Professional Documents
Culture Documents
Vdocuments - MX - SCT 1466 Vol G Techno Commercial Bid Technical For Electrical Vol G PDF
Vdocuments - MX - SCT 1466 Vol G Techno Commercial Bid Technical For Electrical Vol G PDF
FOR
TECHNOCOMMERCIAL BID-
VOLUME-G –TECHNICAL
REQUIREMENTS FOR GENERAL
ELECTRICAL
For
Pre-bid tie up on back to back basis for Civil, Structural & Balance of
Plant for 1x700 MW Combined Cycle Power Plant of Andhra Pradesh
Power Development Company Limited (APPDCL) at Nedunoor,
Karimnagar Dist, AP
No. of pages
Sl no of
Description (including Remarks
Volumes
drawings)
BHEL NIT
Vol -A
Project information, schedules, QA, Other
requirements
Scope TP, Exclusions
BHEL
Proposed scope split of Electrical between BHEL &
Vol -B
EPC contractor
Scope split BHEL & EPC contractor dt 29-06-2011
Scope of lifting equipments
BHEL SCC- BHEL
Vol -C
BHEL Consolidated GCC- BHEL-PEM
Vol -D APPDCL Volume -1,SECTION A1 TO A4
Geo tech investigations
BHEL
Tech requirements for General Civil works
Vol -E
Additional civil drgs
BHEL Scope of Cooling tower
Vol -F
BHEL Tech requirements for General Electrical works
Vol -G
BHEL Technical spec for Mechanical packages- Bought
Vol -H out packages
BHEL NOT APPLICABLE
Vol -I
BHEL Amendments & clarifications
Vol -J
BHEL Schedules
Vol -K
BHEL Price schedule
Vol -L
TECHNICAL
REQUIREMENTS FOR
GENERAL ELECTRICAL
VOLUME -G
CONTENTS
2. SCOPE OF WORKS 1
IT IS CONFIRMED THAT OUR TECHNICAL OFFER COMPLIES WITH THE SPECIFICATION IN TOTO.
---------------------------------------------------------------------
BIDDER’S STAMP & SIGNATURE
1
Doc. No. PE-TS-I59-888-E001
700MW KARIMNAGAR CCPP
TECHNICAL SPECIFICATION FOR Rev. : 0
GENERAL ELECTRICAL WORKS
Page : of
1. INTENT OF SPECIFICATION
1.1 The owner Andhra Pradesh Power Development Company Ltd has invited bids for the EPC
package of 1X700 MW CCPP at Nedunoor Karimnagar Dist. BHARAT HEAVY ELECTRICALS
LIMITED (BHEL) intends to bid for this project and invites quotations for design and
execution of the work for electrical systems of the project mentioned in relevant clauses.
1.2 At the outset the bidder must understand that this offer is to be submitted on back to back
basis which means that the bidder assumes total and unconditional responsibility for all
electrical works as per owner’s requirements and subject to owner/ owner’s consultant’
approval.
1.3 Timely submission of drawings & documents / obtaining approval of drawings / documents
from owner / owner’s consultant shall be the responsibility of the bidder.
1.4 It is specifically emphasized that the bidder quoting for Electrical Works package shall be
comprehensively responsible for complete scope of work stated or unstated including
preparation of design and drawings, obtaining necessary approvals, materials, execution as
per codes, best engineering practices and to the satisfaction of the owner.
IT IS CONFIRMED THAT OUR TECHNICAL OFFER COMPLIES WITH THE SPECIFICATION IN TOTO.
---------------------------------------------------------------------
BIDDER’S STAMP & SIGNATURE
2
Doc. No. PE-TS-I59-888-E001
700MW KARIMNAGAR CCPP
TECHNICAL SPECIFICATION FOR Rev. : 0
GENERAL ELECTRICAL WORKS
Page : of
2. SCOPE OF WORKS
2.1 It shall be Contractor’s responsibility to provide all the equipment / systems / services and
interfacing between various systems for the completeness of the 700 MW Combined Cycle
Power Plant (CCPP). The following configuration shall be considered.
