Structural Design Report
Content
1.1.0 Introduction
It is proposed to construct 450m3 capacity Intze type water tank of Bandaranaike International Air
Port Development Project Phase 2, Stage 2.This Design Report is prepared to highlight the loading
details analysis with SAP2000 software and structural design calculations of each elements of the
proposed Intz type water tank.
1.2.0 Brief Structural Description
Among the different types of tanks used for water towers “Intze” tank is a very economical type for
reinforced concrete water towers of large capacity, because of its ability to carry part of water load
by direct compressive forces.
Intze tank, a domed cover is provided at top with a cylindrical and conical wall at bottom. A ring
beam will be required to support the domed roof. A ring beam is also provided at the junction of the
cylindrical and conical walls. The conical wall and the tank floor are supported on a ring girder which
is supported on a circular wall.
1.3.0 Computer Programs/Software
Stresses analysis of “Intze” tank is extremely complicated due to many degrees of redundancy.
Therefore structural analyzed was done using SAP 2000 version 14 (Nonlinear Structural analysis
Software).
• Concrete grade C30 will be used for shaft wall (circular wall), intermediate slabs and
foundation works.
2.1.2 Steel
Page 1
Structural Design Report
2.2 Cover
Cover to outer layer of steel
For Walls,Beams and shaft- 40mm
For base slab and footing- 50mm
Page 2
Structural Design Report
Figure No :2.4-1- Basic Dimensions of proposed intz type water tank for BIA
Page 3
Structural Design Report
Page 4
Structural Design Report
From 1, 2, 3, 4 & 5
Net Capacity of the Tank = V1 + V2 −V 3−V4 − V5
= 337.48 + 176 − 12.83 − 12.84 − 33.7 = 454.11m 3
• British Standard 6399: 1996 - Code of practice for loading for concrete structures. Part 1
• British Standard BS 8007: 1987- Design of concrete structures for retaining aqueous liquids
• British Standard BS 8110: 1985- Structural use of concrete
• CP3: Chapter V: Part 2: 1972 - Code of basic data for the design of buildings. Chapter V:
Loading. Part 2: Wind Loads.
Page 5
Structural Design Report
2.2.0 Loads
The loads were calculated in accordance with BS 6399 and CP3 Chapter V-2 (For Wind loads)
The following loads have been considered:
(a). Permanent Loads :
1. Dead Loads
2. Finishes
3. Loads due to steel structures
(b). Water loads:
1. Water weight
2. Water pressure on walls
(c). Live loads
(d).Wind Loads
Page 6
Structural Design Report
3.1.0 Introduction
Analysis was done using SAP 2000 finite element software. Shell thin area element introduced for
the roof dome, frustum cone, circular walls, intermediate slabs and bottom slab. Pin supports were
applied as a support of the structure alone bottom of the supporting circular wall and foundation
design was done separately.
3D Model of the Intze tank is shown in Figure No: 4.1 to 4.6
3.2 Loads
3.2.1 Dead Load
Self-Weight of the structure Calculate automatically using Self Weight multiplier in SAP2000.
Page 7
Structural Design Report
Therefore the envelopes of above instances of load combinations should be considered. The analysis
results for that envelope should be used for design. In order to that, loading patterns should be
defined to cover all the loading configurations that might be applied to the structure.
The load combinations given in BS8110: Part 1 -1985 Table 2.1 applied to this particular design.
