Schedule of Requirements

Surge Arrester
DOCUMENT REFERENCE: XXXXXXXXXXX
Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Document Control
SIGN OFF
Name (Role) Signature Date

DOCUMENT CONTROL

Document
DMS document refer added here
Number

Schedule of Requirements for Surge Arrester for Solar Farms, Wind Farms, and Battery
Document Title
Energy Storage Systems
Rev. Date Description Prepared Checked Approved
[dd mmm yyyy]

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 2 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

1 INTENT OF SPECIFICATION
This specification is intended to cover the design, manufacture, assembly, testing at manufacturer's works, supply
& delivery, properly packed for transport to site of 400 KV Surge Arrester, complete with all materials and
accessories for efficient and trouble-free operation in a manner acceptable to Owner.
In the event of any discrepancy with listed documents, the stipulation of this specification shall govern.
The specification shall be read and construed in conjunction with other sections of bidding document.

2 SCOPE OF WORK
2.1 Scope of Supply
Type, rating, connections, etc. of the equipment shall be as detailed in the drawings and annexures. The
equipment shall be furnished in strict compliance with the same.
2.1.1 Each surge arrester shall be furnished complete with:
a) Fittings and accessories.

b) Auxiliary equipment.

c) First filling of SF6 gas plus 20% spare.

2.1.2 Spares
2.1.3 All relevant drawings, data and instruction manuals.

3 GENERAL REQUIREMENTS
3.1 Codes and Standards
Equipment is to be NG type registered in line with the requirements of:

NG Specifications / Title Date / Issue


Policies
TS 1 Ratings & Requirements for Plant Issue 7
TS 2.01 Substations Issue 5 and
Addendum
TS 2.02 Switchgear Issue 5
nnnnn Surge Arrester Issue 5
(All associated standards within these documents are to be taken into consideration)

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 3 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

3.2 General Details

Capacitor Voltage Transformer UNIT DATA


EDF Required Offered

General Information

3.3 General
3.3.1 Manufacturer's Name and Country of Manufacture By Bidder
3.3.2 Manufacturer's type and Designation By Bidder
3.3.3 Drawing reference(s)
3.3.4 Metal oxide block designation
3.3.5 Guaranteed Design Life
3.3.6 Application Indoor/ Outdoor
Outdoor
3.3.7 Applicable standards Refer to Clause
3.1
3.3.8 Quantity Nos. As per layout
and BOQ
3.3.9 Class and type of Arrester,
Gapless Metal Oxide Yes / No Station class,
Heavy duty
gapless ZnO
type
3.3.10 System Voltage
– Nominal kV 400kV
– Highest kV 420kV
3.3.11 type of System Neutral Earthing Solidly earthed
3.3.12 Short Circuit Current at Arrester Location kA 63
3.3.13 Maximum Duration of Earth Fault Sec. 1
3.3.14 Impulse Withstand Voltage Value of Equipment to be
Protected:
A) High current short duration kV (peak) By Bidder
B) Low current long duration kV (peak) By Bidder
3.3.15 Rated Frequency Hz 50
3.3.16 Coefficient of Earthing 0.8

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 4 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Capacitor Voltage Transformer UNIT


EDF Required Offered
3.3.17 Temperature Limits As per relevant
standards
3.3.18 Seismic Requirements By EDF
3.3.19 Wind Velocity By EDF
3.3.20 Variation In Frequency By EDF
3.3.21 Altitude Meters By EDF
3.3.22 Is Altitude Correction Factor Applicable Yes / No No.

