You are on page 1of 2

VENDOR DRAWING REVIEW CHECKLIST

MV SWITCHBOARD GENERAL ARRANGEMENT


Client/Project; Project no. :

Package/Equipment; Package/equipment Supplier. :

Vendor Drawing Title : Vendor Drawing No and Rev No. :

SL.NO CHECKLIST/DESCRIPTION CHECKS/COMMENTS REMARKS


1.0 GENERAL CHECKS/VERIFICATION
1.1 Drawing title block/format conforms to standard project requirement
1.2 Drawing number and revision number provided. Drawing number, if allotted by client/project is indicated
1.3 Drawing is to scale and the scale is mentioned on the drawing
1.4 Units (Metric/FPS) is followed per the project requirement
1.5 Drawing is legible and the drawing size submitted for review/approval is per VDRL/project requirement
1.6 Other general checks carried out (Specify)

2.0 SPECIFIC CHECKS/VERIFICATION


2.1 Switchboard make/model indicated
2.2 Switchboard overall dimensions indicated (WxDxH)
2.3 Switchboard shipping sections identified and shipping section overall dimensions (WxDxH) indicated
2.4 Switchboard total weight and shipping section weight indicated
2.5 Switchboard shipping section lifting arrangement (Removable eye bolts) indicated
2.6 Switchboard foundation plan and switchboard mounting details provided
2.7 Switchboard cooling type indicated and is in accordance with specification/datasheet
Switchboard enclosure protection class (IP Class per IEC std or NEMA Class per NEMA/IEEE std) indicated and
2.8
conforms to specification/datasheet
2.9 Switchboard insulation (Air insulated, Gas insulated) indicated
2.10 Switchboard design fully drawout/fixed execution as per specification/datasheet indicated
2.11 Switchboard rating (Rated/nominal Voltage, Phases/wire, frequency and short time rated current) indicated
2.12 Switchboard line-up and number of panels/starters/modules conform to single line diagram
2.13 Switchboard panels/starters/modules service designation/tag number indicated per single line diagram
General arrangement/cross sectional details of individual/typical panel assembly and door mounted components details
2.14
provided and conforms to specification/datasheet/SLD
2.15 Switchboard/panel BOM with components make/type/rating provided
2.16 Circuit breaker type /model in individual panel or switchboard line-up/GA indicated
2.17 MV contactor type /model in individual motor starter/feeder panel or switchboard line-up GA indicated
2.18 If specified, Surge Arrester provided and housed in individual breaker/starter panel.
2.19 Surge arrester type/rating provided and conform to specification/datasheet/SLD
2.20 Reduced voltage auto transformer/reactor starter provided for motor starters, where specified
2.21 Auto transformer/reactor rating/details provided and conforms to specification/datasheet/SLD
Reduced voltage soft starter provided for motor starters, where specified and the soft starter type/rating conforms to
2.22
specification/datasheet/SLD
2.23 Switchboard bussing arrangement with spacing between busses indicated.
2.24 Cable entry to switchboard top or bottom indicated and conforms to specification/datasheet
2.25 Cable gland plate details shown for individual panel (undrilled unless specified)
2.26 Appropriate cable gland type and size provided (if specified in vendor's scope) for the cable type/size for each panel
2.27 Cable alley for individual panel provided/shown on the drawing
2.28 Panel space heater for individual panel provided/shown on the drawing and the space heater rating indicated
Switchboard grounding pad/terminal, 2nos on opposite sides of switchboard line-up provided and the terminal size suitable
2.29
for bolting the grounding lug
2.30 Switchboard external/internal colour finish indicated and conforms to specification/datasheet.
2.31 Any other specific checks required per project requirement (Specify)

3.0 SPECIFIC CHECKS/VERIFICATION FOR OFFSHORE FPSO


3.1 If specified, enclosure and components material certified for marine/offshore installation
3.2 Vendor painting/coating details provided or otherwise reference to painting specification indicated
3.3 Switchboard make and type approved by third party certifying authorities (ABS, DNV, etc)

4.0 APPLICABLE REFERENCE DOCUMENTS


4.1 Purchase Specification as issued to vendor
4.2 MV Switchgear specification/ Datasheet attached with purchase specification
4.3 Approved Vendor MV switchgear Datasheet
4.4 Overall/Switchboard SLD
4.5 Other reference document (Specify)

5.0 NOTES (highlight any specific noting/comments on the drawing here)

Reviewer/Engineer Signature;
Rev.0/28.06.2004
Date;

ABB

Rev.0/28.06.2004

You might also like