Dimensions
Space required for servicing
50 approx. 600 mm
292 + 5 35
Installation width
X
Installation height
A B
Drilling on screws
Seal by others
65
50
2
SelectionTable
Order Example :
Air Volume: 6720 l/s
24000 m3/ h
Installation width: 1961 mm
Installation height : 2588 mm
Mounting bank for 12 aFilter Cells (610 x 610 ax 292 mm)
Mounting Bank
Order Number
Filter Mounting Bank F 262 for Filter Cells 610 x 610 x 150 mm
Filter Mounting Bank F 263 for Filter Cells 610 x 610 x 292 mm
Width in mm 707 1334 1961 2588 3215 3842
Height Filter No. of Horiz. Cells 1 2 3 4 5 6
. . . . . .
in Cell V in V in V in V in V in V in
mm No. of Vert. Cells l/s m3/h l/s m3/h l/s m3/h l/s m3/h l/s m3/h l/s m3/h
F770 K02 / F771 K02 320 1150 640 2300 960 3450 1280 4600 1600 5750 1920 6900
F770 K03 / F771 K03 560 2000 1120 4000 1680 6000 2240 8000 2800 10000 3360 12000
F760 J03 560 2000 1120 4000 1680 6000 2240 8000 2800 10000 3360 12000
707 1 F780 x61 / F781 x 61 830 3000 1660 6000 2490 9000 3320 12000 4150 15000 4980 18000
Total No. of Filter Cells 1 2 3 4 5 6
Weight in kg 5 8 11 14 16 19
Order Number A11 A 12 A 13 A 14 A 15 A 16
F770 K02 / F771 K02 640 2300 1280 4600 1920 6900 2560 9200 3200 11500 3840 13800
F770 K03 / F771 K03 1120 4000 2240 8000 3360 12000 4480 16000 5600 20000 6720 24000
F760 J03 1120 4000 2240 8000 3360 12000 4480 16000 5600 20000 6720 24000
1334 2 F780 x61 / F781 x 61 1660 6000 3320 12000 4980 18000 6640 24000 8300 30000 9960 36000
Total No. of Filter Cells 2 4 6 8 10 12
Weight in kg 8 13 18 23 28 33
Order Number A21 A22 A23 A24 A25 A26
F770 K02 / F771 K02 960 3450 1920 6900 2880 10350 3840 13800 4800 17250 5760 20700
F770 K03 / F771 K03 1680 6000 3360 12000 5040 18000 6720 24000 8400 30000 10080 36000
F760 J03 1680 6000 3360 12000 5040 18000 6720 24000 8400 30000 10080 36000
1961 3 F780 x61 / F781 x 61 2490 9000 4980 18000 7470 27000 9960 36000 12450 45000 14940 54000
Total No. of Filter Cells 3 6 9 12 15 18
Weight in kg 11 18 25 32 39 46
Order Number A31 A32 A33 A34 A35 A36
F770 K02 / F771 K02 1280 4600 2560 9200 3840 13800 5120 18400 6400 23000 7680 27600
F770 K03 / F771 K03 2240 8000 4480 16000 6720 24000 8960 32000 11200 40000 13440 48000
F760 J03 2240 8000 4480 16000 6720 24000 8960 32000 11200 40000 13440 48000
2588 4 F780 x61 / F781 x 61 3320 12000 6640 24000 9960 36000 13280 48000 16600 60000 19920 72000
Total No. of Filter Cells 4 8 12 16 20 24
Weight in kg 14 23 32 41 50 65
Order Number A41 A42 A43 A44 1) A45 1) A46 1)
F770 K02 / F771 K02 1600 5750 3200 11500 4800 17250 6400 23000
F770 K03 / F771 K03 2800 10000 5600 20000 8400 30000 11200 40000
F760 J03 2800 10000 5600 20000 8400 30000 11200 40000
3215 5 F780 x61 / F781 x61 4150 15000 8300 30000 12450 45000 16600 60000
Total No. of Filter Cells 5 10 15 20
Weight in kg 16 28 40 50
Order Number A51 A52 A53 A54 1)
F770 K02 / F771 K02 1920 6900 3840 13800 5760 20700 7680 27600
F770 K03 / F771 K03 3360 12000 6720 24000 10080 36000 13440 48000
F760 J03 3360 12000 6720 24000 10080 36000 13440 48000
3842 6 F780 x61 / F781 x61 4980 18000 9960 36000 14940 54000 19920 72000
Total No. of Filter Cells 6 12 18 24
Weight in kg 20 33 46 65
Order Number A61 A62 A63 A64 1)
3
Installation and use
KSF Filter, With or Without Pre-Filter Housing High Efficiency Terminal Filter Type F 600
Gas-tight filter housing from galvanized steel with suitable Stove enamelled steel housing for universal installation, with
paint finish according to application. Construction includes: secure sealing and clamping device for the particulate filter
– self adjusting clamping device cell. Leak proof test device. Pressure differential measuring
Options: connections. Anodised aluminium or painted steel diffuser
– double grooved service board for contamination-free filter removable for cleaning or decontamination.
change F 600 Terminal Filter also available with airtight flap valve
– leak proof test device for particulate filter cells with automatic closure and airtight to DIN 1946 Part 4.
– two-pack paint system and stainless steel clamping Designed to operate in the event of system shut down or
device. control system failure. Can isolate individual filter from the
Available in three sizes, in single units or combined overall system, and allows smoke filament testing of filter
assembly (see Leaflet KSF Filter”). cell (see leaflet High Ef ficiency Terminal Filters”).
” ”
Ducted Casing for Particulate Filter Cells Filter Module Type F 630 for Clean Rooms with Low
Strong ducted casing in galvanized steel with an internal Turbulence Displacement Ventilation
frame system of aluminium for mounting the filter cells. Side Stove-enamelled robust sheet steel housing with perforated
access door for filter servicing. Apart from standard sizes steel grid on air outlet, connections for monitoring pressure
the ducted casing can be supplied to match specific dif ferential and seal testing of the particulate filter cells.
dimensions (see Leaflet F3/ 5/ EN/ ... Ducted Particulate Designed to fit standard modular ceiling grid sizes and may
”
Filters”). be grouped together to provide localised clean areas.
Ducted Casing for Particulate Filter Cells Filter Module with diffuser for clean rooms with
low turbulence displacement ventilation
4
Filter Data
5
Specification Texts
Specification Texts
Item Qty . Description
Technical Data:
Trox Particulate Filter Cells
Frame is fire resistant moisture proof chipboard Air Volume ................................................................. l/s (m3/ h)
with a neoprene seal on one side. Filter media Dimensions W x H x D ............................................... mm
moisture resistant glass fibrepaper with
Initial Pressure Differential ........................................ Pa
corrugated spacers of aluminium or textile fibres.
The Particulate Filter Cells, type tested to DIN Dust Extraction Efficiency
24184 and individually to Sodium Flame (NaCI)- based on Sodium Flame (NaCI)-Test – DOP 1) ........... %
Test, are packed into special crush-resistant
Particulate Filter Grade based on DIN 24184 ............
cartons.
Order Number ...........................................................
Trox Activated Carbon Filter Cell F760 Make: Trox
Frames in impregnated moisture-resistant chip
board with activated carbon cells in a securely
fixed wedge-shaped arrangement. 1) Dust Extraction Efficiency type tested to Sodium Flame
Filter cells with neoprene seals on one side. (NaCI)-Test approx. conforms to DOP-value.
Price / Each