3.4 Rated Values


3.4.1 Rated Arrester Voltage kV 390
Continuous Operating Voltage at design ambient kV 303
temperature (-15 to 45 °C)
3.4.2 Nominal Discharge Current kA 20kA
3.4.3 Impulse withstand current kA
3.4.4 Maximum operating current (Capacitive current) at 20 °C
at nominal system voltage (76, 159 or 231 kV rms) mArms
at rated system voltage (84, 173 or 242 kV rms) mArms
at continuous operating voltage mArms
at rated voltage mArms
3.4.5 Maximum Operating Current (Resistive current Peak) at
Nominal System Voltage
at 20 °C mApk
at 40 °C mApk
3.4.6 Maximum Residual Voltage for,
Lightning Cur. Impulse at Nominal Discharge Cur. kV (peak) 900kVp
Switching Current Impulse kV (peak) By Bidder
3.4.7 Minimum Residual Voltage at Nominal Discharge Cur. kV (peak)
Switching Current Impulse kV (peak)
3.4.8 Pressure Relief Class
(Short Circuit Capability) 63 kA

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 5 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Capacitor Voltage Transformer UNIT


EDF Required Offered

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 6 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

3.4.9 Long Duration Discharge Class


(Applicable Only for Heavy Duty Arrestors of 10kA or Class-4
Above)
3.4.10 Energy absorption capability per operation of the arrester, kJ 1170
during a switching surge discharge
3.4.11 Maximum amount of energy that may be despatched into kJ 2360
the arrester during discharge assuming heat discharge takes
place within 1 min. period and state the switching surge
current
3.4.12 Reference Current mA By Bidder

3.4.13 Reference Voltage kV By Bidder

3.4.14 Maximum internal leakage current at:

A) COV mA 2
B) 1.1 COV mA 3
C) COV at 150 °C mA 15

3.5 Arrester Housing


3.5.1 Material of Housing Porcelain
3.5.2 Nominal Creepage Distance mm 25mm/kV
3.5.3 Total Creepage Distance of whole arrester housing mm By Bidder
3.5.4 Suitability for Live Washing Yes/No Yes
3.5.5 Level of Pollution Lightly polluted
3.5.6 Minimum Bursting Pressure kPa
3.5.7 Minimum discharge capability kJ/kV min. 8
referred to rated voltage at minimum of
discharge characteristic
3.5.8 Maximum Residual Voltage at
A) 5kA Nominal Discharge Current kV (peak) By Bidder

B) 10kA Nominal Discharge Current kV (peak) 900

C) 20kA Nominal Discharge Current kV (peak) 975

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 7 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Capacitor Voltage Transformer UNIT


EDF Required Offered

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 8 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

D) Steep fronted wave residual voltage at 10 kA kV (peak) 1050


E) Steep fronted wave residual voltage at 1 kA kV (peak) By Bidder
F) V-I Curve attached Yes / No To be attached
by Bidder
3.5.9 Maximum Value of Temporary Over-Voltages and Their kV (peak), By Bidder
Durations Sec.
3.5.10 Dynamic overvoltage withstand:

A) For 3 peaks kV (peak) 705


B) For 0.01 sec. kV (peak) 725
C) For 0.1 sec. kV (peak) 580
D) For 1 sec. kV (peak) 565
E) For 10 sec. kV (peak) 537
3.5.11 High current long duration (4/10 micro sec. Wave) kA (peak) 100

3.5.12 Low current long duration (2000 micro sec) A (peak) 800

3.5.13 Range of Milli ammeter Provided for Leakage Current mA By Bidder


Measurement
3.5.14 Recommended Clearances

A) Phase to Phase mm 4200

B) Phase to Earth mm 3500

3.5.15 Maximum Permissible Lengths of Lead between Arrester, mtr. By Bidder


Discharge Counter and Earth
3.5.16 Size of The Above Lead Sq.mm By Bidder

3.5.17 Rated Voltage of Insulation of Lead kV As per relevant


standards
3.5.18 Total Height of the Arrester mm By Bidder

3.5.19 Height upto top of terminal pad from mounting plane mm By Bidder

3.5.20 Material of terminal pad By Bidder

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 9 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

3.5.21 Total Weight of the Arrester Kg By Bidder

3.5.22 Mounting dimensions and diameter of mounting holes By Bidder

3.5.23 Size of terminal pad By Bidder.

3.5.24 Diameter of insulator mm By Bidder)

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 10 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Capacitor Voltage Transformer UNIT


EDF Required Offered

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 11 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

