Results:
Size of Busbar: 2 Nos X 75 X 10 Per Phase
Total No's of Busbar: 6 Nos X 75 X 10 for Phase and 1 Nos X 75 X 10 Per Neutral 1
Forces at the head of the Supports or Bus Bar (F) :2.625Kg/mm2
Mechanical strength of the busbars :0.7Kg/mm2
#N/A
Ref: Merlin Gerin design guide
Various Derating Factor
Number of Bus bar Strip per Phase (K1)
No of Bus bar per Phase
e/a
1 2 3
0.05 1 1.63 2.4
0.06 1 1.73 2.45
0.08 1 1.76 2.5
0.1 1 1.8 2.55
0.12 1 1.83 2.6
0.14 1 1.85 2.63
0.16 1 1.87 2.65
0.18 1 1.89 2.68
0.2 1 1.91 2.7
Volume of Enclosure & Ventilation De rating Factor (K6)
cross Section area of Indoors ( Panel is well Indoors ( Panel is Poorly
Outdoor
Busbar/Total Bus bar Area Ventilated) Ventilated)
0% 0.95 0.85 0.65
1% 0.95 0.85 0.65
5% 0.9 0.7 0.6
10% 0.85 0.65 0.5