2 GTs + 2 HRSGs + 1 STG in Multishaft configuration.
2.2 The requirements described here are for 700 MW CCPP. All equipment in the plant shall
operate without any limitation upto the full load of Gas Turbine offered. This shall be applicable
to all regimes of GT operation including the temperature range, frequency range, voltage range,
with evaporative cooler etc.
However for the purpose of the PG test, the evaporative cooler shall be switched off.
2.3 The Plant electrical systems for proposed combined cycle power plant shall essentially
comprise but not be limited to the following:
1. HT power cables, LT Power cables, LT Control cables & instrumentation cables
2. Cabling & installation equipment(cable trays & accessories, cable tray support, trefoil clamps,
termination kits, jointing kits cable glands & lugs etc).
3. Earthing & lightning protection(including above & below grade grounding material)
4. Station lighting system.
5. Neutral grounding resistors for Unit auxiliary transformers.
6. 220V DC battery, battery chargers, DC switchboards and their accessories.
7. 400V AC switchgear, LV power distribution boards and accessories.
8. Public address system equipment.
9. Electrical laboratory equipment
10. Insulating mats
11. Cathodic protection
12. Drawing & Document submission for all packages : System design, Design Calculations,
Design Memorandums, Layout drgs., Electrical load list, cable schedules, cable
interconnections, Data sheets, OGA, Quality plans, test certificate etc.
IT IS CONFIRMED THAT OUR TECHNICAL OFFER COMPLIES WITH THE SPECIFICATION IN TOTO.
---------------------------------------------------------------------
BIDDER’S STAMP & SIGNATURE
3
Doc. No. PE-TS-I59-888-E001
700MW KARIMNAGAR CCPP
TECHNICAL SPECIFICATION FOR Rev. : 0
GENERAL ELECTRICAL WORKS
Page : of
4
4. MASTER LIST OF DRAWINGS/ DOCUMENTS TO BE SUBMITTED BY EPC PARTNER AFTER AWARD OF CONTRACT
(INDICATIVE)
10 ELE 100 ELE LAYOUT PE-DG-I59-100-E016 CABLING LAYOUT BELOW DC BATTERY ROOM
CABLING TRAY LAYOUT AT 9.5M EL. CABLE VAULT-
11 ELE 100 ELE LAYOUT PE-DG-I59-100-E020 BC BAY
CABLE TRAY LAYOUT IN TG HALL IN BELOW 8.5M
12 ELE 100 ELE LAYOUT PE-DG-I59-100-E021 EL
CABLE TRAY LAYOUT IN TG HALL IN ABOVE
13 ELE 100 ELE LAYOUT PE-DG-I59-100-E022 8.5M EL
14 ELE 100 ELE LAYOUT PE-DG-I59-100-E038 CABLE TRAY LAYOUT ON HRSG PLATFORMS
20 ELE 100 ELE LAYOUT PE-DG-I59-100-E063 CABLE TRENCH LAYOUT IN GAS TURBINE BUILDING
ELECTRICAL EQUIPMENT LAYOUT OF BFP
21 ELE 100 ELE LAYOUT PE-DG-I59-100-E065 BUILDING
CABLE TRENCH LAYOUT IN STEAM TURBINE
22 ELE 100 ELE LAYOUT PE-DG-I59-100-E067 BUILDING
33 ELE 100 ELE LAYOUT PE-DG-I59-100-E081 CABLE TRAY LAYOUT IN CW PUMP HOUSE
5
4. MASTER LIST OF DRAWINGS/ DOCUMENTS TO BE SUBMITTED BY EPC PARTNER AFTER AWARD OF CONTRACT
(INDICATIVE)
34 ELE 100 ELE LAYOUT PE-DG-I59-100-E082 CABLE TRAY LAYOUT IN RAW WATER PUMP HOUSE
47 ELE 507 CABLES & CABLING PE-DG-I59-507-EXXX LAYOUT FOR ALL AREAS
48 ELE 507 CABLES & CABLING PE-DG-I59-507-EXXX CABLE TRAY LAYOUT FOR ALL AREAS
49 ELE 507 CABLES & CABLING PE-DG-I59-507-EXXX CABLE SCHEDULES FOR ALL AREAS
CABLE INTERCONNECTION FOR ALL CABLE
50 ELE 507 CABLES & CABLING PE-DG-I59-507-EXXX SCHEDULES
6
SPEC.NO.
