auxiliary Contact Rating V/A 230V ac, 10A
10.16 DC Control Relay - -
10.17 Make / Type - STS
10.18 Rated Voltage V dc 48
10.19 Auxiliary Contacts - 1 N/O + 1 N/C (Spare)
10.20 Auxiliary Contact Rating V/A 48V dc, 5A
10.21 Control Switches - Make / Type - STS
10.22 Control Switches - Voltage V STS
10.23 Pushbuttons - Make / Type - STS
10.24 Power Terminals Make / Type - STS
10.25 Control Terminals Make / Type - STS
11.0 SWITCHBOARD TIER - CURRENT TRANSFORMERS
11.1 Protection CT Manufacturer - STS
11.2 Protection CT Burden and Class - STS
11.3 Protection CT Ratio A/A As per Single Line Diagram
11.5 Differential Protection CT Manufacturer - STS
11.7 Differential Protection CT Burden and Class - STS
11.6 Differential Protection CT Ratio A/A As per Single Line Diagram
11.8 Earth Leakage Toroid Manufacturer - STS
11.9 Earth Leakage Toroid Ratio A/A As per Single Line Diagram
11.10 Earth Leakage Toroid Class - STS
11.11 Transformer Neutral CT Manufacturer - By Others -
11.12 Transformer Neutral CT Ratio A/A By Others -
11.13 Transformer Neutral CT Burden and Class - By Others -

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 14 of 18


473779459.xlsx ABN: 56 004 239 972
0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS:
SERVICE DESCRIPTION:
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

12.0 SWITCHBOARD TIER - VOLTAGE TRANSFORMERS


12.1 Voltage Ratio V/V 11kV / 110V
12.2 Power / Class VA STS
12.3 Fixed / Withdrawable - STS
12.4 Primary Fuse Rating A STS
12.5 Secondary Fuse Rating A STS
13.0 SWITCHBOARD TIER
13.1 Service - Incomer
13.2 Device Type - Circuit Breaker
13.3 Device Model / Manufacturer - STS
13.4 Switching Device Insulation Type SF6 / Vacuum STS
13.5 Continuous Rating A As per Single Line Diagram
13.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s
13.7 Rated Short Circuit Breaking Current rms kA 31.5
13.8 Rated Short Circuit Making Current rms kA STS
13.9 Earth Switch Required and Location (with mechanical interlock) Y/N Y, Cable Side
13.10 Earth Switch Making Current Capacity kA STS
13.11 Protection and Metering Relay Y/N Y (Refer to sections 18 and 19)
13.12 Spring Charging Manual Y/N Y
13.13 Spring Charging Motorized Y/N Y
13.14 Operation Duty - STS
13.15 Number of Operations per Annum - STS
13.16 Opening Time ms STS
13.17 Protection Scheme - Refer Single Line Diagram
13.18 Shunt Trip Coil Y/N Y
13.19 Shunt Trip Coil - Minimum Voltage to Activate %V Min. 90%
13.20 No Voltage Coil Y/N N -
13.21 Amp Metering Switch & Ammeter Y/N N -
13.22 Volt Metering Switch & Voltmeter Y/N N -
13.23 Key Interlocking System Description - Note 4
13.24 Surge Arrestor Y/N Y
13.25 Cable Type - Cu, XLPE/SWA/XLPE
13.26 Cable Entry - Bottom
13.27 Max Cable Size mm2 STS
13.28 Live Cable Indication Y/N Y
13.29 Tier Section Dimensions (L x W x H) mm STS
14.0 SWITCHBOARD TIER
14.1 Service - Bus Tie
14.2 Device Type - Circuit Breaker
14.3 Device Model / Manufacturer - STS
14.4 Switching Device Insulation Type SF6 / Vacuum STS
14.5 Continuous Rating A As per Single Line Diagram
14.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s
14.7 Rated Short Circuit Breaking Current rms kA 31.5
14.8 Rated Short Circuit Making Current rms kA STS
14.9 Spring Charging Manual Y/N Y
14.10 Spring Charging Motorized Y/N Y
14.11 Operation Duty - STS
14.12 Number of Operations per Annum - STS
14.13 Opening Time (Full Load) ms STS
14.14 Protection Scheme - NA
14.15 Shunt Trip Coil Y/N N -
14.16 Shunt Trip Coil - Minimum Voltage to Activate %V NA -
14.17 No Voltage Coil Y/N N -
14.18 Key Interlocking System Description - Note 4
14.19 Tier Section Dimensions (L x W x H) mm STS

