NOIDA POWER COMPANY LIMITED

Technical Specification

Noida Power Company Limited


Technical Specification for 400A LT PANEL

Document No. NPCL/TS/LT/LT PANEL 400A

Creation Date 22.05.2015 Revision Number 1

Created By No. Of Pages: 4


Patri Dileep

Checked By Pavan Pratihast Approved By Rajiv Goyal


Material Code: LTP001A Dated: 22/05/2015
Technical Specification LT Panel 400A Doc. No.: NPCL/TS/LT/LT Panel 400A

INDEX
SL.no CLAUSE ITEM PAGE
1 SCOPE 3
2 SPECIFICATIONS 3
3 CONSTRUCTION 4
4 CURRENT TRANSFORMERS 4
5 SWITCH FUSES UNITS 5
6 ROUTINE TEST 5
7 List of drawings and documents 5
8 SPECIAL NOTES 5
Material Code: LTP001A Dated: 22/05/2015
Technical Specification LT Panel 400A Doc. No.: NPCL/TS/LT/LT Panel 400A

TECHNICAL SPECIFICATION – LT PANEL 800A

Scope:

This specification covers the technical requirements of design, test, and supply of L.T Panels
complete with all accessories for efficient and trouble free operation.

All the panels shall be manufactured as per the following specification. In case of any
deviation from the mentioned, vendor shall bring into notice the same along with its offer. In
absence of such deviation, it will be presumed that equipment offered is exactly similar to the
specification.

Scope of Supply

Panels shall be supplied with the following:


a. Commissioning spares.
b. All relevant drawings, data and instruction manuals.

SPECIFICATION:

Air insulated enclosed rigid floor mounting free standing cubicle type manually operated
L.T. Panel for incoming/outgoing circuits. The panel shall comprise of suitable length of 400
Amp. TPN Bus bar chamber with aluminium Bus bar. Panel should be equipped with the
following:-

1 LT Panel 400A
S.No. Description Ratings Unit Qty Make
A INCOMING:
TP MCCB, Microprocessor based (O/L, S/C)
i. 400A, 36kA Nos 1
protection with door Operating Handle
ii. Trivector Meter, CL - 0.5 0-400A Nos 1
iii. Digital Ammeter with Switch 0-400A Nos 1
iv. Digital Voltmeter with Switch 0-500V Nos 1
v. CT - Class 0.5, 10 VA 400/5A 1 Set 3
vi. Test Terminal Block Standard Nos 1
vii. Phase Indication lamps (R, Y, B) 22.5 mm 1 Set 3
viii. Indication Lamps (On, Off) 22.5 mm 1 Set 2
ix. Control MCB, SP 6A Nos 3
x. Bus Bars : 400A TPN Al. Bus bars 1 Set
B OUTGOINGS:
i. TP SFU with HRC Fuse 100A Nos 1
ii. TP SFU with HRC Fuse 63A Nos 6
Material Code: LTP001A Dated: 22/05/2015
Technical Specification LT Panel 400A Doc. No.: NPCL/TS/LT/LT Panel 400A

General:
Frequency - 50Hz.
Voltage Variations - +10%.
Frequency Variations - +3%.

Construction

1. The cable box chamber shall have adequate space to accommodate 4C X 300 sq mm for
incomer and 16 sq. mm for all outgoing cable glands, packing glands. Outgoing feeder
terminals shall be brought out into the cable box chamber for easy connection of cables.
For Incomer and outgoing cable entries shall be arranged from bottom.
2. Adequate illumination shall be provided for interior of the cubicle.
3. Proper space shall be provided in the meter cubical for accessing.
4. Indicating instruments [viz. Voltmeter Ammeter, LED type indicating lamps for supply
‘ON’ ‘OFF’ ‘TRIP’ indication] shall be mounted on the front. Ammeters and voltmeters
shall be of flush mounting type. The switchboard panel shall be, completely wired, ready
for connecting to the purchaser’s equipment. Name plate with fuse rating details shall also
be provided on the front.
5. Wiring shall be done with 1.1KV PVC copper conductors of suitable size.
6. At least 15 day advance information should be given to enable us to depute our
representative for inspection / testing. Dispatch shall be affected only after inspection
7. Each cable chamber shall have cable entry from bottom and suitable removable gland
plates shall be provided for this purpose. The cable chamber shall be provided with
suitable supporting arrangement between the gland plate and terminals, in the middle. The
cable chamber shall have a minimum width depending upon the outgoing cables.
8. Earth Bus bar shall be provided all around the cubicle at the bottom & it shall be of the
same size as neutral bus bar.

KWH METER:

Energy meter shall be of base mounting type (E3T055) premier or equivalent.

Current Transformers: Ring Type / tape insulated.

I. C.T. shall be ring type / tape insulated as per IS: 2705 of latest version for CT operated
Energy meters.
II. CTs.: Required for metering and instrumentation shall be within the scope of supply.
All wiring required for current and potential terminals of the C.T. operated KWH
meter shall be provided.
Material Code: LTP001A Dated: 22/05/2015
Technical Specification LT Panel 400A Doc. No.: NPCL/TS/LT/LT Panel 400A

MAIN BUS:

The main bus bar shall be rated for 500V, 400 Amps continuous current. Bus Bars shall be
suitably insulated by means of insulating color sleeves of 0.5 KV rating. The temperature of
bus bar and bus bar connections when carrying rated current at rated frequency shall not
exceed 90 C for a maximum ambient temperature of 50 C.

SWITCH FUSES UNITS

I. Switch Fuse units shall be 3 pole units for A.C. capable of breaking of the associated circuit.
Switches shall be quick make and quick break design. Compartment doors shall be
interlocked with the operating handle of the switch so as to prevent opening of the door when
the switch is closed. Switch handles shall have provision for locking in both fully open and
fully closed position.
II. Fuses shall be H.R.C. type. The fuse rating shall be according to the designed load on the
circuit.

Name Plate

The panel as well as the feeder compartments door shall be provided with the name plates
giving the feeder description as required.

ROUTINE TEST

Routine tests shall be performed in compliance of relevant IS to ensure that the equipment
comply with the requirements of this specification. The routine test certificates shall be
submitted to the purchaser for his approval prior to the dispatch of the equipment.

List of drawings and documents to be submitted before ordering

 General outline drawing showing dimensions and shipping weight, quality of


insulating media.
 Section views showing the general constructional features.
 Drawings showing circuit for electrical and logic diagrams.

SPECIAL NOTES

 Warranty shall be for 5 years including all major parts in the supplied panel
 Naming shall be provided in front of all Incomer and all Outgoing chambers.