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. VOLUME III
TCE.5960A-H-500- TITLE
001 SECTION:
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST. CONTENT SHEET
EPC SPECIFICATION -ELECTRICAL SYSTEMS SHEET 1 OF 2
VOLUME-III – CONTENTS
ELECTRICAL SYSTEM
NO. OF
SECTION NO. SPECIFICATION NO. REV.NO. TITLE
SHEETS
D3.0 TCE-5960A-H-500-01 R0 GENERAL REQUIREMENT 15
ISSUE
R0
BID DRAWING
NO. OF
SL NO. DRAWING NO. REV.NO. TITLE
SHEETS
1.0 TCE.5960A-EL-2001 P0 KEY ONE LINE DIAGRAM 01
ISSUE
R0
TITLE SHEET 1 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
(d) All the equipment, material and systems shall, in general, conform to
the latest edition of relevant National and International Codes &
Standards, especially the Indian Statutory Regulations. The
accompanying specifications also indicate the applicable codes and
standards. The equipment/material/systems conforming to other
equivalent national and international standards shall also be
considered provided the same ensures equal or better features
compared to standards listed in accompanying specification.
(e) Control supply voltage for all the switchgear for the GTG, HRSG,
Cooling tower & STG shall be 220 V DC & 110 V AC. However the
area where the DC control supply is required shall be finalized during
the detailed engineering.
(f) Fault level shall be limited to 44 kA rms for 6.6 kV systems and 50 kA
rms for 400 V system. However the three phase symmetrical short
circuit fault current value shall be based on load flow and fault
studies, to be carried out as a part of this contract.
(g) The nominal voltage of main DC system shall be 220V and 24V DC
system for I& C application. To cater the 400kV switchyard PLCC
load, separate 48V DC system shall be provided. Any other voltage
required shall be derived from 220V DC or 230V AC UPS distribution
board for catering to the control & instrumentation loads.
ISSUE
R0
9
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 2 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
(l) The electrical scheme for the project shall be as per the enclosed
drawings:
ISSUE
R0
10
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 3 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
1.1.1 The generator shall be three phase, horizontal, two pole, cylindrical rotor,
Wye connected machine with phase and neutral terminals brought out for
connection to isolated phase bus duct. The Gas turbine generators /steam
turbine generators and their excitation systems shall have a capability at
least matching the declared maximum continuous output of the associated
gas turbine /steam turbine at the outside ambient air temperature ranging
from 00C to 500C, at all power factor between 0.85 lagging and 0.95 leading.
The contractor shall ensure that when the generator is working at this
capability, no part of the generator shall attain a temperature in excess of the
temperature limit specified in IEC 60034. The Insulation class of the machine
shall be Class-F but its temperature rise shall be limited to Class-B.
1.1.2 The Gas Turbine Generator and Steam turbine Generator shall be of
hydrogen & water cooled. The Stator core & Rotor winding shall be hydrogen
cooled. The Stator winding shall be DM water cooled.
1.1.3 The Contractor shall offer 2 nos. Static Frequency Converter (SFC) for
starting of one gas turbine generator at a time. It shall be ensured that either
of SFC can be used for cranking any of the Gas turbines without any
limitation on successive starts of all gas turbines and restarts thereon.
The continuous current rating of the GCB shall be arrived at considering the
maximum output of the generator and at specified minimum voltage. The
voltage class of the Generator circuit breaker shall be same as that of the
generator. The GCB shall be of SF6, metal enclosed, outdoor and
freestanding type.
1.3.1 The continuous rating of the generator transformers shall be such that the
declared maximum continuous output of the respective turbine unit at any
ambient temperature between 00C and 500C can be delivered at the rated
ISSUE
R0
11
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 4 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
1.3.2 The GT shall be with voltage ratio of generator voltage / 420kV, two winding,
50 Hz, ONAN / ONAF / OFAF cooled transformer, with On Load Tap
Changer with +10% to -10% of in steps of 1.25% on the HV side.
