DESIGN OF CANTILEVER SLAB (BALCONY)

Dused= 170 mm Bar diameter used= 14 mm


and d= 148 mm Cantilever length, L= 1.7 m

LOADING

DEAD LOAD

Weight of 30mm thick terrazo tile= 0.69 KN/m2


Weight of 20mm thick cement screed= 0.46 KN/m2
Weight of RC slab= 4.25 KN/m2
Weight of 20mm thick plastering= 0.46 KN/m2
Total= 5.86 KN/m2
LIVE LOAD
For balcony, live load= qk= 4 KN/m2 (EBCS-1,Table 2.10)
Qk= 2 KN
Weight of the wall at the edge of slab:

Wall used= 20 cm thick HCB wall of height h= 2.88 m

Then, P= 10.7136 KN/m

DL= 5.86 KN/m P= 10.7136 KN


LL= 4 KN/m

Load transfer to supprting beam: DL= 20.68 KN/m


LL= 6.80 KN/m

Maximum design moment at the support= 43.93 KN.m/m

m= M/(fcdbd2)= 0.177
From the general design chart in design aid for EBCS-2,Kz= 0.89

As=Msd/(zfyd)=Msd/(Kzdfyd)= 1275.89 mm2 As,min= 296 mm2

There fore use dia. 14 mm bar c/c 120 mm


check!!!!
DESIGN OF CANTILEVER SLAB (BALCONY)

Dused= 170 mm Bar diamet 14 mm


and d= 148 mm Cantilever 1.7 m

LOADING

DEAD LOAD

Weight of 3 0.69 KN/m2


Weight of 0.46 KN/m2
Weight of 4.25 KN/m2
Weight of 0.46 KN/m2
Total= 5.86 KN/m2
LIVE LOAD
For balconyqk= 4 KN/m2 (EBCS-1,Table 2.10)
Qk= 2 KN
Weight of the wall at the edge of slab:

Wall used= 20 cm thick HCB wall of height h= 2.88 m

Then, P= 10.7136 KN/m

DL= 5.86 KN/m P= 10.7136 KN


LL= 4 KN/m

Load transfer to supprting beam: DL= 20.68 KN/m


LL= 6.80 KN/m

Maximum design moment at the support= 43.93 KN.m/m

m= M/(fcdbd2) 0.177
From the ge 0.89

As=Msd/(zf 1275.89 mm2 As,min= 296 mm2


There fore 14 mm bar c/c 120 mm
check!!!!
DESIGN OF CANTILEVER SLAB (BALCONY)

Dused= 200 mm Bar diameter used= 14 mm


and d= 178 mm Cantilever length, L= 0.8 m

LOADING

DEAD LOAD

Weight of 30mm thick terrazo tile= 0.69 KN/m2


Weight of 20mm thick cement screed= 0.46 KN/m2
Weight of RC slab= 5 KN/m2
Weight of 20mm thick plastering= 0.46 KN/m2
Total= 6.61 KN/m2
LIVE LOAD
For balcony, live load= qk= 4 KN/m2 (EBCS-1,Table 2.10)
Qk= 2 KN
Weight of the wall at the edge of slab:

Wall used= 15 cm thick HCB wall of height h= 3 m

Then, P= 9.06 KN/m

DL= 6.61 KN/m P= 9.06 KN


LL= 4 KN/m

Load transfer to supprting beam: DL= 14.35 KN/m


LL= 3.20 KN/m

Maximum design moment at the support= 14.22 KN.m/m

m= M/(fcdbd2)= 0.040
From the general design chart in design aid for EBCS-2,Kz= 0.97