3.5.25 RIV A 267 kV rms By Bidder

3.5.26 Minimum prospective symmetrical fault current By bidder

3.5.27 Partial discharge at: 1.05 continuous operating voltage

3.5.28 1.05 continuous operating voltage pC Less than 50

3.5.29 1.0 continuous operating voltage pC Less than 50

3.5.30 ZnO block details By bidder

3.5.31 Height / Thickness of ZnO discs mm By bidder

3.5.32 Diameter of ZnO disc mm By bidder

3.5.33 External insulation

A) Type Hollow
B) Applicable standard IEC 61462:2023
C) Impulse voltage withstand test voltage of kV (peak) 1425
housing with 1.2/50 micro sec. Wave (kVp)
D) One minute power frequency withstand voltage of kV (rms) 630
arrester housing dry & wet kV
Confirm whether equipment type tested with offered type Yes / No Yes
of ZnO block
3.5.34 No. of units /arrester By Bidder

3.6 Additional Requirements


3.6.1 Cantilever Strength Kg 500
3.6.2 Maximum Radio Interference Voltage (for 132 kV and µV less than 500µV
Above)
3.6.3 Type of Mounting Pedestal
3.6.4 Filling gas or gas mixture:
air %
3.6.4.1

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 12 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

nitrogen %
3.6.4.2

oxygen %
3.6.4.3

sulphur hexafluoride %
3.6.4.4

others – specify %
3.6.4.5

3.6.5 Gas pressure at 10 oC

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 13 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Capacitor Voltage Transformer UNIT


EDF Required Offered
minimum kPa
3.6.5.1

Maximum kPa
3.6.5.2

3.6.6 Gas pressure at 40 oC


minimum kPa
3.6.6.1

maximum kPa
3.6.6.2

3.6.7 Maximum condensation temperature of gas at maximum o


C
filling pressure
3.6.8 Whether Insulating Base Required Yes/No Yes
3.6.9 Accessories Required
A) Discharge Counter Yes/No Yes to be
provided by
bidder
B) Grading Ring Yes/No Yes to be
provided by
bidder
C) Clamps and Connectors Yes/No Yes to be
provided by
bidder
D) Leakage Current Meter Yes/No Yes to be
provided by
bidder
E) Earth Lead Disconnector Yes/No Yes to be
provided by
bidder
F) Complete Set of Gaskets Yes/No Yes to be
provided by
bidder

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 14 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Capacitor Voltage Transformer UNIT


EDF Required Offered
G) Insulating Base Yes/No Yes to be
provided by
bidder
H) Insulated Connecting Lead between Arrester and Yes/No Yes to be
Discharge Counter provided by
bidder
3.6.10 Purchaser's Conductor Sizes Refer relevant
layout
A) Line Side mm High ampacity
conductor
B) Earth Side mm 75 x 10 GI
3.6.11 Visual Discharge Voltage kV By Bidder

3.6.12 Pressure Relief Valve YES/NO Yes to be


provided by
bidder
3.6.13 Whether Drawings/Data As Specified Enclosed Yes/No Yes to be
provided by
bidder
Whether Power Frequency Voltage Vs Time Yes/No Yes to be
Characteristics Enclosed provided by
bidder
Factory Acceptance Test – Routine Tests As per NGTS
According to to IEC 60099-4 and accompanying specification
Factory Acceptance Test – Type Tests As per NGTS
According to IEC 60099-4 standard and accompanying
specification
Factory Acceptance Test – Special Tests As per NGTS
According to IEC 60099-4 and accompanying specification

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 15 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

4 TECHNICAL COMPLIANCE
The attached appendix ‘A’ technical compliance check sheet is to be provided as part of the clarified quotation.

Appendix ‘A’ Technical compliance

Fully complying with this Technical specification requirements

Yes No

Fully complying with relevant NG specifications mentioned in section 3 above

Yes No

Documents including revisions are as listed in Clause 5 and 6:

Yes No

Equipment type registered:

Yes (____________) No

If ‘No’ please provide the details below in brief:

Table for Deviations.