Combination 1 (Full condition) : 1.4 Dead +1.6 Live loads+1.4 Water Loads
Combination 2 (Empty) : 1.0 Dead+1.4Wind
Combination 3 (Full condition) : 1.2Dead+1.2Imposed loads 1.2 Water loads+1.2 Wind
Page 8
Structural Design Report
Page 9
Structural Design Report
Page 10
Structural Design Report
Page 11
Structural Design Report
Water Pressure
Page 12
Structural Design Report
Wind Load
Page 13
Structural Design Report
Max hoop Thrust(ULS) = 42 kN/m Max hoop Stress (ULS) = 0. 19N/mm2 (Compressive)
Page 14
Structural Design Report
Figure No :6-3- Meridional Stress thrust and Meridional Stress of Top Dome- Ultimate limit
state
Page 15
Structural Design Report
Figure No :6.5 –Hoop Stress of Cylindrical Wall- Ultimate state & serviceability state
Max Circumferential(hoop) Thrust(ULS) = 510 kN/m Max hoop Stress(ULS) = 1.275 N/mm2
Page 17
Structural Design Report
Max Meridional thrust (ULS) = 600 kN/m MaxMeridional Stress(ULS) = 1.5 N/mm2- Compressive
Figure No :6-8- Meridional Thrust and Meridional Stress of Conical section- Ultimate limit state
Page 18
Structural Design Report
Max hoop Thrust(ULS) = 300 kN/m Max hoop Stress(ULS) = 1.2 N/mm2 Compressive
Figure No :6-10- Hoop Thrust and Hoop Stress of Bottom Spherical Dome - Ultimate limit state
Max Meridional thrust(ULS) = 250 kN/m Max Meridional Stress(ULS) = 1.0 N/mm2-Compressive
Figure No :6-11- Meridional Thrust and Meridional Stress of Bottom Spherical Dome - Ultimate limit
state
Page 19
Structural Design Report
Upper
lantern(walls &
T10 @150 C/C for both
Slabs)& 200mm C30
directionboth layers
intermediate
platforms
Page 20
Structural Design Report
Reinforcement of each elements were calculated for restrict cracking due to both serviceability limit
state-flexural effect (mature concrete) and thermal and moisture effect.
Maximum design surface crack widths “W” in BS8007 for direct tension and flexure or restrained
temperature and moisture effects are as,
W=0.2mm –for severe or very severe exposure.
.
Page 21
9. Annex A- Structural Design Calculation
Page 22
A.1 Design of Top Dome
Rev
450m3 Intz Type Water Tank
Sheet No 01
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for Top Dome
Checked by T.M.C.R
Basic Dimensions
Basic Dimensions
imit State
Serviceability Limit
Page | 1
Rev
450m3 Intz Type Water Tank
Sheet No 02
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for Top Dome
Checked by T.M.C.R
Reinforcement Design of Top Dome
Hoop stress is compressive over the entire domain (except of
edges) and it is less than the meridinal stress.
Hence ,Provide minimum R/ F
100 A
s 0 .4
BS8110
bh
As 0.4 1000 225
Part 1:1985 100
Table3.27 As 900 mm / m 2
Pcrit 0.0035
BS8007
0.0035 10 225
3
Minimum R / F
Cl 2.6.2.3 2
393.75mm per each direction each Zone
2
As 0.00402 10 3 225
2
452.25mm / m 2
T12@200
Consider T12@200 As Prov=566 mm2/m each face
Page | 2
Structural Design for Intz Type Water Tank
Rev
450m3 Intz Type Water Tank
Sheet No 03
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for Top Dome
Checked by T.M.C.R
Apparent Strain ε = TA E
1
s s
ε = 48 × 103
1 (566 × 2) × 225 × 10 3
ε = 1.88 × 10 − 4 mm
1
Both Layers
Page | 3
Structural Design for Intz Type Water Tank
A.2 Design of Top Ring Beam
Rev
450m3 Intz Type Water Tank
Sheet No 04
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for Top Ring Beam
Checked by T.M.C.R
Basic Dimensions
FigureA.1-2:Dimensions
Dimensions of the Top Ring
Beam,b=400mm,h=500mm
,b=400mm,h=500mm
SAP 2000 Outputs
tate
Ultimate Limit State
SAP 2000 Hoop Tension = Horizontal component of meridianal
meridi thrust
Outputs from the dome.
Tuls = Nφ × cos φ × D / 2, φ = 33
Tuls = 60 × cos 33 × 12.5 / 2 = 315kN
imit State
Serviceability Limit
Tsls = Nφ × cos φ × D / 2, φ = 33
Tsls = 48 × cos 33 × 12.5 / 2 = 251kN
Steel Ast = T
0.87 f y
3
Ast = 315 × 10 = 787 mm 2 / m
0.87 × 460
4T16 each
4T 16 − As = 805 mm 2 / m for each layer layer
Page | 4
Rev
450m3 Intz Type Water Tank
Sheet No 05
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for Top Ring Beam
Checked by T.M.C.R
Strain ε = 2bh 3 A E
2
s s
ε = 2 × 400 × 500
2 3 × 200 × 103 × 805
ε = 8.28 × 10 − 4 mm
2
ε = ε −ε
m 1 2
BS8007 ε = 7.22 × 10 − 4 mm
m
Cl B-5
a cr = ( S ) 2 + [C + φ / 2 + φ1 ]2 − φ / 2
2
S = 140mm
φ = 10mm, C = 40mm Link (φ ) = 10mm
then,
a cr = 83mm
W = 3a cr ε
m
= 3 × 83 × 7.22 × 10 − 4
= 0.18mm < 0.2mm OK .