1.5.1 The continuous current rating of the generator bus duct shall be arrived at
considering the maximum output of the generator and at specified minimum
voltage.
1.5.2 The M.V. / L.V. Bus duct shall be sized based on the transformer rating at
minimum tap.
1.6 Protection
ISSUE
R0
12
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 5 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
(b) The layout of the switchyard shall be such that adequate space for
maintenance of prime equipment like circuit breakers and current
transformers is available. Approach road shall be provided. Approach
road all around the switchyard shall also be provided for maintenance
and patrolling.
The earth mat shall be extended 2 m beyond fence for the switchyard.
The earth mat of 400kV switchyard shall be inter connected with main
plant. The earth mat shall be designed for short time rating of 1
second rating and shall be considered for calculation of step & touch
potential. For the Earthing system design System fault current to be
considered is 50 kA.
(d) The EMVT/CVT and LA shall be connected to earth pit through pipe
electrodes.
(f) All tension insulator strings shall have double tension string
arrangement.
(i) The coolers shall preferably be arranged on side, other than LA.
(k) The aluminium tubular busbar conductors wherever if used shall have
maximum one joint per span.
ISSUE
R0
13
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 6 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
(l) Corona rings & corona bells shall be used wherever required and
same shall be of non-magnetic material. The requirements regarding
RIV and corona extinction voltage shall include terminal fittings.
(o) The switchyard shall be provided with suitable phase markers and
danger plates.
The Contractor shall furnish the system studies like load flow, short
circuit and transient stability studies of the complete system including
the transmission lines during detail engineering stage for Owner’s
approval. In addition to the above, Contractor shall submit the relay
co-ordination, motor starting studies for the complete plant for
Owner’s approval.
ISSUE
R0
14
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 7 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
(iii) Rated short time current 50 kA rms for one (1) second
withstand capacity
vi) Clearance
ISSUE
R0
15
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 8 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
(a) Control of L.V. and M.V. auxiliary power system, covered under the
scope of this package shall be provided through the DCS system.
(c) PLCC panels for lines shall be located in the outdoor kiosk panels.
The 6.6 kV switchgear and its accessories shall conform to all latest editions
of national and international standards. For feeding the plant auxiliaries rated
for 6.6 kV and service transformers, adequately rated switchgears shall be
provided. The fault level for the switchgear, circuit breakers, isolators, earth
switch, bus bars, etc., shall be arrived at, on the basis of short circuit current
contribution from UAT plus short circuit contribution by the motors running on
the bus.
A margin of 5% over higher of the above S.C current, shall be applied and
rounded off to the next higher standard ratings and this value shall be
adopted for the breakers and switchgears. The momentary current ratings
shall be 2.55 times this value.
Adequate number of 6.6 kV / 420V epoxy cast resin dry type service
transformers shall be provided to meet the demand on 400V systems, with
the criteria that each 400 V switchgear / MCC / DB shall be fed by 2x100%
transformers / feeders, and these shall be rated to carry the maximum load
expected to be imposed with 10% margin at all ambient. Each of the
ISSUE
R0
16
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 9 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
The service transformers shall be two winding, three phase, 50 Hz, 6600 /
420 Volts, Dry type AN cooled with off-circuit taps of ±5% in steps of 2.5%.
The 400 V switchgear and its accessories shall conform to all latest editions
of national and international standards. For feeding the 400V / 230V AC
loads of the plant, 400V switchgear / motor control centres (MCCs) and AC
distribution boards (ACDBs) shall be provided. The switchgears shown in
Key One Line Diagram drg. No. TCE.5960A-EL-SK-2001 is tentative. Any
additional switchgear / MCCs as required shall also be provided.
(b) Generator neutral shall be high resistance earthed. The neutral shall
be connected to a suitably rated neutral earthing transformer with
secondary loading resistor, limiting the earth fault current to about 5-
10 A. The neutral earthing equipment shall be rated to carry this
current for at least 30 seconds considering the generator terminal
voltage under maximum field forcing conditions.