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 15 of 18


473779459.xlsx ABN: 56 004 239 972
0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS:
SERVICE DESCRIPTION:
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

15.0 SWITCHBOARD TIER


15.1 Service - Feeder or Motor Starter
15.2 Device Type - Fuse Contactor
15.3 Device Model / Manufacturer - NA -
15.4 Switching Device Insulation Type SF6 / Vacuum NA -
15.5 Fuse Continuous Rating A NA -
15.6 Fuse Rated Short-Time Withstand Current and Duration kA/s NA -
15.7 Contactor Continuous Rating A NA -
15.8 Contactor Rated Short-Time Withstand Current and Duration kA/s NA -
15.9 Contactor Breaking Current Capacity A NA -
15.10 Contactor Making Current Capacity A NA -
15.11 Earth Switch Required and Location (with mechanical interlock) Y/N NA -
15.12 Earth Switch Making Current Capacity kA NA -
15.13 Interrupting time ms NA -
15.14 Protection and Metering Relay Y/N NA -
15.15 Protection Scheme - NA -
15.16 Shunt Trip Coil Y/N NA -
15.17 Shunt Trip Coil - Minimum Voltage to Activate %V NA -
15.18 No Voltage Coil Y/N NA -
15.19 Amp Metering Switch & Ammeter Y/N NA -
15.20 Volt Metering Switch & Voltmeter Y/N NA -
15.21 Key Interlocking System Description - NA -
15.22 Surge Arrestor Y/N NA -
15.23 Cable Type - NA -
15.24 Cable Entry - NA -
15.25 Max Cable Size mm2 NA -
15.26 Live Cable Indication Y/N NA -
15.27 Tier Section Dimensions (L x W x H) mm NA -
16.0 SWITCHBOARD TIER
16.1 Service - Typical Feeder
16.2 Device Type - Circuit Breaker
16.3 Device Model / Manufacturer - STS
16.4 Switching Device Insulation Type SF6 / Vacuum STS
16.5 Continuous Rating A 630A
16.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s
16.7 Rated Short Circuit Breaking Current rms kA 31.5
16.8 Rated Short Circuit Making Current rms kA STS
16.9 Earth Switch Required and Location (with mechanical interlock) Y/N Y, Cable Side
16.10 Earth Switch Making Current Capacity kA STS
16.11 Protection and Metering Relay Y/N Y (Refer to sections 18 and 19)
16.12 Spring Charging Manual Y/N Y
16.13 Spring Charging Motorized Y/N Y
16.14 Operation Duty - STS
16.15 Number of Operations per Annum - STS -
16.16 Opening Time ms STS -
16.17 Protection Scheme - Refer Single Line Diagram
16.18 Shunt Trip Coil Y/N Y
16.19 Shunt Trip Coil - Minimum Voltage to Activate %V Min 90%
16.20 No Voltage Coil Y/N Motor Starter only
16.21 Amp Metering Switch & Ammeter Y/N N -
16.22 Volt Metering Switch & Voltmeter Y/N N -
16.23 Key Interlocking System Description - None
16.24 Surge Arrestor Y/N Y
16.25 Cable Type - Cu, XLPE/SWA/XLPE
16.26 Cable Entry - Bottom
16.27 Max Cable Size mm2 STS
16.28 Live Cable Indication Y/N Y
16.29 Tier Section Dimensions (L x W x H) mm STS
17.0 SWITCHBOARD TIER
17.1 Service - Typical Motor Starter
17.2 Device Type - Circuit Breaker
17.3 Device Model / Manufacturer - STS
17.4 Switching Device Insulation Type SF6 / Vacuum STS
17.5 Continuous Rating A 630A

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 16 of 18


473779459.xlsx ABN: 56 004 239 972
0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS:
SERVICE DESCRIPTION:
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