Hence Crack Width is satisfactory.
Page | 5
Structural Design for Intz Type Water Tank
Rev
450m3 Intz Type Water Tank
Sheet No 06
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for Top Ring Beam
Checked by T.M.C.R
Shear Reinforcement
Table 3.8 0.4bv
Asv
BS 8110-1:1985 Sv 0.87 f y
Consider T 10 @150mm
As 524mm 2 / m
d 500 40 10 16 442mm
2
Sv ( 10 2 ) (0.87 460
2
)
4 0.4 400
Sv 393mm
Sv 0.75d
Sv 331.5mm
T10 @150
PROVIDE T 10 @150mm
W max ( f ct ) ( ) R (T1 T2 )
fb 2
0.2 0.67 ( ) 10 10 6 1 (30 10)
2 2
3.35 10 4
BS 8007
Cl A.3 for 10 3.35 10 3 cnt
for 12 4.02 10 3 cnt
10, As 0.00335 10 3 200 670mm 2 / m
12, As 0.00402 10 3 200 804mm 2 / m
OK
Page | 6
Structural Design for Intz Type Water Tank
A.3 Design of Cylindrical Wall
Rev
450m3 Intz Type Water Tank
Sheet No 07
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for Cylindrical wall
Checked by T.M.C.R
Steel Area As = T
0.87 f y
3
As = 325 × 10
0.87 × 460
As = 812mm 2 / m
T12 @150
Minimum R / F = 0.4 × 300 × 1000 = 1200mm 2 / m
100 Both layer
Pr ovide two layers each have 600 mm 2 / m
PROVIDE T 12 @150 ( Asprov = 754mm 2 / m)
Page | 7
Rev
450m3 Intz Type Water Tank
Sheet No 08
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for Cylindrical wall
Checked by T.M.C.R
Check for Crack width
BS8007 T
1 A E
s s
Cl B-4 3
250 10
1 (754 2) 200 103
8.3 10 4 mm
1
Strain 2bh
2 3A E
s s
2 300 1000
2 3 200 103 754 2
6.63 10 4 mm
2
1.65 10 4 mm S 100mm, acr 66mm
m 1 2
W 3acr 3 66 1.65 10 4 0.03 0.2mm OK
m
Hence OK , Crack Width is satisfactory.
Page | 8
Structural Design for Intz Type Water Tank
A.4 Design of Middle Ring Beam
Rev
450m3 Intz Type Water Tank
Sheet No 09
BIA Development Project
ECL Date
Design Calculations for Middle Ring Made by S.M.A.K
Beam Checked by T.M.C.R
Basic Dimensions
ULS-Hoop
Hoop tension on beam=1.4*449+1.2*115=766.6 kN/m
As for ULS ,
As = T
0.87 f y
3
As = 766.6 × 10 = 1915mm 2 / m 4T25 each
0.87 × 460
PROVIDE 4T 25 ( Asprov = 1960 mm 2 / m) for each face layer
Page | 9
Rev
450m3 Intz Type Water Tank
Sheet No 10
BIA Development Project
ECL Date
Design Calculations for Middle Ring Made by S.M.A.K
Beam Checked by T.M.C.R
Strain ε = 2bh 3 A E
2
s s
ε = 2 × 500 × 750
2 3 × 200 × 10 3 × 1960
ε = 6.37 × 10 − 4 mm
2
ε = ε −ε
m 1 2
BS8007 ε = 7.93 × 10 − 4 mm
m
Cl B-5
a cr = ( S ) 2 + [C + φ / 2 + φ1 ]2 − φ / 2
2
S = 99 mm
φ = 10 mm, C = 40 mm Link (φ ) = 10 mm
then ,
a cr = 74 .7 mm
W = 3a cr ε
m
= 3 × 74.7 × 7.93 × 10 − 4
= 0.18mm < 0.2 mm OK .