1.13 DC System
ISSUE
R0
17
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 10 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
(a) DC power supply with high discharge Lead acid plante type battery
cells forming bank shall be the source of the power supply for control,
protection, interlock, annunciation of the complete plant including I&C
system during the running of the plant as well as for a safe shutdown
at the time of the total power supply failure.
(b) 220V, DC 2 x 100% battery bank with associated float cum boost-
charger, 1 No. DC switchboard shall be provided for each gas turbine
generator (GTG) unit. The GTG unit DC system with 100% capacity
shall be sized to cater complete unit loads for atleast 10 hrs.
(c) 220V, DC 2 x 100% battery banks with associated float cum boost-
chargers and 1 No. DC switchboard shall be provided for station DC
system. The station DC system shall be sized to cater STG, HRSG
and station loads for at least 10 hrs.
(d) 220V, DC 2 x 100% battery banks with associated float cum boost-
chargers and 1 No. DC switchboard having 2 Incomers & one bus
coupler shall be provided for 400kV system (switchyard) auxiliaries.
The switchyard DC system shall be sized to cater loads for at least 10
hrs.
(e) 48V, DC 2 x 100% battery banks with associated float cum boost-
chargers and 1 No. DC switchboard having 2 Incomers & one bus
coupler shall be provided for 400kV switchyard PLCC application.
(f) 24V, DC 2 x 100% battery banks with associated float cum boost-
chargers and 1 No. DC switchboard having 2 Incomers & one bus
coupler shall be provided for I& C , DCS system.
(g) The boost charger unit shall be rated such that the battery can be fully
charged from fully discharged condition within 8 hours.
(h) Each battery charger shall be capable of float charging the two
batteries while supplying the normal DC loads.
(i) Sizing criteria shall include design margin of 10%, 25% margin on
ageing and ambient temperature compensation as per IS.
ISSUE
R0
18
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 11 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
Parallel redundant UPS shall be with duplicate charger, inverter & battery
system and standby supply to cater the UPS loads of complete plant
Instrumentation and control system loads such as HMI, SWAS etc. The UPS
shall be sized considering full load plus spare loops plus 20% margin.
Cables shall be derated for the site ambient and ground temperatures,
grouping and soil resistivity. Contractor shall furnish detailed cable
selection/sizing criteria for Owner’s approval. Cables shall be selected to
limit maximum voltage drop at equipment terminals during normal operation
and starting conditions well within permissible values. Voltage grade of
cables shall be of earthed grade when used in solidly earthed systems, and
unearthed grade when used in non-effectively earthed systems.
Lighting system shall be provided for the entire plant covering all the
buildings, outdoor areas, roads, yards, boundary, etc. The lighting system
design shall comply with the acceptable norms and the best engineering
practices. The lighting layout shall be designed to provide uniform
illumination with minimum glare. The layout design shall meet all the
statutory requirement, local rules etc.
The earthing system shall be designed for a life expectancy of at least forty
(40) years, for maximum fault current of 50kA for 1.0 sec. The minimum rate
of corrosion of steel for selection of earthing conductor shall be 0.12mm per
year. Grounding and lightning protection for the entire power plant,
switchyard and other areas or buildings covered in the specification shall be
provided in accordance with IS:3043, IS:2309 & IEEE : 80 and IEEE : 665.
1.18 Motors
(a) Wherever the basis for motor ratings are not specified in the
corresponding mechanical specification sections, maximum
continuous motor ratings shall be at least 10% above the maximum
load demand of the driven equipment under entire operating range
including voltage and frequency variations.
ISSUE
R0
19
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 12 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
(b) All M.V. motors shall be suitable for 6.6 kV, 3 phase, 50 Hz and LV
motors shall be suitable for 400 V, 3 Phase, 50 Hz power supply. The
voltage for M.V. and L.V. motors shall be ±10%.
(c) The motors rated 175 kW and above shall be 6.6kV and motors rated
upto 175 kW shall be 400 V.
