Calculation of load for frame analysis :

I Dead Load calculation:

Apart from self weight of beam and column following are the

dead loads considered for the analysis

a) Load from parapet wall

Self weight of parapet wall acting on roof beams plus overhang slab

0.3x0x22 +0.15x0.5x25= 1.88 kN/m

b) Load from s/w of roof slab, roof water proofing

i) For roof slab= = 0.15 x 25 + 1.5 5.250 kN/m2

c) Load coming from brick wall

i) Self weight of 230mm brick load acting on beams

=0.23x2.1x22= 10.626 kN/m

ii) Self weight of 230mm brick load acting on tie beams

=0.23x2.2x22= 11.13 kN/m

II Live Load calculation:

a) Load on roof slab = 1.5 kN/m2

a) Load on Pump floor slab = 5 kN/m2

# Sensitivity: LNT Construction Internal Use


III Wind Load (WL1)

Wind Load Calculation:

Basic wind speed (Vb) = 50 m/s

Risk coefficient (k1) = 1

Terrain height, structure size factor (k2) = 1

Topography factor (k3) 1

Importance factor for cyclonic region 1.15

Design wind speed (Vz) = Vbxk1xk2xk3xk4 = 57.5 m/s

Wind pressure Pz = 0.6 x Vz2 = 1983.75 N/m2

Wind directionality factor Kd 1

Area averaging factor 0.9

Combination Factor 1

Design wind Pressure Pd = KdxKaxKcxPz 1785.375

Length of the building (b) = 8.5 m

Width of the building (a) = 8.5 m

Height of the building (h) = 5 m

a/b= 1.00

# Sensitivity: LNT Construction Internal Use


h/b= 0.59

Ref fig 4B of Force coefficient for clad building = 0.8

IS 875 (p III) Wind pressure acting on building =0.8x1785.375/1000= 1.43 kN/m2

IV Seismic Load (SL)

Seismic zone = III

Damping percentage = 5 %

Importance factor (I) = 1.5

Response reduction factor (R) = 2.5

Ref IS:1893-02 Zone factor (Z) = 0.16

V Sungrade modulus

Ref soil report Allowable bearing pressure = 100 kN/m2

Allowable settlement = 50 mm

Subgrade modulus = sbc/settlement


Subgrade modulus = 2000 kN/m2/m

# Sensitivity: LNT Construction Internal Use


51 52 54 58 TO 60 68 TO 71 74 77 79 80 84 TO 87 91 92 96 97 99 TO
415 424 TO 426 484 494 502 TO 505 514 515 523 613 634 650 653 6
677 1141 1500 TO 1502 1504 TO 1506 1508 TO 1512 1514 1518 151
1525 1526 1528 TO 1532 1535 TO 1540 1758 1764 1766 1767 -
1784 UNI 14.168
64 72 427 1515 1524 1746 1772 UNI 16.5
156 162 431 1567 1576 1748 1769 UNI 3.25
63 76 407 614 1507 1533 UNI 24.29
149 TO 154 158 TO 161 163 191 TO 199 408 428 TO 430 577 TO 58
602 TO 604 615 651 654 664 665 1557 1558 1566 1573 TO 1575 157
1593 1594 1597 TO 1599 1747 1760 1770 1771 UNI 8.6
167 168 170 TO 173 175 176 178 TO 181 184 185 487 495 TO 497 5
517 525 635 675 678 1142 1553 1554 1560 TO 1564 1570 1571 1578
1596 1600 1601 1768 1781 TO 1783 UNI 8.6
164 241 243 TO 250 284 321 581 TO 584 593 594 605 TO 608 616 6
1701 1702 UNI 7.84
1 2 317 643 1705 1706 1715 UNI 7.84
251 TO 253 257 261 262 270 271 275 TO 278 290 299 300 318 TO 3
410 412 422 432 435 491 500 511 513 520 585 TO 588 595 596 609
619 636 637 652 655 667 676 679 1143 1503 1602 TO 1604 1606 16
1616 1619 1621 1624 1625 1629 1631 TO 1633 1656 TO 1658 1660
1676 TO 1678 1681 1697 TO 1699 1708 1709 1711 TO 1713 1749 U

# Sensitivity: LNT Construction Internal Use


TO 87 91 92 96 97 99 TO 101 406 -
15 523 613 634 650 653 662 663 674 -
8 TO 1512 1514 1518 1519 1521 TO 1523 -
58 1764 1766 1767 -

8 428 TO 430 577 TO 580 591 592 601 -


8 1566 1573 TO 1575 1577 1582 TO 1591 -
771 UNI 8.6
84 185 487 495 TO 497 506 TO 509 516 -
TO 1564 1570 1571 1578 TO 1581 1592 -

93 594 605 TO 608 616 617 1687 TO 1696 -

78 290 299 300 318 TO 320 336 TO 349 -


585 TO 588 595 596 609 TO 612 618 -
3 1602 TO 1604 1606 1609 1610 1614 -
633 1656 TO 1658 1660 1663 1668 1673 -
09 1711 TO 1713 1749 UNI 1.52