You are on page 1of 1

OFFSHORE DESIGN FUNCTIONAL SPECIFICATION SPEC NO 4024

FOR
SECTION REV NO. 2

HV METAL CLAD SWITCHGEAR Discipline Electrical


Engineering Services
ISO – 9001:2000 Page 15 of 17

5.12.8 Indicating Lamps

LED type low power consumption indicating lamps with minimum 8 mm diameter size
shall be used. Indicating lamps shall be suitable for the voltage indicated on the data
sheet.

5.13 Accessories

All accessories required for erection/maintenance/operation of the switch board shall be


supplied which shall include but not be limited to the following:

- Levering crank for moving breaker between test and service position
- Spanner wrench for main disconnect contacts.
- Set of test plugs for meters and relays.
- Spring charging handle.
- Trolley for drawing out breaker located in upper/lower tier.
- Test cable with male/female plugs along with test cabinet for
electrically operating breaker outside housing.

6.0 TESTING AND INSPECTION

Company shall have the right to inspect the units at any time during fabrication.
However, twenty days advance notice shall be given by Vendor/Contractor to the
Company to witness the final routine tests at Vendor’s works. As a minimum, inspection
and testing shall be done as per IEC 62271.

The vendor shall, with his quotation, provide copies of certificates to prove that the
equipment and components offered have successfully been tested by a recognized
international testing authority at the specified operating and short circuit duty.
Certificates shall be provided for each type and rating of equipment offered.

Tests shall be finally performed at site in presence of vendor’s specialist after the
completion of external cable connections. Test reports shall be compiled and forwarded
to the Company.

7.0 SPARES

Format No Ref. Proc. No Issue No Rev No Rev. Date


ODS/SOF/004B ODS/SOP/008 to 015 01 01 15/10/2003

You might also like