CONTRACT : NE03 DMRC

CABLE DRUM CARD


FORMAT NO. BSL/NE03/DMRC/CARD/003a Tool/Test equipment Sl no Validity Calibration Certificate No

DRUM NO.
DRUM LENGTH
CABLE TYPE AND SIZE
STATION NAME
DATE:
STATION
S.NO Board Start Board Finish Intial Reading Final Reading Laid length Balance in Drun Remarks

Performed By (BSL-E&M) Witnessed by (DMRC-Project) Witnessed By (DMRC-O&M)

1
CONTRACT : NE 03
DMRC
INSTALLATION CHECK OF OF FIRE ALARM PANEL

FORMAT NO.:DMRC/CE-09 -LOT-2/LT/FIRE ALARM PANEL/59 Tool/Test equipment Sl no Validity Calibration Certificate No

DATE:

STATION

LOCATION

INSTRUMENT DETAILS

VISUAL CHECKS

SL. NO. INSPECTION DESCRIPTION OBSERVATION REMARKS


Check layout and method of installation as shown on the approved constructions
1 drawings Approved drawing

2 Check that the proper supply mains is available near the panel & UPS Visual check

3 Verify the quantity of loop cards are as per the approved drawings Visual check

4 Verify that the power supply is as per the requirement Visual check

5 Any damaged part will be removed and the new part will be put in. Physical check

6 Check that the Fire Alarm Cabling is firmly fixed, terminated and tagged as per the Physical check
approved drawing by BSL /DMRC

7 Check availability of AC power supply cable Visual check

Check connection of DC battery to the Panel. The battery AH should be as per the
8 approved drawing/documents Approved drawing/Physical check

9 Check panel internals visually for damage or loose connections Visual check

2
10 Verify Control Panels are properly fixed and wiring is completed Visual check

11 To demonstrate the process of isolation in all loop Individual loop to be checked

Check that FACP clock is synchronized with station clock system & compare after 1 hr /
12 24 hr Visual check

13 Battery Box installation to be Checked Visual check

14 Auto Dialer Installation to be checked Visual check

15 Relay Box installation to be checked Visual check

16 PC/ Printer availability to be checked as per approval Visual check

17 Magnetic lock operation to be checked Physical check

18 Loop & Device to be marked in all Individual device Visual check

19 Grouting of the Panel to be done Visual check

Performed By (BSL-E&M) Witnessed by (DMRC-Project) Witnessed By (DMRC-O&M)

3
CONTRACT : NE03
DMRC
INSTALLATION CHECK OF DETECTORS
FORMAT NO.: Tool/Test equipment Sl no Validity Calibration Certificate No

DATE:

STATION

LOCATION

INSTRUMENT DETAILS

VISUAL CHECKS

SL. NO. INSPECTION DESCRIPTION OBSERVATION REMARKS

1 Layout & Installation as per approved CRD’s & as per manufacture recommdation Approved CRD

Verify that all Mounting Boxes/ Detectors to be fixed at the required locations are of
2 Visual check
the same material as the service passing through them

3 Addressable of detectors will be fixed on the mounting boxes as per the location Approved drawing
marked in the approved drawings.
Addressing to the detectors will be done by means of putting address via rotary
4 Visual check
switches provided in the bases as per approved drawings

5 Detector heads will be fixed on the bases after checking all the addresses on the Physical checking
detectors.

6 Check that all the wiring firmly fixed and connected as per approved drawing Visual check

7 Upon fixing of each mounting box, before installing the detector base check screws Visual check
are properly tightened to hold the detectors
Check that the addressing has been done via rotary switches as per the approved
8 Visual check/Drawing
drawings

9 Check that the detector bases are properly screwed and the cable is properly Visual check/Drawing
terminated on the terminals of the detectors bases
Check that appropriate electrical supply is coming to the terminals of the detector
10 Visual check/Drawing
bases

11 Check that all the Detector heads are properly installed on the detector bases Visual check/Drawing

12 Check that all the installation has been completed in accordance with the Visual check
corresponding Installation Check sheet and test results are recorded.

Ensure that all completed installations look neat and tidy and that there is adequate
13 spacing between services. Suitable access for operation and maintenance will be Visual check
ensured to junction ways and any inline devices

14 Check marking of Loop No & Detector/Device No. on each Detector/Device Visual check

4
Performed By (BSL-E&M) Witnessed by (DMRC-Project) Witnessed By (DMRC-O&M)

5
CONTRACT : NE03
DMRC
INSTALLATION CHECK OF HOOTER /MANUAL CALL POINT
FORMAT NO.: Tool/Test equipment Sl no Validity Calibration Certificate No

DATE:

STATION

LOCATION

INSTRUMENT DETAILS

VISUAL CHECKS

SL. NO. INSPECTION DESCRIPTION OBSERVATION REMARKS

1 Layout & Installation as per approved CRD’s & as per manufacture recommdation Approved CRD

Verify that all Mounting HOOTER to be fixed at the required locations are of the same
2 Visual check
material as the service passing through them

3 Addressing to the Module will be done by means of putting address via rotary Visual check
switches provided in the bases as per approved drawings

4 Check that all the wiring firmly fixed and connected as per approved drawing Visual check

5 Layout & Installation of MCP as per approved CRD’s & as per manufacture Visual check
recommdation

6 Check the type of MCP as per approved drawing.( Glass Break type ) Visual check

8 Check that the sound of the hooter Visual check/Drawing

Check that the bases hooter base properly screwed and the cable is properly
9 Visual check/Drawing
terminated on the terminals of the detectors bases

10 Check that appropriate electrical supply is coming to the terminals of the hooter Visual check/Drawing

Check that all the installation has been completed in accordance with the
11 Visual check
corresponding Installation Check sheet and test results are recorded.

Ensure that all completed installations look neat and tidy and that there is adequate
12 spacing between services. Suitable access for operation and maintenance will be Visual check
ensured to junction ways and any inline devices

Performed By (BSL-E&M) Witnessed by (DMRC-Project) Witnessed By (DMRC-O&M)

6
CONTRACT : NE03
DMRC
INSTALLATION CHECK OF MONITOR MODULE
FORMAT NO.: Tool/Test equipment Sl no Validity Calibration Certificate No

DATE:

STATION

LOCATION

INSTRUMENT DETAILS

VISUAL CHECKS

SL. NO. INSPECTION DESCRIPTION OBSERVATION REMARKS

1 Layout & Installation as per approved CRD’s & as per manufacture recommdation Approved CRD

Verify that all Mounting MODULES to be fixed at the required locations are of the
2 Visual check
same material as the service passing through them

3 Addressable of Module will be fixed on the mounting boxes as per the location Approved drawing
marked in the approved drawings.
Addressing to the Module will be done by means of putting address via rotary
4 Visual check
switches provided in the bases as per approved drawings

6 Check that all the wiring firmly fixed and connected as per approved drawing Visual check

8 Check that the LED flash on mormal condition Visual check/Drawing

9 Check that the module bases are properly screwed and the cable is properly Visual check/Drawing
terminated on the terminals of the detectors bases
Check that all the installation has been completed in accordance with the
12 Visual check
corresponding Installation Check sheet and test results are recorded.

Ensure that all completed installations look neat and tidy and that there is adequate
13 spacing between services. Suitable access for operation and maintenance will be Visual check
ensured to junction ways and any inline devices

14 Check marking of Loop No & Device No. Visual check

Performed By (BSL-E&M) Witnessed by (DMRC-Project) Witnessed By (DMRC-O&M)