Section #9
9-1
Section #9-Determining the TRUE % of
OSA Usingg Charts and Formulas
• The TRUE percent (%) of outside air entering into the building via the air
handling unit is found by using percentage charts or formulas. The next
couple off slides will demonstrate both.
OA Percentage Formula
Tra - Tma
% OA = X 100
Tra -Toa
Or to find Temp of Mixed
Air
Tma=Tra x (%Tra)+Tosa x (%Tosa)
Note
Tma =Temp Mixed Air
T = Temp
Tra T Return
R t Air
Ai
Tosa = Temp Outside Air
OA Percentage Chart
9-2
Outside Air Percentage Chart
9-3
Using the Outside Air Percentage Chart
9-4
Exercise to Determine % OSA Using
the Chart ((Plot out the Answer))
9-5
The Answer to % OSA on the Chart
9-6
Formulas to Determine % OSA and
Minimum Position Control
9-7
Exercise to Determine Actual %
Outside Air Supply using the Formula
EA RA
E h
Exhaust
t Air
Ai Return Air
OA SA
Outside Air Supply Air
MA
Mixed Air
EA RA
E h
Exhaust
t Air
Ai Return Air
OA SA
Outside Air Supply Air
MA
= 62.5% OA Mixed Air
EA RA
E h
Exhaust
t Air
Ai Return Air
85% RA
Temperature Sensor
9-10
Answer to Exercise to Determine
Actual Mixed Air Temperature
p Using
g the
Formula
Return Air ((RA)) is 80°F
EA RA
E h
Exhaust
t Air
Ai Return Air
Temperature Sensor
EA RA
E h
Exhaust
t Ai
Air Return Air
Outside Air (OA) is 40°F Mixed Air Temp (MA) Should be 80°F
OA
Outside Air SA
Supply Air
= 0% OA MA Mixed Air
Command close the OSA dampers to 0% (100% closed).
All of the 3 dampers should sequence together, no OSA should enter
the building,g and no exhaust air should leave the building.
g
Supply Air (SA) should = mixed air and return air (RA). Temperat re Sensor
Temperature
If this test does not work, dampers are mostly likely
not sealing off 100% when closed. Inspect and repair as needed.
9-12
PM Procedure to Determine
Efficiency
y of Economizer Dampers
p in 100%
Open Position
Command Open OA and EA dampers to be fully open.
Return Air (RA) is 80°F
80 F.
EA RA
E h
Exhaust
t Air
Ai Return Air
OA SA
Outside Air Supply Air
= 100% OA MA Mixed Air
Command open the OA dampers to 100% (100% open).
All of the 3 dampers should sequence together, only OA should enter
the building,g, with 100% exhaust air.
Supply Air (SA) should = Outside Air (OA) air. Temperature Sensor
If this test does not work, mixed air dampers are mostly likely
not sealing off 100% when closed. Inspect and repair as needed.
9-13
Exercise #9
(Provide Answers below on notes page)
9-14