Professional Documents
Culture Documents
Electrical Power
Electrical power in watt or joule/s delivered to a device is the product of the voltage between the input
terminals and the current entering at the positive input terminal, p = vi. If this product is negative, then the
device is delivering energy to the external circuit. In a DC circuit under steady conditions v and i are
constant, and so is the power. Therefore, power can be determined by simultaneous measurements of
current and voltage.
In an AC circuit with sinusoidal current and voltage, these quantities are constantly changing, and so then
is the power. The voltage and current measured by instruments are only representative values, usually the
rms or effective values, which are the peak values of the sinusoids divided by the square root of two. The
power averaged over a period is no longer simply VI, where V and I are the rms values, but P = VI cos ,
where is the phase difference between the voltage and current waves. The power factor is cos . In an
inductive circuit, the voltage leads the current, while in a capacitive circuit, the current leads the voltage.
If the phase differences are the same, the power factor has the same sign in both cases, so a power factor
is usually quoted as lagging (inductive) or leading (capacitive), where lagging or leading refers to the
relation of the current wave to the voltage wave.
If we express the voltage and current as phasors, v = v(t) = Vej t and i = i(t) = Iej t - , the instantaneous
power must be written as the product of the real parts of these two expressions, which are V cos t and I
cos( t - ). The final result, after using the usual trigonometric identites, is p(t) = (VI/2)cos +
(VI/2)cos(2 t - ). The first term is a constant, while the second term is a sinusoidal variation of double
frequency. The average power is simply given by the constant term, or P = (VI/2)cos , which is just the
product of the rms values times the power factor as defined above.
In terms of the phasors, we also see that P = Re(vi*/2) = Re(v*i/2). Note that the complex conjugate of
one factor appears, there is a division by 2, and the real part is taken.
We cannot measure AC power using simultaneous measurements of rms values of current and voltage. A
special instrument is necessary that takes into account the phase difference, which is called a wattmeter.
Although wattmeters were once a common AC lab instrument, they are not found in current catalogs of
electronics suppliers. You might want one for testing transformers, for example. It is not difficult to build
your own, however!
The Wattmeter
The traditional wattmeter was an electrodynamometer instrument with a rotating potential coil of many
turns and a fixed current coil of a small number of turns. The torque on the moving coil was proportional
to the product of current and voltage, and therefore to the instantaneous power. The inertia of the moving
coil and pointer averaged the torque. Multipliers and shunts could be used as with ordinary voltmeters and
ammeters. The scale had to be calibrated, since the torque depended on the coil position.
A wattmeter can also be made by multiplying signals proportional to the voltage and current, using an
AD633 analog multiplier, and averaging the result with an op-amp integrator. The signals applied to the
633 should be in the range ±10 V. If these are V' = AV and V" = BI, where V is in volts and I is in
amperes, then the output of the 633 will be V'V"/10 = (AB/10)VI, so that AB/10 volts output corresponds
to 1 W. The AD633 is very easy to use, and is ideal for this application. Use a bipolar power supply of at
least ±12V (maximum ±18V).
A test circuit is shown at the
right, which is easily
assembled on a solderless
breadboard. The load to
which the power is to be
measured is represented by
the 1k resistor in series with
a 2 F capacitor (which
cannot be electrolytic, of
course). The voltage is
applied by a transformer.
Since here the voltage is
applied directly to the 633, about 6.3 V rms is the maximum that is allowed. In most cases, a voltage
divider would be used so that the voltage applied to the 633 is less than ±10 V. The transformer is
necessary, especially if the AC supply is the mains supply, for safety as well as so node "a" on one side of
the load can be assumed to be ground. The current sensing resistor is chosen as 100 , and the voltage is
amplified by a factor 10 by the inverting amplifier using an LF411. In general, the sensing resistor and the
gain of the amplifier can be chosen as convenient in any particular case.
The averaging amplifier is an integrator with a low-frequency gain of unity, and a time constant of 0.1 s,
which is satisfactory for 60 Hz. The resistors connected to the noninverting inputs of the op-amps reduce
the effects of bias currents.
On test, the voltage across the load was measured by a voltmeter, from which the power dissipated in the
resistor can be calculated by the usual circuit theory. This quantity was compared with the voltage output
from the circuit, and the agreement was very good. The wattmeter does not have to be calibrated, if
normal component tolerances are acceptable. The power factor in this case is 0.60 leading. The load
current could also be easily measured, which would allow this power factor to be found experimentally,
as P/VI.
It is instructive to look at the signals with an oscilloscope, and to estimate the phase angle independently
(it is -53° for the test load). The output of the 633 is also interesting, where the frequency doubling is
clearly seen.
The circuit can also be tested with direct current. Replace the load with, say, a 4.7k resistor, and apply 8-
10 V. Compare the output voltage with the calculated power. I used a 4.7k load, and 7.66 V, measuring
12.70 mW, which is 1.8% high. The circuit works for any higher frequency than 60 Hz as well as at DC.
For a lower frequency the time constant of the integrator has to be increased. Furthermore, the accuracy
of the circuit does not depend on the waveform; the average power is measured for any waveform.
A Practical Wattmeter
The power indicated by this meter includes the power dissipated in the voltage divider, which is easily
found once the load voltage is known. For 120V, this is 41 mW, which should be subtracted from the
indicated power. This can be measured in the absence of a load other than the voltage divider. Care
should be taken that the meter is not overloaded (voltage inputs to the AD633 exceeded) at low power
factors, when the output voltage may be small, while the currents and voltages are not. It is a peculiarity
of wattmeters that they can be seriously overloaded while still reading low. Remember that the peak
voltage of 120V AC is 170V. Test the wattmeter at DC to verify the calibration.
References
Short-circuit and open-circuit tests of transformers are explained in any text on AC machinery. Usually,
the primary is excited with the secondary shorted, and the secondary is excited with the primary open,
respectively (for a step-down transformer). A Variac is used since the voltage applied is low in either
case. In the open-circuit test, the wattmeter measures the core loss.