Clause Equipment Deviation

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 16 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

5 TO BE SUBMITTED WITH THE BID


 Typical general arrangement drawings of the equipment.

 Technical leaflets on equipment explaining construction features, principle of operation, special features etc.

 Type test certificate on similar equipment.

6 TO BE SUBMITTED FOR APPROVAL AND DISTRIBUTION


 Technical Data and Type Test evidence (Schedule A and B) Refer to Annexure A and B

 Dimensional general arrangement drawing showing disposition of various fittings.

 Transport/shipping dimensions with weights.

 Foundation plan and loading.

 Assembly drawing for erection at site with part numbers and schedule of materials.

 Control schematic and wiring diagram.

 Any other relevant drawing or data necessary for satisfactory installation, operation and maintenance.

 Instruction manuals on surge arrester and its accessories.

 The manual shall clearly indicate method of installation, check ups and tests to be carried out before
commissioning of the equipment.

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 17 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

7 SCHEDULE OF RECOMMENDED SPARES

Sl. No. Description Quantity

1 360kV LA complete with accessories & Counter 6 nos.

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 18 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

8 LIST OF SUPPLIERS

Sl. No. Description

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 19 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

9 SCHEDULE A

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 20 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

SCHEDULE OF GENERAL AND TECHNICAL DETAILS (SURGE ARRESTERS)

GENERAL DETAILS

1.1 Manufacturer

Manufacturer's address

1.2 Surge arrester type designation

1.3 Drawing reference(s)

1.4 Metal oxide block designation

1.5 Enclosure type (porcelain/polymeric/GIS)

1.6 Guaranteed Design Life

TECHNICAL DETAILS

Section 2 Surge Arrester Electrical Performance Characteristics

No. DESCRIPTION UNIT VALUE

2 Nominal system voltage kVrms

2.1 Rated Voltage kVrms

2.2 Maximum Continuous Operating Voltage kVrms

2.3 Nominal Discharge Current kA

2.4 Thermal Energy Rating W

Repetitive Charge Transfer rating J

Preheat Temp. for Operating Duty Test o


C 60

2.5 Impulse withstand current kA

2.6 Short Circuit Capability to IEC Recommendation 60099-4

For 0.2s Fault Duration kArms

For 1.0s Fault Duration kArms

2.7 Energy Input Capacity (using MCOV in 2.2) for Complete Arrester kJ/kV

2.8 Arrester Temperature Rise due to MCOV energy input (2.7)

Minimum o
C

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 21 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

GENERAL DETAILS

Maximum o
C

2.9 Maximum Recommended Arrester Temperature before 2.7 o


C

2.1 Maximum Steep Current Impulse Residual Voltage

10 kA kVpk

20 kA kVpk

2.11 Maximum Lighting Impulse Residual Voltage at routine test level

1 kA kVpk

5 kA kVpk

10 kA kVpk

20 kA kVpk

40 kA kVpk

65 kA kVpk

100 kA kVpk

2.12 Maximum Switching Current Impulse Residual Voltage at

1 kA kVpk

2 kA kVpk

3 kA kVpk

2.13 Maximum Operating Current (Capacitive current) at 20oC


see Note
at nominal system voltage (76, 159 or 231 kV rms) mArms
1
at rated system voltage (84, 173 or 242 kV rms) mArms

at continuous operating voltage [2.2] mArms

at rated voltage [2.1] mArms


Maximum Operating Current (Resistive current Peak) at Nominal
2.14
System Voltage
see note
at 20oC mApk
1
at 40oC mApk
Maximum Operating Current (Resistive current Peak) at Continuous
2.15
Operating Voltage [2.2]

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 22 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