(c) 6.6kV and 400V switchgear, MCCs and DBs shall have positive fool-
proof interlocking to ensure that different supplies and transformers
are never operated in parallel and fault level does not exceed the
switchgear capability. For 400V switchgear, contribution from
emergency DG set shall be considered while designing the fault level.
ISSUE
R0
20
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 13 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
(d) During Grid black-out condition, it shall be ensured that only the
essential auxiliaries of all units are fed from emergency Diesel
generator & non- essential loads are automatically tripped.
(e) DC scheme shall provide at least two feeds through diode sharing to
critical consumers e.g. all protection panels / control desks, circuit
breakers, GCB, 6.6 kV / 400 V unit and emergency switchgear panels,
generator excitation system, generator oil seal system, etc. The
details shall be subject to Owner’s approval. For generator protection
and protection panels for all 400 kV switchyard feeders, duplicated
DC feeders shall be provided, one from each battery system.
1.22 The insulation level for the transformer windings and bushings shall be as
follows:
Winding Bushing
7.2 kV 20 60 20 60
12 kV 28 75 28 75
17.5 kV 38 95 38 95
Note: for 400kV system switching impulse of 1050 kVp shall be considered.
ISSUE
R0
21
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 14 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
i) VT/relay compartments - IP 52
iii) GCB - IP 65
(d) Motors
i) Indoor motors - IP 54
i) In air-conditioned areas - IP 32
ii) In other areas - IP 52
(f) Transformers
ISSUE
R0
22
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 15 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
i) Indoor Transformers - IP 31
(g) Push button stations and any other kiosk / box / panel / enclosure
i) Indoor - IP 54
ii) Outdoor - IP 55
v) Switchgears - 1 second
ISSUE
R0
23
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 16 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
b) EPABX System
This system will have adequate number of push button type handset
stations, central automatic telephone exchange, etc. The handsets in the
control room would be provided with priority service facility to enable
them to have immediate access to any handset even if it is already
engaged.
ISSUE
R0
24
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.0
TITLE SHEET 17 OF 17
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERAL REQUIREMENTS TCE.5960A-H-500-001
ISSUE
R0
25
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 1 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.1 Generator
1.1.1 The MW out put of generator of the Gas turbine generator unit and
Steam turbine generator unit shall be sufficient to evacuate the
normal and peak power output of gas turbine power over the
complete range of site ambient conditions specified in Section-B
and at rated casing (Hydrogen) pressure and temperature.
1.1.3 The generator shall be three phase, horizontal, two pole, cylindrical
rotor, Wye connected machine with phase and neutral terminals
brought out for connection to isolated phase bus duct. The
generators shall conform to IEC60034-1, IEC60034-3 or other
equivalent international standards. The generator shall be capable
of satisfactory continuous operation at rated MVA and power factor
at any voltage from 95% to 105% of rated voltage and within a
frequency range of 47.5 to 51.5 Hz (and a combined frequency and
voltage variation of 5%) even if frequency and voltage variations
occur simultaneously, without exceeding safe temperature rises, but
not necessarily in accordance with the standards established for
operation at rated voltage and frequency. The generators shall be
provided with Class-F insulation with temperature rise limited to that
of Class-B at full load and at rated voltage & frequency. However,
for abnormal operating conditions of voltage and frequency, the
temperature rise shall in no case exceed that of Class-F when the
machine is operating continuously at full load and at rated power
factor at any working voltage and any frequency in the range
stipulated above.
ISSUE
R0
26
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 2 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.1.5 The line charging capability of the generator shall not be less than
30% of its rated MVA at zero power factor.
1.1.7 The core of the generator shall be designed such that it permit the
flow of earth fault current of at least 15 amperes for one (1) second
without any core damage.
1.1.8 The generator phase and neutral side terminals shall be brought out
through seal off bushings.
1.1.9 The bearings shall be lubricated by oil from the turbine lube oil
system. Non-hygroscopic insulation shall be provided to prevent
any damage due to the circulation of shaft current to the bearing
surfaces and the lubricating oil.
27
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 3 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.1.16 When tested on open circuit and at rated speed and voltage, the
telephone influence factor of the turbine generator shall not exceed
1.5 %.