Hence Crack Width is satisfacto ry.
Page | 10
Structural Design for Intz Type Water Tank
Rev
450m3 Intz Type Water Tank
Sheet No 11
BIA Development Project
ECL Date
Design Calculations for Middle Ring Made by S.M.A.K
Beam Checked by T.M.C.R
Shear Reinforcement
Shear effect is nominal, provide nominal R/F
Table 3.8 0.4bv
Asv
BS 8110-1:1985 Sv 0.87 f y
Consider T 12 @150mm
As 905mm 2 / m
d 750 40 10 25 687.5mm
2
Sv ( 10 2 ) ( .87 460
2 0 )
4 0.4 500
Sv 453mm
Sv 0.75d
Sv 518mm
T12 @150
PROVIDE T 12 @150mm
W max ( f ct ) ( ) R (T1 T2 )
fb 2
0.2 0.67 ( ) 12 10 6 1 (30 10)
2 2
3.35 10 4
BS 8007
Cl A.3
for 12 4.02 10 3 cnt
As 0.00402 10 3 250
1005mm 2 / m
4T25
Page | 11
Structural Design for Intz Type Water Tank
A.5 Design of Conical Section
Rev
450m3 Intz Type Water Tank
Sheet No 12
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for Conical Section
Checked by T.M.C.R
Basic Dimensions
imit State
Serviceability Limit
Page | 12
Rev
450m3 Intz Type Water Tank
Sheet No 13
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for Conical Section
Checked by T.M.C.R
Reinforcement Design of Conical Section
T
As = uls
130
3
As = 510 × 10
130
2
BS8007 As = 3923 mm / m
Table3.1
2011mm 2 / m for each face
PROVIDE T 16 @ 100, As = 2011mm 2 / m T16@100
Each face
ε = 400 × 103
1 (2011 × 2) × 200 × 103
ε = 4.97 × 10 − 4 mm
1
Strain ε = 2bh 3 A E
2
s s
ε = 2 × 400 × 1000
2 3 × 200 × 103 × 2011 × 2
ε = 3.31 × 10 − 4 mm
2
ε = ε −ε = 1.66 × 10 − 4 mm
m 1 2
Page | 13
Structural Design for Intz Type Water Tank
Rev
450m3 Intz Type Water Tank
Sheet No 14
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for Conical Section
Checked by T.M.C.R
acr (S ) 2 [C / 2 1 ]2 / 2
2
S 100mm
16mm, C 40mm Link( ) 10mm
then,
BS8007 acr 61.31mm
Cl B-5 W 3acr
m
3 61.311.66 10 4
0.0305mm 0.2mm OK.
Hence Crack Width is satisfactory
As 0.00402 10 3 400
2
804mm / m2
T12@200
Consider T12@200 As Prov=566 mm2/m each face
Page | 14
Structural Design for Intz Type Water Tank
A.6 Design of bottom spherical dome
Rev
450m3 Intz Type Water Tank
Sheet No 15
BIA Development Project
ECL Date
Design Calculations for bottom spherical Made by S.M.A.K
dome Checked by T.M.C.R
Basic Dimensions
Page | 15
Rev
450m3 Intz Type Water Tank
Sheet No 16
BIA Development Project
ECL Date
Design Calculations for bottom spherical Made by S.M.A.K
dome Checked by T.M.C.R
Reinforcement Design of bottom Dome
Hoop stress and meridinal stress compressive over the entire
domain.