GENERAL DETAILS
see note
at 10oC mApk
1
at 20oC mApk

at 30oC mApk

2.16 Reference Current mApk

2.17 Reference Voltage

Minimum kVrms

Maximum kVrms
Minimum Temporary Over Voltage Withstand Capability (Duration)
2.18 with 40oC Ambient and Zero Preload and Followed by Rated System
Voltage (1 pu)
at 1.4 pu s

at 1.5 pu s

at 1.6 pu s

at rated voltage [2.1] s


Minimum Temporary Overvoltage Withstand Capability (Duration)
2.19 with 40oC Ambient and Rated Energy Input Capacity [2.7] Pre-load
Followed by Rated System Voltage
at 1.4 pu s

at 1.5 pu s

at 1.6 pu s

at rated voltage [2.1] s


2.20 see Maximum Radio Interference Voltage at 1 MHz Across 300° at
µV
Note 2 Rated System Voltage
2.21 Maximum Voltage acceptable on Test with Direct Current [2.23]

at -20oC kVdc

at 0oC kVdc

at 20oC kVdc

at 40oC kVdc

2.22 Minimum Voltage acceptable on Test with Direct Current [2.23]

at -20oC kVdc

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 23 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

GENERAL DETAILS

at 0oC kVdc

at 20oC kVdc

at 40oC kVdc
Direct Current Level for HVDC Commissioning Test (D.C. fingerprint)
for which Acceptable Voltage Values Quoted [2.21, 2.22] or
2.23 mA
Reference to Voltage/Current Characteristic Showing Maximum and
Minimum Values
2.24 Voltage across Most Highly Stressed block at 20oC

at nominal system voltage (76, 159 or 231 kV rms) kVrms

at rated system voltage (84, 173 or 242 kV rms) kVrms

at continuous operating voltage [2.2] kVrms

at rated voltage [2.1] kVrms

Section 3 Arrester Enclosure

No. DESCRIPTION UNIT VALUE


Enclosure (porcelain, polymeric, integrated-polymeric or metal-
3.1 type
enclosed)
3.2 Number of Units num

3.3 IEC designated pollution class num

3.4 Total Creepage Length mm

3.5 90o Protected Creepage Length mm

3.6 Internal Diameter (Nominal) mm

3.7 Reference to Shed Profile Drawing ref

3.8 Enclosure Length per Unit

minimum mm

maximum mm

3.9 Minimum Impulse (1.2/50µs) Breakdown Voltage kVpk

3.1 Minimum Wet or Dry Power Frequency Breakdown Voltage kVpk

3.11 Minimum Bursting Pressure kPa

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 24 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

GENERAL DETAILS

3.12 Reference to sealing, pressure relief arrangement if equipped ref

3.13 Maximum pressure for operation of pressure relief kPa

3.14 Filling gas or gas mixture

air %

nitrogen %

oxygen %

sulphur hexafluoride %

others – specify %

3.15 Gas pressure at 10oC

minimum kPa

maximum kPa

3.16 Gas pressure at 40oC

minimum kPa

maximum kPa
Maximum condensation temperature of gas at maximum filling
3.17 o
C
pressure

Section 4 Internal Construction

No. DESCRIPTION UNIT VALUE

4.1 Number of parallel block columns per unit No.

4.2 Number of blocks per column per unit

minimum No.

maximum No.

4.3 Number of blocks per complete arrester

minimum No.

maximum No.
Materials used (if any) to locate blocks and/or spacers radially
4.4 type
within the housing

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 25 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

GENERAL DETAILS

4.5 Method of applying contact pressure between blocks type

4.6 Number of grading capacitors (if any) per blocks

minimum No.

maximum No.

4.7 Capacitance value per capacitor

minimum pF

maximum pF

4.8 Reference to drawing showing internal construction ref

Section 5 Metal Oxide Blocks

No. DESCRIPTION UNIT VALUE

5.1 Type designation of blocks ref

5.2 Outside diameter mm

5.3 Internal diameter where applicable mm

5.4 Height per block mm

5.5 Mass per block

minimum kg

maximum kg

5.6 Heat capacity per arrester

minimum kJ/oC

maximum kJ/oC

5.7 Designation of block material type

5.8 Material of contact surfaces type

5.9 Material of outside coating (s) type

5.1 Rated voltage per block

minimum kVrms

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 26 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

