Project Job no.

N108-NB-WP-CAL
Calcs for Start page no./Revision
1
Calcs by Calcs date Checked by Checked date Approved by Approved date
M 14/11/2019

WIND LOADING (EN1991-1-4)


TEDDS calculation version 3.0.13

12500
60000 200
Plan Elevation
200

Building data
Type of roof; Flat
Length of building; L = 60000 mm
Width of building; W = 200 mm
Height to eaves; H = 12500 mm
Eaves type; Sharp
Total height; h = 12500 mm
Basic values
Fundamental basic wind velocity; vb,0 = 25.0 m/s
Season factor; cseason = 1.00
Direction factor; cdir = 1.00
Shape parameter K; K = 0.2
Exponent n; n = 0.5
Probability factor; cprob = [(1 - K  ln(-ln(1-p)))/(1 - K  ln(-ln(0.98)))]n = 1.00
Basic wind velocity (Exp. 4.1); vb = cdir  cseason  vb,0  cprob = 25.0 m/s
Reference mean velocity pressure; qb = 0.5    vb2 = 0.391 kN/m2

Orography
Orography factor not significant; co = 1.0
Terrain category; II
Displacement height (sheltering effect excluded); hdis = 0mm
The velocity pressure for the windward face of the building with a 0 degree wind is to be considered as 1 part as
the height h is less than b (cl.7.2.2)
The velocity pressure for the windward face of the building with a 90 degree wind is to be considered as 3 parts as
the height h is greater than 2b (cl.7.2.2)
Peak velocity pressure - windward wall - Wind 0 deg and roof
Reference height (at which q is sought); z = 12500mm
Displacement height (sheltering effects excluded); hdis = 0 mm
Roughness length (Table 4.1); z0 = 50 mm
Roughness length (Category II); z0,II = 50 mm
Minimum height (Table 4.1); zmin = 2000 mm
Maximum height; zmax = 200000 mm
Terrain factor; kr = 0.19  (z0 / z0,II)0.07 = 0.19
Roughness factor; cr = kr  ln(z / z0) = 1.05
Mean wind; vm = cr  co  vb = 26.2 m/s
Turbulence factor; kI = 1.0
Turbulence intensity; Iv = kI / (co  ln(z / z0)) = 0.181
Project Job no.
N108-NB-WP-CAL
Calcs for Start page no./Revision
2
Calcs by Calcs date Checked by Checked date Approved by Approved date
M 14/11/2019

Peak velocity pressure; qp = (1 + 7  Iv)  0.5    vm2 = 0.97 kN/m2

Structural factor
Building type; Other
Structural factor (Annex D); csCd = 1.00
Peak velocity pressure - windward wall (lower part) - Wind 90 deg
Reference height (at which q is sought); z = 200mm
Displacement height (sheltering effects excluded); hdis = 0 mm
Terrain factor; kr = 0.19  (z0 / z0,II)0.07 = 0.19
Roughness factor; cr = kr  ln(zmin / z0) = 0.70
Mean wind; vm = cr  co  vb = 17.5 m/s
Turbulence factor; kI = 1.0
Turbulence intensity; Iv = kI / (co  ln(zmin / z0)) = 0.271
Peak velocity pressure; qp = (1 + 7  Iv)  0.5    vm2 = 0.56 kN/m2
Peak velocity pressure - windward wall, (middle part) - Wind 90 deg
Reference height (at which q is sought); z = 12300mm
Displacement height (sheltering effects excluded); hdis = 0 mm
Terrain factor; kr = 0.19  (z0 / z0,II)0.07 = 0.19
Roughness factor; cr = kr  ln(z / z0) = 1.05
Mean wind; vm = cr  co  vb = 26.2 m/s
Turbulence factor; kI = 1.0
Turbulence intensity; Iv = kI / (co  ln(z / z0)) = 0.182
Peak velocity pressure; qp = (1 + 7  Iv)  0.5    vm2 = 0.97 kN/m2
Peak velocity pressure - windward wall (upper part), other walls and roof - Wind 90 deg
Reference height (at which q is sought); z = 12500mm
Displacement height (sheltering effects excluded); hdis = 0 mm
Terrain factor; kr = 0.19  (z0 / z0,II)0.07 = 0.19
Roughness factor; cr = kr  ln(z / z0) = 1.05
Mean wind; vm = cr  co  vb = 26.2 m/s
Turbulence factor; kI = 1.0
Turbulence intensity; Iv = kI / (co  ln(z / z0)) = 0.181
Peak velocity pressure; qp = (1 + 7  Iv)  0.5    vm2 = 0.97 kN/m2

Peak velocity pressure for internal pressure


Peak velocity pressure – internal (as roof press.); qp,i = 0.97 kN/m2
Pressures and forces
Net pressure; p = csCd  qp  cpe - qp,i  cpi;
Net force; Fw = pw  Aref;

