Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0
Document Control
SIGN OFF
Name (Role) Signature Date
DOCUMENT CONTROL
Document
DMS document refer added here
Number
Schedule of Requirements for Surge Arrester for Solar Farms, Wind Farms, and Battery
Document Title
Energy Storage Systems
Rev. Date Description Prepared Checked Approved
[dd mmm yyyy]
1 INTENT OF SPECIFICATION
This specification is intended to cover the design, manufacture, assembly, testing at manufacturer's works, supply
& delivery, properly packed for transport to site of 400 KV Surge Arrester, complete with all materials and
accessories for efficient and trouble-free operation in a manner acceptable to Owner.
In the event of any discrepancy with listed documents, the stipulation of this specification shall govern.
The specification shall be read and construed in conjunction with other sections of bidding document.
2 SCOPE OF WORK
2.1 Scope of Supply
Type, rating, connections, etc. of the equipment shall be as detailed in the drawings and annexures. The
equipment shall be furnished in strict compliance with the same.
2.1.1 Each surge arrester shall be furnished complete with:
a) Fittings and accessories.
b) Auxiliary equipment.
2.1.2 Spares
2.1.3 All relevant drawings, data and instruction manuals.
3 GENERAL REQUIREMENTS
3.1 Codes and Standards
Equipment is to be NG type registered in line with the requirements of:
General Information
3.3 General
3.3.1 Manufacturer's Name and Country of Manufacture By Bidder
3.3.2 Manufacturer's type and Designation By Bidder
3.3.3 Drawing reference(s)
3.3.4 Metal oxide block designation
3.3.5 Guaranteed Design Life
3.3.6 Application Indoor/ Outdoor
Outdoor
3.3.7 Applicable standards Refer to Clause
3.1
3.3.8 Quantity Nos. As per layout
and BOQ
3.3.9 Class and type of Arrester,
Gapless Metal Oxide Yes / No Station class,
Heavy duty
gapless ZnO
type
3.3.10 System Voltage
– Nominal kV 400kV
– Highest kV 420kV
3.3.11 type of System Neutral Earthing Solidly earthed
3.3.12 Short Circuit Current at Arrester Location kA 63
3.3.13 Maximum Duration of Earth Fault Sec. 1
3.3.14 Impulse Withstand Voltage Value of Equipment to be
Protected:
A) High current short duration kV (peak) By Bidder
B) Low current long duration kV (peak) By Bidder
3.3.15 Rated Frequency Hz 50
3.3.16 Coefficient of Earthing 0.8
A) COV mA 2
B) 1.1 COV mA 3
C) COV at 150 °C mA 15
3.5.12 Low current long duration (2000 micro sec) A (peak) 800
3.5.19 Height upto top of terminal pad from mounting plane mm By Bidder
A) Type Hollow
B) Applicable standard IEC 61462:2023
C) Impulse voltage withstand test voltage of kV (peak) 1425
housing with 1.2/50 micro sec. Wave (kVp)
D) One minute power frequency withstand voltage of kV (rms) 630
arrester housing dry & wet kV
Confirm whether equipment type tested with offered type Yes / No Yes
of ZnO block
3.5.34 No. of units /arrester By Bidder
nitrogen %
3.6.4.2
oxygen %
3.6.4.3
sulphur hexafluoride %
3.6.4.4
others – specify %
3.6.4.5
Maximum kPa
3.6.5.2
maximum kPa
3.6.6.2
4 TECHNICAL COMPLIANCE
The attached appendix ‘A’ technical compliance check sheet is to be provided as part of the clarified quotation.
Yes No
Yes No
Yes No
Yes (____________) No
Technical leaflets on equipment explaining construction features, principle of operation, special features etc.
Assembly drawing for erection at site with part numbers and schedule of materials.
Any other relevant drawing or data necessary for satisfactory installation, operation and maintenance.
The manual shall clearly indicate method of installation, check ups and tests to be carried out before
commissioning of the equipment.
8 LIST OF SUPPLIERS
9 SCHEDULE A
GENERAL DETAILS
1.1 Manufacturer
Manufacturer's address
TECHNICAL DETAILS
2.7 Energy Input Capacity (using MCOV in 2.2) for Complete Arrester kJ/kV
Minimum o
C
GENERAL DETAILS
Maximum o
C
10 kA kVpk
20 kA kVpk
1 kA kVpk
5 kA kVpk
10 kA kVpk
20 kA kVpk
40 kA kVpk
65 kA kVpk
100 kA kVpk
1 kA kVpk
2 kA kVpk
3 kA kVpk
GENERAL DETAILS
see note
at 10oC mApk
1
at 20oC mApk
at 30oC mApk
Minimum kVrms
Maximum kVrms
Minimum Temporary Over Voltage Withstand Capability (Duration)
2.18 with 40oC Ambient and Zero Preload and Followed by Rated System
Voltage (1 pu)
at 1.4 pu s
at 1.5 pu s
at 1.6 pu s
at 1.5 pu s
at 1.6 pu s
at -20oC kVdc
at 0oC kVdc
at 20oC kVdc
at 40oC kVdc
at -20oC kVdc
GENERAL DETAILS
at 0oC kVdc
at 20oC kVdc
at 40oC kVdc
Direct Current Level for HVDC Commissioning Test (D.C. fingerprint)
for which Acceptable Voltage Values Quoted [2.21, 2.22] or
2.23 mA
Reference to Voltage/Current Characteristic Showing Maximum and
Minimum Values
2.24 Voltage across Most Highly Stressed block at 20oC
minimum mm
maximum mm
GENERAL DETAILS
air %
nitrogen %
oxygen %
sulphur hexafluoride %
others – specify %
minimum kPa
maximum kPa
minimum kPa
maximum kPa
Maximum condensation temperature of gas at maximum filling
3.17 o
C
pressure
minimum No.
maximum No.
minimum No.
maximum No.
Materials used (if any) to locate blocks and/or spacers radially
4.4 type
within the housing
GENERAL DETAILS
minimum No.
maximum No.
minimum pF
maximum pF
minimum kg
maximum kg
minimum kJ/oC
maximum kJ/oC
minimum kVrms
GENERAL DETAILS
maximum kVrms
minimum kVrms
maximum kVrms
minimum kV
maximum kV
total kg
GENERAL DETAILS
10 SCHEDULE B
SCHEDULE OF TYPE TESTS (METAL OXIDE SURGE ARRESTER (AIS & GIS)
Product Description
Product Type