You are on page 1of 10

Article

How to avoid pressure oscillations


in district heating systems
Herman Boysen, Jan Eric Thorsen

www.danfoss.com
Herman Boysen, Danfoss Heating Segment Application Centre, Denmark
Jan Eric Thorsen, Director, DHS Application Centre

How to avoid pressure oscillations


in district heating systems
The phenomenon pressure oscillation in District Heating systems can
arise even in traditional systems with normal supply conditions.
Over years the reason and theories for it has been discussed and many
remedies has been proposed to eliminate or reduce the oscillations.

Introduction This article describes a part of the valve for controlling a single loop.
experiences gained by Danfoss in this See fig 1.
Pressure oscillation can be observed in particular field of application To understand the function of the
the whole network, part of it or in the knowledge. The article also includes differential pressure controlling it is
District Heating house substation. a brief description of the theoretical important to realize that only the
Experience shows, that high and practical background work made. pressure where the differential pressure
concentration of substations in an area The contents are: controller is mounted can be controlled
gives increasing risk of pressure • Differential Pressure Controller or adjusted. The pressure in the
oscillation (Resonance oscillation). function. connected supply lines are only used
In one family house areas, where the • Influence of application layout and as a reference for the controlled
concentration of small district heating sizing. differential pressure.
substation is high, this is very typical. • Types of oscillations and The function of the differential pressure
Differential pressure controllers play recommendations on how to damp controller is based on a force balance
a significant role in this phenomenon. the oscillations. established in the controller, between
Also the internal system can be the • Computer Simulation Model. the spring and the differential pressure
source for oscillation (Self-oscillation). • Laboratory Test Rig. in the impulse tube.
A correct valve and system sizing, right • Conclusion.
chosen application and correct The mode of operation in a differential
installation of the differential pressure pressure controller is as following:
controller can avoid this kind of Differential Pressure During operation, the differential
oscillations. Controller function pressure controller will try to find
a force balance where the force from
This conclusions mentioned, are based The task of the differential pressure the setting spring Fsp together with the
on detailed analyse of the controller is to keep the system lower pressure p2 will find a balance
phenomenon where the following tools differential pressure in a control loop with the higher pressure p1.
have been used: on a constant value, expressed by
• Observations in the field.
• System calculation. Δ pa = p1 − p2
• Computer simulations. The main parts of the differential
• Laboratory tests for verifying pressure controller are the control
 the theory’s. valve, a diaphragm house, a setting A = area of the diaphragm in the
Among others, pressure oscillation in spring and two impulse tubes. differential pressure controller [m2].
district heating network can have the This shows that the force balance and
p1 and p2 are the pressures where the
following negative effect: the valve cone will move to another
two impulse tubes are connected to the
• Generation of noise in the system. system. The impulse line for position under the following
• Instable temperature and pressure determination of p1 and p2 can be circumstances:
control. connected across at the whole system • Change in the Δpa because change
• Failure of components in the where more heat circuit are connected, in heat consumption.
application caused by peak loads or it can be connected across a control • Change of pressures in the
and/or fatigue. distribution net.

2 Danfoss Heating · VF.CV.V3.02 · ©Danfoss


FIGURE 1: dP control of single loop and dP control of several loops

• Change of the Δpa by adjusting


the spring setpoint.
A movement of the valve cone means
change of Δpa across the differential
pressure controller diaphragm.
The reaction speed of the differential
pressure controller R h can be expressed as:

Where
R h = reaction speed of the differential
controller
qi = flow rate in impulse tube [m3/sec]

∆kv
= valve gain characteristic
∆s   [m3/h√bar/m]
Am = Area of the diaphragm in the
pressure controller [m2] FIGURE 2: Cross-section of differential pressure controller, principal