Roof load case 1 - Wind 0, cpi 0.20, -cpe


Ext pressure Peak velocity
Net pressure Area Net force
Zone coefficient pressure
p (kN/m2) Aref (m2) Fw (kN)
cpe qp, (kN/m2)
F (-ve) -1.80 0.97 -1.95 2.50 -4.87
Total vertical net force; Fw,v = -4.87 kN
Total horizontal net force; Fw,h = 0.00 kN
Project Job no.
N108-NB-WP-CAL
Calcs for Start page no./Revision
3
Calcs by Calcs date Checked by Checked date Approved by Approved date
M 14/11/2019

Walls load case 1 - Wind 0, cpi 0.20, -cpe


Ext pressure Peak velocity
Net pressure Area Net force
Zone coefficient pressure
p (kN/m2) Aref (m2) Fw (kN)
cpe qp, (kN/m2)
A -1.20 0.97 -1.36 2.50 -3.41
D 0.80 0.97 0.58 750.00 438.72
E -0.70 0.97 -0.88 750.00 -658.08

Overall loading
Equiv leeward net force for overall section; Fl = Fw,wE = -658.1 kN
Net windward force for overall section; Fw = Fw,wD = 438.7 kN
Lack of correlation (cl.7.2.2(3) – Note); fcorr = 1.00; as h/W is 62.500
Overall loading overall section; Fw,D = fcorr  (Fw - Fl) + Fw,h = 1096.8 kN

Roof load case 2 - Wind 0, cpi -0.3, +cpe


Ext pressure Peak velocity
Net pressure Area Net force
Zone coefficient pressure
p (kN/m2) Aref (m2) Fw (kN)
cpe qp, (kN/m2)
F (+ve) -1.80 0.97 -1.46 2.50 -3.66
Total vertical net force; Fw,v = -3.66 kN
Total horizontal net force; Fw,h = 0.00 kN
Walls load case 2 - Wind 0, cpi -0.3, +cpe
Ext pressure Peak velocity
Net pressure Area Net force
Zone coefficient pressure
p (kN/m2) Aref (m2) Fw (kN)
cpe qp, (kN/m2)
A -1.20 0.97 -0.88 2.50 -2.19
D 0.80 0.97 1.07 750.00 804.32
E -0.70 0.97 -0.39 750.00 -292.48

Overall loading
Equiv leeward net force for overall section; Fl = Fw,wE = -292.5 kN
Net windward force for overall section; Fw = Fw,wD = 804.3 kN
Lack of correlation (cl.7.2.2(3) – Note); fcorr = 1.00; as h/W is 62.500
Overall loading overall section; Fw,D = fcorr  (Fw - Fl) + Fw,h = 1096.8 kN

Roof load case 3 - Wind 90, cpi 0.20, -cpe


Ext pressure Peak velocity
Net pressure Area Net force
Zone coefficient pressure
p (kN/m2) Aref (m2) Fw (kN)
cpe qp, (kN/m2)
F (-ve) -1.80 0.97 -1.95 0.00 0.00
G (-ve) -1.20 0.97 -1.36 0.00 0.00
H (-ve) -0.70 0.97 -0.88 0.02 -0.01
I (-ve) -0.20 0.97 -0.39 11.98 -4.67
Total vertical net force; Fw,v = -4.69 kN
Total horizontal net force; Fw,h = 0.00 kN
Walls load case 3 - Wind 90, cpi 0.20, -cpe
Ext pressure Peak velocity
Net pressure Area Net force
Zone coefficient pressure
p (kN/m2) Aref (m2) Fw (kN)
cpe qp, (kN/m2)
Project Job no.
N108-NB-WP-CAL
Calcs for Start page no./Revision
4
Calcs by Calcs date Checked by Checked date Approved by Approved date
M 14/11/2019

Ext pressure Peak velocity


Net pressure Area Net force
Zone coefficient pressure
p (kN/m2) Aref (m2) Fw (kN)
cpe qp, (kN/m2)
A -1.20 0.97 -1.36 0.50 -0.68
B -0.80 0.97 -0.97 2.00 -1.95
C -0.50 0.97 -0.68 747.50 -510.14
Db 0.70 0.56 0.19 0.04 0.01
Dm 0.70 0.97 0.48 2.42 1.17
Du 0.70 0.97 0.49 0.04 0.02
E -0.30 0.97 -0.49 2.50 -1.22