As=Msd/(zfyd)=Msd/(Kzdfyd)= 315.78 mm2 As,min= 356 mm2


There fore use dia. 14 mm bar c/c 300 mm
check!!!!
DESIGN OF CANTILEVER SLAB (BALCONY)

h h

Dused= 170 mm Bar diameter used= 14 mm


and d= 148 mm Cantilever length, L= 1.7 m

LOADING

DEAD LOAD

Weight of 30mm thick terrazo tile= 0.69 KN/m2


Weight of 20mm thick cement screed= 0.46 KN/m2
Weight of RC slab= 4.25 KN/m2
Weight of 20mm thick plastering= 0.46 KN/m2
Total= 5.86 KN/m2
LIVE LOAD
For balcony, live load= qk= 4 KN/m2 (EBCS-1,Table 2.10)
Qk= 2 KN
Weight of the wall at the edge of slab:

Wall used= 20 cm thick HCB wall of height h= 2.88 m

Then, P= 10.7136 KN/m

DL= 5.86 KN/m P= 10.7136 KN


LL= 4 KN/m

Load transfer to supprting beam: DL= 20.68 KN/m


LL= 6.80 KN/m

Maximum design moment at the support= 43.93 KN.m/m

m= M/(fcdbd2)= 0.177
From the general design chart in design aid for EBCS-2,Kz= 0.89

As=Msd/(zfyd)=Msd/(Kzdfyd)= 1275.89 mm2 As,min= 296 mm2

There fore use dia. 14 mm bar c/c 120 mm


check!!!!
DESIGN OF CANTILEVER SLAB (BALCONY)

Dused= 170 mm Bar diameter used= 14 mm


and d= 148 mm Cantilever length, L= 1.7 m

LOADING

DEAD LOAD

Weight of 30mm thick terrazo tile= 0.69 KN/m2


Weight of 20mm thick cement screed= 0.46 KN/m2
Weight of RC slab= 4.25 KN/m2
Weight of 20mm thick plastering= 0.46 KN/m2
Total= 5.86 KN/m2
LIVE LOAD
For balcony, live load= qk= 4 KN/m2 (EBCS-1,Table 2.10)
Qk= 2 KN
Weight of the wall at the edge of slab:

Wall used= 20 cm thick HCB wall of height h= 2.88 m

Then, P= 10.7136 KN/m

DL= 5.86 KN/m P= 10.7136 KN


LL= 4 KN/m

Load transfer to supprting beam: DL= 20.68 KN/m


LL= 6.80 KN/m

Maximum design moment at the support= 43.93 KN.m/m

m= M/(fcdbd2)= 0.177
From the general design chart in design aid for EBCS-2,Kz= 0.89

As=Msd/(zfyd)=Msd/(Kzdfyd)= 1275.89 mm2 As,min= 296 mm2

There fore use dia. 14 mm bar c/c 120 mm


check!!!!
DESIGN OF CANTILEVER SLAB (BALCONY)

Dused= 170 mm Bar diameter used= 14 mm


and d= 148 mm Cantilever length, L= 1.7 m

LOADING

DEAD LOAD

Weight of 30mm thick terrazo tile= 0.69 KN/m2


Weight of 20mm thick cement screed= 0.46 KN/m2
Weight of RC slab= 4.25 KN/m2
Weight of 20mm thick plastering= 0.46 KN/m2
Total= 5.86 KN/m2
LIVE LOAD
For balcony, live load= qk= 4 KN/m2 (EBCS-1,Table 2.10)
Qk= 2 KN
Weight of the wall at the edge of slab:

Wall used= 20 cm thick HCB wall of height h= 2.88 m

Then, P= 10.7136 KN/m

DL= 5.86 KN/m P= 10.7136 KN


LL= 4 KN/m

Load transfer to supprting beam: DL= 20.68 KN/m


LL= 6.80 KN/m

Maximum design moment at the support= 43.93 KN.m/m

m= M/(fcdbd2)= 0.177
From the general design chart in design aid for EBCS-2,Kz= 0.89

As=Msd/(zfyd)=Msd/(Kzdfyd)= 1275.89 mm2 As,min= 296 mm2

There fore use dia. 14 mm bar c/c 120 mm


check!!!!
DESIGN OF CANTILEVER SLAB (BALCONY)

