The Interface Test Set (ITS-04) is used to simulate the current and Ratings
voltage signals generated by sensors inside the OSM 210, 300 and
310 Series Recloser bushings. It can be connected to the OSM Frequency ................................................50/60Hz
Control Cubicle and OSM Tank for testing purposes. When used in Operating Temperature............................0-55°C
conjunction with a power system and three phase test set, it can be Humidity ...................................................98%
used to conduct the following tests: Altitude .....................................................1000m
Three phase short circuit Degree of Protection.................................IP40
Phase to phase short circuit Weight .....................................................15.0kg
Dimensions ..............................................490x365x190mm
Earth fault Tank Simulator Operating Time………....<50ms
Upstream broken wire
Low source voltage Current Channels
Loss of supply. Current Simulation Channels …………....3
The ITS is supplied with a control cable for connecting the set to the Input Current Range AC……….……........0-16A (3 seconds max)
RC10 Control Cubicle. Use the control cable supplied with the OSM to Rated Short-Time
connect the set to the Tank. Thermal Current (1sec)…….....16A
Secondary Injection Conversion Ratio ....1A - 1kA
The ITS OSM Simulator is available for testing purposes where an
actual OSM Recloser is unavailable. In addition to interfacing to the Voltage Channels
Control Cubicle to provide trip/close functionality, the simulator Voltage Simulation Channels …...............6
provides switches for different coil status (Normal and Open Circuit) Input Voltage Range AC...........................0-50V max
and mechanical trip. Test sockets connect to voltage free relay Voltage Conversion Ratio.........................1V - 1kV
contacts to provide Normally Open and Normally Closed OSM position
indication. Note: The test set has been designed so it can use the
primary injection test set outputs to generate voltage as well
as current. Refer to the adjacent diagrams for connection
Warning: Do not inject current into the ITS unit unless examples using this method.
the control cable is connected to the ITS and OSM Control Cubicle.
Military Connector
for connection to
OSM Tank
Earthing Terminal
Banana Sockets
for Voltage
Injection
Banana Sockets
for Current
Injection