Overall loading
Equiv leeward net force for upper section; Fl = Fw,wE / Aref,wE  Aref,wu = 0.0 kN
Net windward force for upper section; Fw = Fw,wu = 0.0 kN
Lack of correlation (cl.7.2.2(3) – Note); fcorr = 0.85; as h/L is 0.208
Overall loading upper section; Fw,u = fcorr  (Fw - Fl) + Fw,h = 0.0 kN
Equiv leeward net force for middle section; Fl = Fw,wE / Aref,wE  Aref,wm = -1.2 kN
Net windward force for middle section; Fw = Fw,wm = 1.2 kN
Lack of correlation (cl.7.2.2(3) – Note); fcorr = 0.85; as h/L is 0.208
Overall loading middle section; Fw,m = fcorr  (Fw - Fl) = 2.0 kN
Equiv leeward net force for bottom section; Fl = Fw,wE / Aref,wE  Aref,wb = 0.0 kN
Net windward force for bottom section; Fw = Fw,wb = 0.0 kN
Lack of correlation (cl.7.2.2(3) – Note); fcorr = 0.85; as h/L is 0.208
Overall loading bottom section; Fw,b = fcorr  (Fw - Fl) = 0.0 kN

Roof load case 4 - Wind 90, cpi -0.3, +cpe


Ext pressure Peak velocity
Net pressure Area Net force
Zone coefficient pressure
p (kN/m2) Aref (m2) Fw (kN)
cpe qp, (kN/m2)
F (+ve) -1.80 0.97 -1.46 0.00 0.00
G (+ve) -1.20 0.97 -0.88 0.00 0.00
H (+ve) -0.70 0.97 -0.39 0.02 -0.01
I (+ve) 0.20 0.97 0.49 11.98 5.84
Total vertical net force; Fw,v = 5.83 kN
Total horizontal net force; Fw,h = 0.00 kN
Walls load case 4 - Wind 90, cpi -0.3, +cpe
Ext pressure Peak velocity
Net pressure Area Net force
Zone coefficient pressure
p (kN/m2) Aref (m2) Fw (kN)
cpe qp, (kN/m2)
A -1.20 0.97 -0.88 0.50 -0.44
B -0.80 0.97 -0.49 2.00 -0.97
C -0.50 0.97 -0.19 747.50 -145.75
Db 0.70 0.56 0.68 0.04 0.03
Dm 0.70 0.97 0.97 2.42 2.35
Du 0.70 0.97 0.97 0.04 0.04
Project Job no.
N108-NB-WP-CAL
Calcs for Start page no./Revision
5
Calcs by Calcs date Checked by Checked date Approved by Approved date
M 14/11/2019

Ext pressure Peak velocity


Net pressure Area Net force
Zone coefficient pressure
p (kN/m2) Aref (m2) Fw (kN)
cpe qp, (kN/m2)
A -1.20 0.97 -0.88 0.50 -0.44
B -0.80 0.97 -0.49 2.00 -0.97
C -0.50 0.97 -0.19 747.50 -145.75
Db 0.70 0.56 0.68 0.04 0.03
Dm 0.70 0.97 0.97 2.42 2.35
Du 0.70 0.97 0.97 0.04 0.04
E -0.30 0.97 0.00 2.50 0.00

Overall loading
Equiv leeward net force for upper section; Fl = Fw,wE / Aref,wE  Aref,wu = 0.0 kN
Net windward force for upper section; Fw = Fw,wu = 0.0 kN
Lack of correlation (cl.7.2.2(3) – Note); fcorr = 0.85; as h/L is 0.208
Overall loading upper section; Fw,u = fcorr  (Fw - Fl) + Fw,h = 0.0 kN
Equiv leeward net force for middle section; Fl = Fw,wE / Aref,wE  Aref,wm = 0.0 kN
Net windward force for middle section; Fw = Fw,wm = 2.4 kN
Lack of correlation (cl.7.2.2(3) – Note); fcorr = 0.85; as h/L is 0.208
Overall loading middle section; Fw,m = fcorr  (Fw - Fl) = 2.0 kN
Equiv leeward net force for bottom section; Fl = Fw,wE / Aref,wE  Aref,wb = 0.0 kN
Net windward force for bottom section; Fw = Fw,wb = 0.0 kN
Lack of correlation (cl.7.2.2(3) – Note); fcorr = 0.85; as h/L is 0.208
Overall loading bottom section; Fw,b = fcorr  (Fw - Fl) = 0.0 kN

200
60000
Wind - 0o

F Plan viewG- Flat roof F


6250 47500 6250
200

12500

60000
Windward face
12500

12500

A E

200 60000
Side face Leeward face
200

60000
Wind - 90o
100
50 F
G
H Plan view I- Flat roof
59900
20
80
Project Job no.
N108-NB-WP-CAL
Calcs for Start page no./Revision
6
Calcs by Calcs date Checked by Checked date Approved by Approved date
M 14/11/2019

160
40

59800

12500

12500

12500
A
B C DDmu E

Db
60000 200 200
Side face Windward face Leeward face