Dused= 170 mm Bar diameter used= 14 mm


and d= 148 mm Cantilever length, L= 1.7 m

LOADING

DEAD LOAD

Weight of 30mm thick terrazo tile= 0.69 KN/m2


Weight of 20mm thick cement screed= 0.46 KN/m2
Weight of RC slab= 4.25 KN/m2
Weight of 20mm thick plastering= 0.46 KN/m2
Total= 5.86 KN/m2
LIVE LOAD
For balcony, live load= qk= 4 KN/m2 (EBCS-1,Table 2.10)
Qk= 2 KN
Weight of the wall at the edge of slab:

Wall used= 20 cm thick HCB wall of height h= 2.88 m

Then, P= 10.7136 KN/m

DL= 5.86 KN/m P= 10.7136 KN


LL= 4 KN/m

Load transfer to supprting beam: DL= 20.68 KN/m


LL= 6.80 KN/m

Maximum design moment at the support= 43.93 KN.m/m

m= M/(fcdbd2)= 0.177
From the general design chart in design aid for EBCS-2,Kz= 0.89

As=Msd/(zfyd)=Msd/(Kzdfyd)= 1275.89 mm2 As,min= 296 mm2

There fore use dia. 14 mm bar c/c 120 mm


check!!!!
DESIGN OF CANTILEVER SLAB (BALCONY)

Dused= 170 mm Bar diameter used= 14 mm


and d= 148 mm Cantilever length, L= 1.7 m

LOADING

DEAD LOAD

Weight of 30mm thick terrazo tile= 0.69 KN/m2


Weight of 20mm thick cement screed= 0.46 KN/m2
Weight of RC slab= 4.25 KN/m2
Weight of 20mm thick plastering= 0.46 KN/m2
Total= 5.86 KN/m2
LIVE LOAD
For balcony, live load= qk= 4 KN/m2 (EBCS-1,Table 2.10)
Qk= 2 KN
Weight of the wall at the edge of slab:

Wall used= 20 cm thick HCB wall of height h= 2.88 m

Then, P= 10.7136 KN/m

DL= 5.86 KN/m P= 10.7136 KN


LL= 4 KN/m

Load transfer to supprting beam: DL= 20.68 KN/m


LL= 6.80 KN/m

Maximum design moment at the support= 43.93 KN.m/m

m= M/(fcdbd2)= 0.177
From the general design chart in design aid for EBCS-2,Kz= 0.89

As=Msd/(zfyd)=Msd/(Kzdfyd)= 1275.89 mm2 As,min= 296 mm2

There fore use dia. 14 mm bar c/c 120 mm


check!!!!
DESIGN OF CANTILEVER SLAB (BALCONY)

Dused= 170 mm Bar diameter used= 14 mm


and d= 148 mm Cantilever length, L= 1.7 m

LOADING

DEAD LOAD

Weight of 30mm thick terrazo tile= 0.69 KN/m2


Weight of 20mm thick cement screed= 0.46 KN/m2
Weight of RC slab= 4.25 KN/m2
Weight of 20mm thick plastering= 0.46 KN/m2
Total= 5.86 KN/m2
LIVE LOAD
For balcony, live load= qk= 4 KN/m2 (EBCS-1,Table 2.10)
Qk= 2 KN
Weight of the wall at the edge of slab:

Wall used= 20 cm thick HCB wall of height h= 2.88 m

Then, P= 10.7136 KN/m

DL= 5.86 KN/m P= 10.7136 KN


LL= 4 KN/m

Load transfer to supprting beam: DL= 20.68 KN/m


LL= 6.80 KN/m

Maximum design moment at the support= 43.93 KN.m/m

m= M/(fcdbd2)= 0.177
From the general design chart in design aid for EBCS-2,Kz= 0.89

As=Msd/(zfyd)=Msd/(Kzdfyd)= 1275.89 mm2 As,min= 296 mm2

There fore use dia. 14 mm bar c/c 120 mm


check!!!!