2nd DESIGN OF SHORING

Perhitungan Structure Dinding Shoring Box

ϓ Tanah 1.56-1.85 Ton/m3 ==> dipakai terbesar = 1.85 Ton/m3

Sudut Geser ø 11 - 49o dipakai angka Median = 33.5 o

Beban Asumsi pada permukaan 2 Ton/m


Tinggi =3.2 meter

2 Ton/m
Ka = tg2 (45o - ø/2)
= tg2 (45o - 33.5/2)
= 0.29

Tekanan Tanah aktif akibat tanah (Pa1)


Pa2 Pa = H.ϓ .Ka = 3.2m x 1.85 t/m3 x 0.29
= 1.709 t/m2
Pa1
Pa1 = 0.5.H2.ϓ .Ka = 0.5x3.2m2 x 1.85 t/m3 x 0.29
= 2.73 t/m

Tekanan Tanah aktif Beban di atasnya (Pa2)


Pa = q.Ka = 2 x 0.29
= 0.577 t/m2

Pa1 = q.Ka.H = 0.577 x 3.2


= 1.85 t/m

Total Beban = 2.73 + 1.85


= 4.58 t/m = 4,582 Kg/m
45.82 Kg/cm
Grafik Momen

1/8 W x L2 = 1/8 X 4582 x 62


= 20,621 kg m 2,062,100 kgcm

Beam Properties (Metric Beam) Menggunakan Beam yang dilas pelat sebagai tambahan kekuatan penampang
H Beam 150 x 150 x 7 Check Terhadap Lentur
Dicoba H Beam 150 x 150 x 7 ==> Wx = 442.84 cm3
t2 = 15mm
Dipakai 4 Beam ==> 1,771.4 cm3

Fa = M/Wx = 2062100/1771.4
1164 Kg/Cm2 < 1600 Kg/cm2 ==> OK
t1 = 7mm h = 158 mm
Check Terhadap Geser
D = ½.q.L = ½ x 45.82 x 600 =
= 13,747 Kg

Ix = 3463.87 cm4 b = 150 mm Sx = d.½.h.¼.h + (b - d).t.½.(h - t) = 0.7.½.15.8.¼.15.8 + (15 - 0,7).1,5.½.(15.8 - 1,5)


Wx = 443.84 cm3 = 276.03 cm3
τ= DSx / d Ix . 5 =(19,748 x 276.03)/(0.7x3463.87x5)
Weight = 31.5 Kg/m = 313.00 < 812 Kg/cm2 ==> OK

Terhadap Lendutan

ƒ = 5.L2 .M = 5x6002x2062100
48.E.Ix 48x2,1*106 x 3463.87x5

2.13
ƒ > ƒijin = 1/500.L = 1/500 x 600 cm = 1,2 cm (Tidak Aman)
Dipasang stiffener/pengaku pada tengah bentang

5.L2 .M = 5x6002x2062100
ƒ=
48.E.Ix 48x2,1*106 x 3463.87x5

0.53
ƒ < ƒijin = 1/500.L = 1/500 x 600 cm = 1,2 cm (Aman)
Analisa terhadap kolom

Mmax 5,155 KgM

515,524 KgCm

1/8 W x L2 = 1/8 X 4582 x 32


Mmax = 5,155.24 kg m

Dipakai H Beam 250x250x9

Wx = 867
Check Terhadap Lentur
Dicoba H Beam 250x250x9 ==> Wx = 867.0 cm3

t2 = 14mm
Fa = M/Wx = 740,550/867
595 Kg/Cm2 < 1600 Kg/cm2 ==> OK

t1 = 9mm h = 250 mm Check Terhadap Geser


D = ½.q.L = ½ x 45.82 x 300 =
= 6,874 Kg

b = 250 mm Sx = d.½.h.¼.h + (b - d).t.½.(h - t) = 0.9.½.25.¼.25 + (25 - 0.9).1.4.½.(25 - 1,4)


= 660.76 cm3
τ= DSx / d Ix =(6.874 x 660.76)/(0.9x10800)
= 467 < 812 Kg/cm2 ==> OK
Ix = 10800 cm4
Weight 72.4 Kg/m Terhadap Lendutan

5.L2 .M = 5x4002x5115.24
ƒ=
48.E.Ix 48x2,1*106 x 10800

0.00
ƒ < ƒijin = 1/500.L = 1/500 x 400 cm = 0.8 cm (Aman)
Perhitungan Balok antara 2 dinding shoring

Dicoba H Beam 150 x 150 x 7 x 14

rasio kelangsingan batang profil baja.

struktur tekan maka L/r ≤ 200


= 300 / 3.75
= 80.00 < 200 = aman

Check Kekuatan terhadap Beban


ƛ = Lk / iy
= 150/3.75
40.00 Nilai ω untuk fe 360 pada tabel Baja = 1.144

Penentuan nilai beban = N


Akibat beban lintang ==> 27,494.63 Kg

Tegangan pada Baja = (N / A) x ω = (27494.63 / 40.14) * 1,144


784 < 1600 kg/cm2 ==> OK