Danfoss Heating · VF.CC.V3.02 · ©Danfoss 3


In general it’s a fact, that a too quick The relation between changes in Dimension of the supply lines
reacting differential pressure controller pressure Δpr and changes in trapped
In district heating systems, the size
(high Rh value) can generate oscillation volume of water V is determined by the
of the supply lines have an essential
in a system. A lower Rh will reduce the system elasticity. The definition of
influence on creating pressure
system tendency for oscillation. system elasticity C [m3/Pa] is the
oscillation. Velocities of water in
As the formula (2) indicates, the only relation of volume change of water in
a pipeline depend on the differential
way to change the Rh value in an the system related to the pressure
pressure and the length and the
existing system, is to change the flow change:
dimension of the pipe.
rate in the impulse tube. It can also be
Changing velocity of the water stream
seen from formula (2) that a oversized
in the system, will generate a pressure
valve, normally resulting in a high
pulse positive or negative due to
dkv/ds value, will increase the risk of
acceleration or deceleration of the
oscillation.
water.
The task of the differential pressure
Influence from application The rate of system elasticity can easily
controller is to maintain a set Δpa.
be measured in an individual loop. The
layout and sizing During operation the pressure in the
procedure is:
System elasticy system determines whether a large or
Close the main shot-of valves in the small quantity of water is let into the
All water-contained equipment in
loop where to measure the elasticity. system (when the controller is installed
a heating system has more or less
Open a drain in the loop and measure in the flow pipe) or whether more or
elasticity. This means, if the pressure in
the volume of water drained out until less water is remaining in the system
a system changes, the amount of water
the pressure has dropped e.g. 1 bar. (when the controller is installed in the
trapped in the system will change too.
Not all components have the same return pipe) in the way that the
range of elasticity. Heat exchangers quantity of water necessary to give the
and radiators have a high rate of set differential pressure is always
elasticity. Compared to this, the present in the system. Variations in pr
elasticity of valves and pipes can be cause variations in the amount of water
considered in the system because of the system
as insignificant. elasticity. This change of amount of
Table 1: Typical system elasticy’s in district water in the system during variation of
Air in the water has significant
heating substations with Heating and pr can generate a change in velocity for
influence on the system elasticity. DHW circuit
the water stream and consequently
At increasing pressure, more water will high pressure surge on which the
be pressed into the system. On the differential pressure controller can
other hand at pressure decreasing, “overreact” and generate oscillation.
water will be pressed out of the system
Assuming that the compressibility of
because of the system elasticity.
the water is insignificant and ignoring
pipe elasticity, the amplitude of
a pressure surge Δpd [kPa] (index d for
dynamic) can be evaluated by means of
equations:

where
ρ = the density of the water [kg/m 3]
q = specific flow rate [m 3/s]
u = flow velocity [m/s]
t = time [sec]
L = length of the pipe [m]
D = Internal pipe diameter [m]
As the cross-sectional area of the pipe
is a function of the square of the inner
diameter of the pipe (D), it can be seen
that the diameter of the pipe has a big
influence of the Δpd. Also the length of
the pipe has influence of Δpd.
The dimension of the supply line is very
often kept small. The reason are:
• Heat loss from the pipeline.
• Pipeline cost price.
• Installation cost price.

4 Danfoss Heating · VF.CV.V3.02 · ©Danfoss


• The oscillation is not regular,
 i.e. periodically stationary.
• The pressure peak is different from
 case to case.

