You are on page 1of 1

PT.

SULFINDO ADIUSAHA SPECIFICATION DATA SHEET :

DEPT. TECHNICAL – ENGINEERING LIGHTNING TERMINAL


1 AIR TERMINAL
TYPE LIGHTNING TERMINAL *E.F.* Early Streamer Emission
IONIZATION POWER 6 X 1012 electrons/sec/microAmpere
STANDARD NFC 17 – 102

2 LIGHTNING CARRIER
MODEL *E.F.* LS+HF Lightning Carrier
TYPE Double Concentric Cu 2 x 35mm2
INNER CONDUCTOR CONDUCTION AREA 35Mm2
OUTER CONDUCTOR CONDUCTION AREA 35Mm2
INSULATION VOLTAGE BETWEEN INNER
250KV @ 1/50μs based on IEC 230 Standard
AND OUTER CONDUCTOR
INSULATION VOLTAGE OF SHEATH 80KV @ 1/50μs based on IEC 230 Standard
Flame-retardant, low smoke emission, halogen free,
INSULATING AND SHEATH MATERIAL
UV rated, non-conductive
BENDING RADIUS 60 Centimeters
SIZE Outer diameter 31mm

3 LIGHTNING COUNTER RECORD


TYPE *E.F.* Lightning Counter Record
TRIGGERING CURRENT 1.5kA @ 1.5μs
INTERNAL APERTURE 32Mm
DIMENSION 69Mm x 105mm x 70mm

4 LIGHTNING EARTH / GROUND TERMINAL


MATERIAL Copper-Clad Steel
DIAMETER 1/2” in
LENGTH 2.4 meter

PROCESS REFERENCE -
LOCATION CHG Plant Project
PR NO
PROJECT NAME CHG Plant Project
DESIGN BY Ardiyansah Date : …….. / …….. / ……..
CHECK BY Budi Aris H Date : …….. / …….. / ……..
APPROVED BY Mangadar M Date : …….. / …….. / ……..
Rev. (0)

Specification Ligthning Air Terminal.xls Sheet 1 of 1

You might also like