VENDOR DRAWING REVIEW CHECKLIST

LV SWITCHGEAR/MCC GENERAL ARRANGEMENT


Client/Project; Project no. :

Package/Equipment; Package/equipment Supplier. :

Vendor Drawing Title : Vendor Drawing No and Rev No. :

SL.NO CHECKLIST/DESCRIPTION CHECKS/COMMENTS REMARKS


1.0 GENERAL CHECKS/VERIFICATION
1.1 Drawing title block/format conforms to standard project requirement
1.2 Drawing number and revision number provided. Drawing number, if allotted by client/project is indicated
1.3 Drawing is to scale and the scale is mentioned on the drawing
1.4 Units (Metric/FPS) is followed per the project requirement
1.5 Drawing is legible and the drawing size submitted for review/approval is per VDRL/project requirement
1.6 Other general checks carried out (Specify)

2.0 SPECIFIC CHECKS/VERIFICATION


2.1 Switchgear/MCC make/model indicated
2.2 MCC double or single front construction per specification/datasheet
2.3 Switchgear/MCC overall dimensions indicated (WxDxH)
2.4 Switchgear/MCC shipping sections identified and shipping section overall dimensions (WxDxH) indicated
2.5 Switchgear/MCC total weight and shipping section weight indicated
2.6 Switchgear/MCC shipping section lifting arrangement (Removable eye bolts) indicated
2.7 Switchgear/MCC foundation plan and mounting details provided
Switchgear/MCC enclosure protection class (IP Class per IEC std or NEMA Class per NEMA/IEEE std) indicated and
2.8
conforms to specification/datasheet
2.9 Switchgear/MCC design fully drawout/fixed execution as per specification/datasheet indicated
2.10 Switchgear/MCC rating (Rated/nominal Voltage, Phases/wires, frequency, and rated short time current) indicated
2.11 Switchgear/MCC line-up and number of panels/starters/modules conform to single line diagram
2.12 Switchgear/MCC panels/starters/modules service designation/tag number indicated per single line diagram
General arrangement/cross sectional details of individual/typical breaker panel assembly and door mounted components
2.13
details provided and conforms to specification/datasheet/SLD
Typical motor starters cross sectional/assembly details with door mounted components provided and conforms to
2.14
specification/datasheet/SLD/Typical starter control schematics
2.15 Switchgear breaker panel/MCC motor starter BOM with components make/type/rating provided
2.16 Circuit breaker type /model in individual panel or switchgear/MCC line-up GA indicated
Reduced voltage soft starter provided for motor starters, where specified and the soft starter type/rating conforms to
2.17
specification/datasheet/SLD
2.18 Switchgear/MCC bussing arrangement with spacing between busses indicated.
2.19 If specified, Switchgear/MCC incomer breaker panel GA shows details for busduct termination
Ensure incoming bus phase arrangement and the busduct phase arrangement shown on the GA is correct/matching at
2.20
termination on the switchgear/MCC incomer.
2.21 Cable entry to switchgear/MCC top or bottom indicated and conforms to specification/datasheet
2.22 Cable gland plate details shown for individual vertical panel (undrilled unless specified)
Appropriate cable gland type, size and quantity provided (if specified in vendor's scope) for the cable type/size for each
2.23
panel/starter
2.24 Cable alley for individual panel provided/shown on the drawing
2.25 Panel space heater for individual panel provided/shown on the drawing and the space heater rating indicated
Switchgear/MCC grounding pad/terminal, 2nos on opposite sides of switchboard line-up provided and the terminal size
2.26
suitable for bolting the grounding lug
2.27 Switchgear/MCC external/internal colour finish indicated and conforms to specification/datasheet.
2.28 Any other specific checks required per project requirement (Specify)

3.0 SPECIFIC CHECKS/VERIFICATION FOR OFFSHORE FPSO


3.1 If specified, enclosure and components material certified for marine/offshore installation
3.2 Vendor painting/coating details provided or otherwise reference to painting specification indicated
3.3 Switchgear/MCC make and type approved by third party certifying authorities (ABS, DNV, etc)

4.0 APPLICABLE REFERENCE DOCUMENT


4.1 Purchase Specification as issued to vendor
4.2 LV Switchgear specification/ Datasheet attached with purchase specification
4.3 Approved Vendor LV switchgear Datasheet
4.4 LV Switchgear/MCC Single Line Diagram
4.5 Other reference document (Specify)

5.0 NOTES (highlight any specific noting/comments on the drawing here)

Reviewer/Engineer Signature;