How to reduce resonance


oscillation?
Activity to reduce resonance oscillation
in a system:
• Make sure the system is well air
vented.
• Install the differential pressure
 controller in a loop with low rate of
 elasticity. (i.e. next to and in series
with the control valve).
• Damping of the differential pressure
FIGURE 3: The four general applications including differential pressure controller  controllers on all or on some of the
 locations in the affected area.
One way of damping the differential
Position of the differential Resonance oscillation pressure controller could be increasing
of the resistance in the impulse tube,
pressure controller Reaction oscillation, as it can be seen in
by applying longer impulse tubes and/
a system, can start when the
To avoid the impact of system elasticity or decrease the internal diameter.
differential pressure controller reacts
it’s important that the impulse tubes and reinforce a pressure change Have in mind that the consequence of
for determining the controlled pressure entered from the network. The damping of the differential pressure
are connected in a non-elastic part of controller itself is not unstable, but it controller will lead to slower control of
the system. Normally in line with only reacts on the impulse coming the system. This can be critical in
a temperature control valve as shown from the network. systems with instantaneous heat
in fig. 3 b) and d). If the impulse tube, exchangers in Domestic Hot Water
A typical source for resonance
determining the controlled pressure, systems. Figure 4 shows the result of
oscillation can come up when more
is connected in the elastic part of the a quick change of the pressure. If the
differential pressure controllers within
system, fig 3 a) and c), the conditions net pressure drops momentary, and
a short distance are creating self–
for oscillation possibly are present. the reaction speed (Rh) on the
–oscillation. Typical for this behavior is
Taking the compression of the water differential pressure controller is very
the differential pressure in a residential
into consideration, the amplitude of slow, there is a risk of negative Δpa.
house area with high content of air in
pressure surge Δpd, when changing the This results in backwards flow through
the water. Here the differential pressure
water velocity Δu is: the system, and may cause
controller’s act simultaneous as one big
“hammering” control valves. See the
differential pressure controller, as the
dotted area (a) in figure 4, representing
time constant is the same all over in the
the period of negative system
system. This cause rapidly changes in
differential pressure.
acceleration or deceleration in the
network.
where Self-oscillation
Even though most of the individual
a = sound - progagation velocity differential pressure controllers in Self-oscillation occurs in individual
in water [m/s] a system are stable and in balance, the systems and starts when the
resonance oscillation coming from differential pressure during operation
Depending on the air content in the
outside will influence the differential reacts on pressure impulse generated
water, the speed of sound normally
pressure controllers and it can be within the system loop of the system.
ranges between 1200 –1400 m/s.
considered as all systems operate In this case the differential pressure
Air content in the water will drastically
unstable. controller is an essential part of the
reduce the speed of sound and there
phenomenon.
by also the pressure peak. If the
content of air in the water is 0,7%, the Parameters that influence the
How to recognize the resonance
speed drops to 250 m/sec. oscillation can be:
oscillation?
• The function of the differential
Characteristics of resonance
 pressure controller.
Types of oscillations and oscillation are:
• The reaction speed of the differential
recommendations on • Strong pressure oscillations in  pressure controller.
how to damp them.  flow- and return line. • The system elasticity.
• Pulsating noise or flow noise altering • The dimension of the supply lines.
Pressure oscillation can be split up  with silence.
in two main categories. Typical for self-oscillation is:
• Oscillation frequency between 0,5 Hz
• Reaction oscillations.  and 0,1 Hz. • The pressure controller is able to
• Self–oscillation. • The oscillation disappear after a while  change the flow rate faster than the
 when the system is well vented.  flow rate in the pipe can be changed.

Danfoss Heating · VF.CC.V3.02 · ©Danfoss 5


How to reduce self-oscillation?
Activity to reduced or eliminate
self-oscillation.
• Dampen the differential pressure
 controller impulse tubes.
• Install the differential pressure
 controller in the stiff part of the
 application.
• If the differential pressure controller
 is mounted in the flow line, it has to
 be ensured that the static pressure in
 the system is high enough to vent it.

Simulation model
FIGURE 4: Consequence of a momentary change in the net pressure To investigate the influence of the
application layout and sizing of i.e.
consumer’s branch lines, on the overall
hydraulic stability, and in order to
develop design rules for future
installations, a simplified dynamic
model of a consumer substation was
built. The model is universal as regards
number and placements of pipes and
valves, as long as they are connected in
series. The model is build up in
Simulink®, which is a widely used
software for i.e. dynamic control
system simulations and analysis. The
model is build up by sub systems as
described below.