Hence ,Provide minimum R/ F
100 A T12@200
s 0 .4
bh each
BS8110 As 0.4 1000 250 direction
100
Part 1:1985
As 1000 mm 2 / m bath layers
Table3.27
565mm 2 / m for each face
PROVIDE T 12 @ 200
Reinforcement for shrinkage
Pcrit 0.0035
BS8007
0.0035 10 250
3
Minimum R / F
Cl 2.6.2.3 2
437.5mm per each direction each Zone
2
f
for 12 4.02 10 3 cnt
As 0.00402 10 3 250
2
502.5mm / m 2
Page | 16
Structural Design for Intz Type Water Tank
Rev
450m3 Intz Type Water Tank
Sheet No 17
BIA Development Project
ECL Date
Design Calculations for bottom spherical Made by S.M.A.K
dome Checked by T.M.C.R
ε = 18.1 × 103
1 (566 × 2) × 200 × 10 3
ε = 7.99 × 10 − 5 mm
1
Strain ε = 2bh 3 A E
2
s s
ε = 2 × 250 × 1000
2 3 × 200 × 103 × 566 × 2
ε = 7.36 × 10 − 4 mm
2
ε
= ε −ε Negative value
m 1 2
Hence Uncracked sec tion OK
Page | 17
Structural Design for Intz Type Water Tank
A.7 Design of Bottom Ring Beam
Rev
450m3 Intz Type Water Tank
Sheet No 18
BIA Development Project
ECL Date
Design Calculations for Bottom Ring Made by S.M.A.K
Beam Checked by T.M.C.R
Basic Dimensions
Page | 18
Rev
450m3 Intz Type Water Tank
Sheet No 19
BIA Development Project
ECL
Date
Design Calculations for Bottom Ring Made by S.M.A.K
Beam Checked by T.M.C.R
Apparent Strain ε = TA E
Cl B-4 1
s s
ε = 660 × 10 3
1 2514 × 200 ×10 3
ε = 1.3110 − 3 mm
1
Strain ε = 2bh 3 A E
2
s s
ε = 2 × 500 × 1000
2 3 × 200 × 10 3 × 2514
ε = 6.6 × 10 − 4 mm
2
ε =ε −ε
m 1 2
BS8007 ε = 6.52 × 10 − 4 mm
m
Cl B-5
a cr = ( S ) 2 + [C + φ / 2 + φ1 ] 2 − φ / 2
2
S = 96mm
φ = 2mm, C = 40mm Link (φ ) = 10mm
then,
a cr = 68.7m
W = 3a cr ε
m
= 3 × 68.7 × 6.520 − 4
= 0.134mm < 0.2mm OK .
Hence Crack Width is satisfactory.
Page | 19
Structural Design for Intz Type Water Tank
Rev
450m3 Intz Type Water Tank
Sheet No 20
BIA Development Project
ECL Date
Design Calculations for Bottom Ring Made by S.M.A.K
Beam Checked by T.M.C.R
Shear Reinforcement
Shear effect is nominal, provide nominal R/F
Table 3.8 0.4bv
Asv
BS 8110-1:1985
Sv 0.87 f y
Consider T 12 @ 150mm
As 754mm 2 / m
d 1000 40 10 20 / 2 940mm
Sv ( 12 2 2 ) (0.87 460 )
4 0.4 500
Sv 453mm
Sv 0.75d
Sv 705mm
PROVIDE T 12 @ 150mm T12@150
W max ( f ct ) ( ) R (T1 T2 )
fb 2
0.2 0.67 ( ) 10 10 6 1 (30 10)
2 2
3.35 10 4
BS 8007
Cl A.3
As 0.00402 10 3 500
2
1005mm / m 2
OK
Page | 20
Structural Design for Intz Type Water Tank
A.8 Design of supporting shaft
Rev
450m3 Intz Type Water Tank
Sheet No 21
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for supporting Shaft
Checked by T.M.C.R
Load
SAP 2000 Factored total Weight of the tank (ULS condition) = 15200kN
Outputs Serviceability Limit State
Figure 5.1 Total Weight of the tank (SLS condition) = 11627kN
2 2
SectionalArea = π (r1 − r2 ) = π (3.0 2 − 2.8 2 )
SectionalArea = 3.64m 2
π
Second moment of area = × (6 4 − 5.6 4 )
64
= 15.3m 4
Wind Load
Page | 21
Structural Design for Intz Type Water Tank
Rev
450m3 Intz Type Water Tank
Sheet No 22
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for supporting Shaft
Checked by T.M.C.R
Page | 22
Structural Design for Intz Type Water Tank
Rev
450m3 Intz Type Water Tank
Sheet No 23
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for supporting Shaft