17.6 Rated Short-Time Withstand Current and Duration kA/s 31.5/3s


17.7 Rated Short Circuit Breaking Current rms kA 31.5
17.8 Rated Short Circuit Making Current rms kA STS
17.9 Earth Switch Required and Location (with mechanical interlock) Y/N Y, Cable Side
17.10 Earth Switch Making Current Capacity kA STS
17.11 Protection and Metering Relay Y/N Y (Refer to sections 18 and 19)
17.12 Spring Charging Manual Y/N Y
17.13 Spring Charging Motorized Y/N Y
17.14 Operation Duty - STS
17.15 Number of Operations per Annum - STS -
17.16 Opening Time ms STS -
17.17 Protection Scheme - Refer Single Line Diagram
17.18 Shunt Trip Coil Y/N Y
17.19 Shunt Trip Coil - Minimum Voltage to Activate %V STS
17.20 No Voltage Coil Y/N Y
17.21 Amp Metering Switch & Ammeter Y/N N -
17.22 Volt Metering Switch & Voltmeter Y/N N -
17.23 Key Interlocking System Description - SAG & Ball Mill required
17.24 Surge Arrestor Y/N Y
17.25 Cable Type - Cu, XLPE/SWA/XLPE
17.26 Cable Entry - Bottom
17.27 Max Cable Size mm2 STS
17.28 Live Cable Indication Y/N Y
17.29 Tier Section Dimensions (L x W x H) mm STS

OP4.E3305_1 Jacobs E&C Australia Pty Ltd Page: 17 of 18


473779459.xlsx ABN: 56 004 239 972
0 DOC NO REV

ELECTRICAL DATA SHEET 0 0

EQUIPMENT TAGS:
SERVICE DESCRIPTION:
CLIENT: 0 PURCHASER: 0
PROJECT TITLE: 0 PROJECT NUMBER: 0
REQUISITION NUMBER: 11442-0000-33010
ITEM DESCRIPTION UNIT PURCHASER SUPPLIER

18.0 SWITCHBOARD TIER - PROTECTION RELAYS


18.1 Protection Relay - Motors <1MW - STS
18.2 Protection Relay - Motors ≥1MW - STS
18.3 Protection Relay - Transformer - STS
18.4 Protection Relay - Incomer - STS
18.5 Protection Relay - Generators - STS
18.6 Protection device Open, Voltage Free Contact - 4 N/O
18.7 Protection device Closed, Voltage Free Contact - 4 N/O
18.8 Protection device Status, Voltage Free Contact - 2 N/O for each position
18.9 Protection device Spring Charged, Voltage Free Contact - 2 N/O
18.10 Protection Relay Trip, Voltage Free Contact - 2 N/O + 2 N/C
18.11 Protection Relay Alarm, Voltage Free Contact - 2 N/O + 2 N/C
18.12
19.0 SWITCHBOARD TIER - METERING
19.1 Metering Type Make / Type Part of protection relay
19.2 -Amp Meter Y/N Part of protection relay
19.3 -Volt Meter Y/N Part of protection relay
19.4 -kW, kVAr, kVA Meter Y/N Part of protection relay
19.5 -kW/hr, kVAr/hr, kVA/hr Meter Y/N Part of protection relay
19.6 -Power Factor Y/N Part of protection relay
19.7 -Hours Run Meter Y/N Part of protection relay
19.8 -Frequency Y/N Part of protection relay
19.9 -%THD Y/N Part of protection relay
19.10 -Communication Protocol - Profibus DP - TBC
19.11
20.0 NOTES & ABBREVIATIONS
20.1 1. Supplier to complete all empty fields or where noted as "STS" (Supplier to State)
20.2
20.3 3. Refer 11442-0000-E0710 Clause 8.24 and functionality shown in Single Line Diagram
20.4 4. Fortress key interlock , 2 out of 3 operation for switchboard
20.5
20.6
20.7
20.8
20.9 Abbreviations
20.10 NA = Not Applicable
20.11 STS = Supplier to State
20.12 TBC = To be Confirmed
20.13
20.14