Pipes
The dynamic pipe model is of the “rigid
water column type”, where the fluid
flowing through the pipe is treated as
a single mass moving at the flow
velocity U. This assumption is
applicable if the elasticity of the system
is dominant, compared to the
compressibility of the water in the
branch lines. The mass is accelerated
according to the net pressure forces
acting at the pipe ends as well as the
pressure head loss due to friction in the
pipe. The model considers the water to
be incompressible, and it takes the
FIGURE 5: A system with self-oscillation (a). The same system after damping pressure drop due to friction into
the impulse pipes (b) account as well as pressure variations
due to acceleration/deceleration of the
water. The steady state flow velocity is
• The system elasticity in the control How to recognize the self- obtained when the pressure loss across
 loop for the differential pressure oscillation? the pipe equals the difference in
 controller must be large enough to The following conditions are pressures at the pipe ends.
 create a pressure oscillation. characteristic for self-oscillation: The pressure difference between the
Critical for this kind of oscillation is: • Strong pressure oscillation in the flow pipe ends Δpp, thus constitutes three
• System elasticity in the control loop. and return line during operation. parts: The flow friction forces Δpf, the
• The reaction speed Rh on the This will disappear when the system minor loss pressure (bends, flow meter,
 differential pressure controller.  is shut off. strainer etc.) Δpm, and the dynamic
• The dimension of the District Heating • Pulsating noise or rumbling altering pressure variations Δpd.
 supply lines.  into silence over and over. The calculation of Δpf and Δpm is
• A change in system pressure can be • Oscillating frequency between straight–forward and is based on the
 the trigger for oscillation, because the  0.2 Hz and 3 Hz. well–known principles of flow theory:
 controller is not stable.

6 Danfoss Heating · VF.CV.V3.02 · ©Danfoss


In this case, the sign of the pressure
loss and flow is of relevance.
Equation (6) is now expressed as:
Pure air AVP kvs 2.5 Return
DH NET Flow pipe Control valve expansion volume pipe
differential
pressure

Elastic part
FIGURE 6: The Simulink® model of application (a) shown in figure 3. The elastic part of the model is
The lines between the model components represent data connections characterised by a lumped pure air
elasticity. Effects from the elasticity of
pipes and radiators are included in the
Experimental results. Pressure after AVP [bar] specification of the system elasticity,
6 but described by pure air volume
5 behaviour, which is a reasonable
4 assumption in the case where the
3 dominant elasticity is represented by
the air volume. The ideal gas equation
2
for the air volume, based on constant
1 temperature, is:
0
0 2 4 6 8 10 12 14 16 18 20
Time [sec]
Simulation results. Pressure after AVP [bar]
6
5
4 Deriving the elasticity from
3 equation (13) becomes:
2
1
0
0 2 4 6 8 10 12 14 16 18 20
Time [sec]

As it can been seen from equation (14),


FIGURE 7: Experimental and simulation results using an APV controller
the elasticity for the pure air volume is
depending on the static pressure, p, i.e.
a double up of the static pressure
results in 4 times lower elasticity.
For small changes in static pressure
a linearization can be done, which
where ζ is the minor loss results in the expression:
coefficient, and The total pressure difference across the
pipe is then:

where q1 and q2 are flow into and flow


where f is the friction factor and d the out of the lumped system described by
pipe diameter. As it can be seen from equation 5,
the elasticity C. This is a reasonable
the differential equation in of the
Δpd can be calculated on the basis of description of the pipes and heat
non–linear type.
Newton’s second law, the momentum exchanger, which to a certain extent
equation: have linear elastic characteristics.
Valves If equation (15) is rearranged, an
The flow q through a valve is a function expresion to determine the system
of the actual valve opening s and the pressure pr is determined by:
pressure drop Δpv across the valve.
The well–known static orifice law
where m is the lumped mass and u̇ models the flow:
denotes the time derivative of the flow
velocity. Equation (8) implies that

Danfoss Heating · VF.CC.V3.02 · ©Danfoss 7


Controller activating unit
The correct dynamic description of the
activating unit of the differential
pressure controller is of great
importance, and at the same time it
is the most complicated part of the
simulation model. Several different
factors and variables have to be
accounted for. Due to the complexity,
the exact formulation of the applied
model will not be listed here, but in
principle the time derivative of the
valve opening s. can be determined
by means of