Checked by T.M.C.R
Seismic Force
The design load for seismic effect is taken as,
Dead Load+ weight of Over Head Tank including water+0.25%of Live load
F ( Design Load ) = 9817 kN
W (Weight of shaft ) = 1809kN
Effective equivalent force f = F +W
3
= 10420kN
The lateral deflection at the top of the water tank due to equivalent load
is
V (
= WL
3
3EI
)(
× 1 + 3 × 0.5h
2L
)
L = 18 + 2.61 + 1 + 3.115 / 2 = 23.16m
E = 27GPa
V = 0.105
Natural period of the Tank T = 2π v
g
= 0.65 sec
α h = βIF0 S a g
α h = 1× 1.5 × 0.2 × 0.12 = 0.036
Page | 23
Structural Design for Intz Type Water Tank
Rev
450m3 Intz Type Water Tank
Sheet No 24
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for supporting Shaft
Checked by T.M.C.R
h
[( 2
)]
Mq = α F 18 + 1 + 2.61 + 3.11 + W (18 + 1)
2
Mq = 0.036 × {[9817 × 23.16] + 1809 × 9.5}
Mq = 8803kN
Seismic load condition dominates over the wind condition. The critical
bending moment and shear forces at 1m below the ground
level(neglecting the passive resistance of earth)are,
Mq=9000kNm
Vq =4250kN
P=11627kN
P My
σc = +
A I
σc
11627 9000 ×
=
(
6.0 + 0.2
2
) ×10 −3
+
3 . 64 15 . 3
σc = 5.07 N / mm 2
No Tension is developed in the sec tion.
Page | 24
Structural Design for Intz Type Water Tank
Rev
450m3 Intz Type Water Tank
Sheet No 25
BIA Development Project
ECL Date
Made by S.M.A.K
Design Calculations for supporting Shaft
Checked by T.M.C.R
Vq 425 × 10 3
Average of shear stress = = = 0.12 N / mm 2
A 3.64 ×10 6
This value is far less than t he allowable stress. The nominal
circumferential reinforcement specified earlier is adequate.
Hence,
Provide T12@200
T12@200
Each
layer
Page | 25
Structural Design for Intz Type Water Tank
A.9 Foundation Design of Intz Type Water Tank
f = 25N/mm2
cu
f = 460N/mm2
y
Bearing Capacity
Level.
π × 62 π × 2.82
W = 24 π × 62 × 0.6 + × 0.5625 − × 0.2625
3 3
= 2086kN
Assume Radius of the Circular Raft is R.
The distribution of pressure under the circular footing is given
by,
(P + W) 4Mf
psls = ±
π × R2 π × R3
Where Mf is the moment due to wind loadings. On the other
(P + W)
≥ 140
πR2
(P + W)
R2 ≥
140π
(11613 + 2086)
R2 ≥
140π
R2 ≥ 5.58
Hence Select a Radius of 6m. R=6m
π r2 = π × 4.13752 = 53.78m2
The depth of the footing at Critical Perimeter (h),
0.3
h = 0.6 + × (6 − 4.1375) = 0.775m
(6 − 2.8)
The effective depth of the footing at Critical Perimeter ( d′ )
d′ = 775 − 50 − 25 = 700mm
8527.125 × 103
v= = 0.46N/mm2
700 × 26000
BS 8110- 100As
As per Table 3.8 for a = 0.40 , v c = 0.46
1:1997 bvd
respectively.
For , r < c
r 2 2
Mr =
P
3 − 1 + 22ln R + 1 − C
16π R C R
P
r 2 2
Mθ = − 3 + 22ln R + 1 − C
16π R C R
r 2 2 2
Mr =
P
3 − 1 + 22ln R − C + C
16π R r R r
r 2
P
2 2
R C C
Mr = − 3 + 22ln − − + 2
16π R r R r
The bending moment variation is graphed with a Microsoft
Excel sheet as shown Figure 2.
-200
Bending Moment (kNm)
-300
-400
-500
-600
-700
-800
-900
Distance
M,radial M, cir
k
z = d0.5 + 0.25 −
0.9
0.043
z = d0.5 + 0.25 − = 0.95d
0.9
M 733 × 10 6
As = = = 2336mm2
0.87fy z 0.87 × 460 × 0.95 × 825
100As
However for shear requirements = 0.40
bvd
k
z = d0.5 + 0.25 −
0.9
0.086
z = d0.5 + 0.25 − = 0.89d
0.9
M 596 × 10 6
As = = = 3187mm 2
0.87fy z 0.87 × 460 × 0.89 × 525