DESIGN OF SEVEN STOREY BUILDING

Live Load : 2 kN/m²

Live Load : 1.5 kN/m² ( Terrace )

Floor Finish : 1 kN/m²

Water Proofing : 2 kN/m²

: As per IS:875(Part-2) - Not Design for Wind Load, Since Earthquake


Wind Load
Load is exceed the Wind Loads

Earthquake Load : As per IS:1893(Part-1)-2002

Depth of foundation : 3 m
Below Ground Level

Type of soil :

Allowable Bearing
: 28.5 kN/m²
Pressure

Average Thickness of
:
Footing

Storey Height : 3m ( For Each Floors)

Floors : Basement + Seven Floors

Plinth Level : 6'6"


Walls : 230mm Thick Wall
Material Properties

Concrete : All component unless specified in Design M25 grade all

Ec = 5000 √fck N/mm²

= 25000 N/mm²

Steel :
HYSD Reinforcement of grade Fe 415 conforming to IS-1786 used
throughout

GRAVITY LOAD CALCULATION

Brick Wall
0.23 x 19 ( Wall ) x 2 0.012 x 20 ( plaster ) = 4.9 kN/m²
(230mm thick) =

Slab (5" thick) 0.127 x 25.00 = 3.81 kN/m²


=

FACTOR LOAD CALCULATION

Factor of Safety = 1.5


STRUCTURAL DESIGN
COLUMN DESIGN CALCULATION
WAFFLE SLAB DESIGN CALCULATION
PLINTH BEAM DESIGN CALCULATION
RAFT SLAB & BEAM DESIGN CALCULATION
STAIR DESIGN CALCULATION
3.175
Earth Quake Load:

20.1 x 12.3 m
Floor Area = 247.23 sq. ft = 22.96842 sq. m

Terrace Load = 7.68 x 22.968 = 176.39745 Kn

Typical Load = 7.18 x 22.968 = 164.91325 Kn

Total Load = 1330.79 Kn

wxhxh (wxhxh / Lateral Force for EL


Storey Level W h hxh
/1000 Total(wxhxh)) X Y

7 164.91 21 441 72.73 0.35 62.88 62.88


6 164.91 18 324 53.43 0.257142857143 46.20 46.20
5 164.91 15 225 37.11 0.178571428571 32.08 32.08
4 164.91 12 144 23.75 0.114285714286 20.53 20.53
3 164.91 9 81 13.36 0.064285714286 11.55 11.55
2 164.91 6 36 5.94 0.028571428571 5.13 5.13
1 164.91 3 9 1.48 0.007142857143 1.28 1.28
Total 207.79
X-Direction
EL
T = 0.09 h / (d)½
h = 21 m
d = 20.1 m
T = 0.421564 sec

Building Located at Type II


Sa/g = 2.5
Z = 0.36
I = 1.5
R =5
Ah = (Z I/2R) X (sa/g)
Ah = 0.135
Base Shear = VB = Ah x w
= 179.66

Y-Direction
EL
T = 0.09 h / (d)½
h = 21 m
d = 12.3 m
T = 0.538901 sec
Building Located at Type II
Sa/g = 2.5
Z = Z = 0.36
I = I = 1.5
R = R = 5
Ah = (Z I/2R) X (sa/g)
Ah = 0.135
Base Shear = VB = Ah x w
= 179.66 Kn
Slab Load APPARTMENT
Component Terrace Typical
DL LL DL LL
Self Wt 3.18 0 3.18 0
Water Proof 2 0 0 0
Floor Finish 1 0 1 0

Live Load 0 1.5 0 3

Total 6.18 1.5 4.18 3