FIGURE 8: Calculated accuracy of the flow limitation if a differential pressure


where Δp denotes the controlled controller is used as flow limiter. The accuray is higher at the
differential pressure, ε is the control increased differential pressure Δpset
error, Am is the diaphragm area, Ri is
the flow resistance in the impulse
tubes, and simulated pressures after a Danfoss Conclusion
H is the hysteresis width, b is a APV pressure controller for
damping constant, c denotes the configuration (a) in figure 3 is illustrated This paper explains the nature of
spring constant and F0 is the in figure 7. differential pressure controller in
pretension of the spring (determines relation to oscillation. Some operative
the set point of the differential pressure hints for eliminating or reducing
Laboratory test rig pressure oscillations are presented.
controller).’
The build up test rig is equipped with Thanks to the application knowledge
variable service pipe diameters (13 mm in the field of differential pressure
The system model and 20 mm) and variable lengths control, it is now possible to solve
The next step is to put together the sub (2 m, 10 m, 20 m and 40 m). A water tank pressure oscillatory problems in
systems, based on the above stated equipped with level indicator and already existing applications, and to
equations, and a network pressure pressure gage introduces the system offer specific advice regarding the right
equation, to form a dynamic, non- elasticity. Hereby, the elasticity of the design of new applications in order to
linear simulation model. By this, a tool pure air volume can easily be eliminate the risk of pressure
for describing the dynamic function of calculated. If the influence of i.e. the oscillations. In the future, when new
the differential pressure controller, heat exchanger or the water applications are designed, allowances
including flow and pressure variations compressibility are of relevance, the should be made for the problems that
in the substation, is launched. The elasticity can simply be measured as arise from the interrelationship
Simulink® block diagram model of the described above. The test rig is between system elasticity in the
application (a) from figure 3 is equipped with flow- and return control loop, the control speed of the
presented in figure 6. mounted differential pressure pressure controller, and the dimensions
controllers and a number of control of the consumer service lines. The aim
The simulation model described in this
valves. This gives the option easily to should be to make the elasticity in the
section has been thoroughly verified
switch between the four different control loop of the pressure controller
by the comparison with measurements
applications as shown in figure 3. A real as low as possible, and at the same
from field tests as well as
time data acquisition system is logging time to avoid too small diameters of
measurements obtained through tests
the measured pressure values. Furthere the branch lines. In practice, it has
on a laboratory test rig. The test rig was
more the pressure levels are plotted already been observed that the whole
designed especially with the purpose
currently in real time on a display. district heating network becomes more
of verifying the knowledge and
stable when the experience described
theories explored through the
in this article is incorporated into the
simulations.
design of consumer installations.
It was found that the model in all
configurations gives a good qualitative
description of the relations and
processes involved in the dynamics of
the differential pressure control. As
long as the elasticity of the substation
is of reasonable size and thereby
dominates the dynamics of the system,
then the quantitative results are quite
accurate. A comparison of measured

8 Danfoss Heating · VF.CV.V3.02 · ©Danfoss


Danfoss Heating · VF.CC.V3.02 · ©Danfoss 9
References [1] Atli Benonysson, Poul Erik Hansen, Herman Boysen, Pressure Oscillations
  in District Heating House Stations, 6th International Symposium for
 District Heating and Cooling, Island 1997.
[2] Valdimarsson P., Modelling of Geothermal District Heating Systems.
Dissertation, Faculty of Engineering, University of Iceland, 1993.
[3] Frank P. Incropera, David P. De Witt, Introduction to Heat Transfer, Second Edition.
John Wiley & Sons, 1990.
[4] Stræde B. Pressure oscillation in district heating installations.
 Danfoss A/S, December 1995.
[5] Thorsen Jan Eric, Dynamic simulation of DH House Stations,
Euro Heat & Power, June 2003.

More information Find more information on Danfoss District Energy products and applications
on our homepage: www.heating.danfoss.com

VF.CC.V3.02 © Copyright Danfoss | DHS-SMCT/PL | 2017.04

You might also like