(a) Twelve (12) duplex RTDs (Four per phase) distributed equally
around the periphery of the stator winding and also between
three phases shall be provided. The geometry of the detectors
shall be such that hot spots anywhere in the stator winding can
be detected.
(b) Twelve (12) duplex RTDs for stator core out of which six shall
be located in the end zones where maximum temperatures are
expected.
(c) Two (2) duplex RTDs for each hydrogen cooler section at inlet
and outlet (if applicable).
(d) Two (2) thermostats per hydrogen cooler section for gas inlet
and outlet (if applicable).
(e) Two (2) duplex RTDs for hydrogen cooler water inlet and outlet
(if applicable).
ISSUE
R0
28
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 4 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
(g) Two (2) duplex RTDs for cold air temperature and two (2)
duplex RTDs each for air temperature in the exciter air
passage and rectifier wheel along with thermostats for cold and
hot air.
(h) Set of duplex RTDs and thermostats for shaft seal system (if
applicable).
1.1.20 All RTDs shall be of platinum duplex four wire type and shall have a
resistance of 100 Ohms at zero degree centigrade and calibrated
as per DIN standards. Termination of RTD leads shall be at terminal
box after grouping of signals. Terminal box shall be at an easily
accessible position so as to enable maintenance / testing of the
devices when the machine is under operation. Termination box of
the temperature measuring devices shall be of IP-55.
29
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 5 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.2.3 The housing shall have suitable provision for handling, lifting and /
or jacking the stator. Manholes with sealing arrangement shall be
ISSUE
R0
30
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 6 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.2.4 End plates of the generator frame shall be suitably shielded from
stray flux. Stray current insulation shall be provided so that all
paths of stray current will be broken at two places in series at one
end of the generator with provision made for determining the
insulation resistance at each place of insulation with the unit in
operation.
1.3.1 The stator core shall be fabricated out of high permeability best
quality cold rolled silicon steel so that losses are minimum. The
core assembly and mounting arrangement shall be such that the
transmission of the forced vibration of the core to the housing and
foundation is effectively restricted. The end packets shall be
adequately strengthened to minimise the magnetic vibration due to
end leakage flux.
1.3.2 The core assembly shall have adequate ventilation ducts for
cooling by hydrogen. Press plates and fastening elements shall be
made of non-magnetic material and shall be with proper locking
arrangement.
ISSUE
R0
31
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 7 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.3.3 The stator core mounting arrangement shall be such that radial
and tangential magnetic vibrations of the stator core due to
electromagnetic loading transferred to stator frame are minimised.
The stator core, frame and mounting shall be designed to avoid
resonance at 50, 100 and 200 Hz.
1.4.1 The stator winding shall consist of three phase, double layer, short
chorded, bar type lap winding having two parallel paths. The
strands making up the stator bar shall be Roebel transposed to
minimise eddy current losses.
1.4.2 The winding and all connections inclusive of phase and neutral
leads shall be insulated for full voltage to ground.
1.4.3 In order to reduce the corona in the slot and where the stator bar
leaves the stator core, a surface treatment corona grading system
shall be applied which shall be carried into the end turn area.
1.4.4 Firm seating of the stator bar in the slot shall be ensured by proper
wedging and fillers. Ripple springs shall be provided below the slot
wedges to compensate for any future shrinkage and ensure
permanent firm seating of the bars in the slot during operation.
The end turns shall be suitably braced and supported to withstand
forces during normal operation and sudden short circuit at
generator terminals when the machine is operating at rated MVA,
power factor and permissible maximum over voltage.
1.4.6 At least six (6) numbers of vibration pickups at each end of over
hang portion of the winding shall be provided, symmetrically
located around the periphery with connection to Turbine
Supervisory system. Provision shall also be made available to
connect the same to DCS. Bidder shall wire up all the pickups to a
junction box outside the generator casing.
