Miniature Circuit Breakers (MCB)

Tugino, ST MT
tugino@gmail.com
081578873090

Dalamnya
MCB

Tugino, ST MT 2

1
MCB 1 
Phase

Tugino, ST MT 3

MCB 3 
Phase

Tugino, ST MT 4

2
Karakteristik MCB MG

Tugino, ST MT 5

Time Current Curves
• An example of 
a TCC with
a TCC with 
Coordinated 
Devices

Current in Amperes X 100


Tugino, ST MT 6

3
Selective Coordination - Good

•No
overlapping
fault current of
individual
devices.
•This is
coordinated
properly.
•In a perfect
Tugino, ST MT world this7is
great.

Selective Coordination - BAD

•ATS Feeder Breaker •In this case,


since it takes 8
cycles for the
upstream
•8 cycles to clear breaker to clear
the fault, a 3
cycle rated
transfer switch
i inadequate.
is i d t

Tugino, ST MT 8

4
Selective Coordination – Circuit Breakers
Not Coordinated above 900A 1000
CURRENT IN AMPERES

800 A. CB
STD @ 0.1 Seconds 100
800 A w/ STD

TIME IN SECONDS
100 A. CB 10
100 A

IT Non Adjustable
20 A
1

20 A. CB
j
IT Non Adjustable
0.10

Coordinated for 900A


overloads and faults 0.01
1 10 100 1K 10K 100K
less than 900A dteate.tcc Ref. Voltage: 480 Current Scale x10^0

Tugino, ST MT 9

Selective Coordination – Circuit Breakers


Selectively Coordinated up CURRENT IN AMPERES

1000
to CBs’ Interrupting Ratings

800 A. CB 100
800 A w/ STD

STD @ 0 0.4
4SSeconds
d
TIME IN SECONDS

100 A w/ STD
10

100 A. CB
STD @ 0.1 Seconds 1
20 A

20 A. CB
0.10
IT Non Adjustable
Overcurrents of any level
0.01
up to CBs’ Interrupting 1 10 100 1K 10K 100K

dteate.tcc Ref. Voltage: 480 Current Scale x10^0


Ratings
Tugino, ST MT 10

5
Coordination
C D B A
t

C D B

Tugino, ST MT 11

Selective Coordination: Avoids Blackouts
Lacking With
Selective Coordination Selective Coordination

Fault Fault

UNNECESSARY NOT AFFECTED 12


OPENS
POWER LOSS
Tugino, ST MT