GENERAL DETAILS

maximum kVrms

5.11 Reference voltage per block

minimum kVrms

maximum kVrms

5.12 Reference current for [5.13] mApk

5.13 Residual voltage per block at nominal discharge current [2.3]

minimum kV

maximum kV

5.14 Reference to block routine tests ref

Section 6 Complete Arrester Assembly

No. DESCRIPTION UNIT VALUE


Reference to drawing of complete arrester assembly including
6.1 ref
external grading ring, line and earth terminals and insulating base
6.2 Overall height mm

6.3 Grading ring

Outside diameter of external grading ring mm


Reference to drawing showing dimension and arrangement of
ref
grading ring
Minimum clearance distance from top of arrester/bottom of
6.4 mm
grading ring to metal of arrester at earthed potential
6.5 Arrester mass

total kg

per unit minimum kg

per unit maximum kg


Cantilever strength of completely assembled arrester in vertical
6.6
position (had applied at HV terminal)
with zero wind speed kN

with 46 m/s wind and 13mm thick coating of ice kN

6.7 Reference to Erection Instructions ref

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 27 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

GENERAL DETAILS

6.8 Reference to Operation and Maintenance Procedures ref

Section 7 Arrester Accessories

No. DESCRIPTION UNIT VALUE

7.1 Type designation of surge counter ref

7.2 Counter trigger level A

7.3 Reference to surge counter characteristics ref

7.4 Outline drawing of surge counter ref

7.5 Type designation of operating current indicator ref

7.6 Reference to current indicator characteristics ref

7.7 Outline drawing of indicator ref

7.8 Type designation of insulating base type

7.9 Reference of insulating base drawing ref


Current values should be those obtained with the enclosure clean and dry (where relevant). The
Note 1
temperature given is that of the arrester metal oxide blocks in each case.
Note 2 With arrester housing clean and dry (where relevant)
The breakdown voltage should apply to external or internal breakdown (including all components except the
Note 3
blocks) whichever is the lower

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 28 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

10 SCHEDULE B

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 29 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

SCHEDULE OF TYPE TESTS (METAL OXIDE SURGE ARRESTER (AIS & GIS)

Product Description

Product Type

Test Reference Test Test Date Compliance (Yes, No, N/A)


NGT TS/IEC Report No.
Item (1) Procedure Witness
(2) (3)
Insulation withstand tests on the IEC 60099-4
arrester housing
Residual voltage tests IEC 60099-4

Test to verify long term stability IEC 60099-4


under continuous operating
voltage
Test to verify the repetitive charge IEC 60099-4
transfer rating, Qrs
Heat dissipation behaviour of test IEC 60099-4
sample
Operating duty test IEC 60099-4

Power-frequency voltage-versus- IEC 60099-4


time test
Tests of arrester disconnector IEC 60099-4

Short-circuit tests IEC 60099-4

Test of the bending moment IEC 60099-4

Environmental tests IEC 60099-4

Seal leak rate test IEC 60099-4

Radio interference voltage (RIV) IEC 60099-4


test
Test to verify the dielectric IEC 60099-4
withstand of internal components
Test of internal grading IEC 60099-4
components
Current Distribution test for multi- IEC 60099-4
column design
Weather ageing test IEC 60099-4
Test procedure to determine the IEC 60099-4
lightning impulse discharge Annex H
capability
Artificial pollution test with IEC 60099-4
respect to the thermal stress on Annex C
porcelain housed multi-unit
metal-oxide surge arresters
Partial Discharge (Routine as IEC 60099-4
example)

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 30 OF 31


Schedule of Requirements – Surge Arresters for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Test Reference Test Test Compliance (Yes, No, N/A)


NGT TS/IEC Report Date
No. Item (1) Procedure Witness
(2) (3)
Internal arc withstand tes IEC 62271-203
evidence and TS
3.02.014
(1) - Supplier to confirm item tested is identical to the item offered for type registration. Differences should be
identified in the non-conformance schedule
(2) - Suppler to confirm item has been tested in full compliance with the reference test specification. Differences
should be identified in the non-conformance schedule
(3) - Supplier to confirm tests have been independently and competantly witnessed

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 31 OF 31