1.5.1 All phase and neutral terminals shall be brought out from the top
of the generator (non-drive end) and located in a non-magnetic
steel terminal box. Phase terminal bushing shall be spaced to
ISSUE
R0
32
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 8 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.6 Rotor
1.6.1 The generator rotor shall be machined from a single alloy steel
forging to ensure required mechanical strength and magnetic
properties. Adequate margin shall be provided between critical
speed and the running speed to ensure smooth running. Facilities
shall be provided for inserting at least two radial and one axial
probe into the rotor shaft for carrying out ultrasonic and residual
stress measurements during the life of the rotor.
1.7.1 Rotor winding shall be made of hard drawn silver bearing solid
copper conductors. Winding insulation shall correspond to Class-F
(i.e. epoxy glass based material) with temperature limited to Class
-B. Rotor winding shall be secured in the slots by suitable slot
wedges and fillers. The overhung portion of rotor winding shall be
held in position against centrifugal force by retaining rings when
the rotor is running at upto 20% above its normal speed.
1.7.2 The retaining rings shall be machined from high strength, non-
magnetic alloy steel forging with the material specification
X8CrMnNi1818 resistant to stress corrosion. The retaining rings
shall be floating type, shrunk on rotor body and prevented from
axial movement by snap rings / locknuts.
ISSUE
R0
33
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 9 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.8 Bearing
1.8.3 Each bearing shall be provided with a well for thermometer in the
return line and a sight glass with illumination to observe bearing oil
flow. Redundant vibration pick-ups and transducers for bearing
shall be provided. The vibration sensors shall be installed on X
and Y dimensions. RTDs for measurement of metal temperature
and bearing drain oil temperature shall be provided.
1.8.4 Provision shall be made for hydraulic jacking of the shaft during
start up and turning gear operation.
34
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 10 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
gas pressure in the generator casing. The face of the sealing ring
shall be lined with babbitt metal.
1.9.2 The hydrogen side seal oil housing shall be provided with oil baffle
rings to prevent intrusion of seal oil into the generator along the
rotor shaft. Shaft seals and oil piping shall be suitably insulated to
prevent circulation of shaft current. Arrangement shall be made to
measure the insulation of the shaft seals while the machine is in
operation.
1.10 Fans
1.11 Brushes
1.12.1 Type
35
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 11 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.12.1.3 The various change over relays and other equipment, which are
not controlled by the control supply required by AVR shall be such
that the loss of their control supply does not lead to the excitation
system outage.
1.12.2.1 The excitation system shall have two (2) 100% channels including
independent AVR’s, power converters and controls. Each shall be
equipped for auto operation with the facility for selecting either
channel in Auto or Manual mode.
1.12.2.2 The system shall function without hunting and shall be capable of
preventing any abnormal change or oscillation in the generator
voltage.
1.12.2.3 The system shall have high initial response to improve steady state
and dynamic stability of the generator. The excitation system
response time shall be less than 0.5 sec.
1.12.2.5 The reference voltage set point shall be adjustable over a range of
70% of no load to 110% of the nominal rated voltage at MCR.
ISSUE
R0
36
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 12 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.12.2.7 The ceiling voltage shall not be less than 150% of the machine
excitation voltage at MCR condition.
1.12.2.9 The nominal exciter response ratio shall not be less than 2.
1.12.2.12 In case of failure of the PMG, the field of the main exciter shall be
transferred to the supply derived from the auxiliary 400V station
supply. This changeover shall be such that it does not result into
the tripping of the generator.
1.12.2.13 An alarm shall be generated if the difference in the set point of the
Auto-1 & Auto-2 is more than a ±0.5% with a 1sec time delay. i.e.
failure in the follow-up circuit.
37
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 13 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
38
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 14 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
ISSUE
R0
39
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 15 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
40
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 16 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.12.6.1 The pilot exciter shall be revolving field, salient pole, permanent
magnet high frequency type. The armature shall be stationary 3
phases feeding current to the static rectifier assembly and
excitation control equipment. The rotor shall be magnetized and
stabilised by the Manufacturer to give stable magnetisation
characteristic during operation.
1.12.6.2 The stator winding shall be of class ‘F’ insulation or better but its
temperature rise shall be limited to Class-B, suitable for operation
at 500C ambient temperature. The machine shall be fitted with
fans for self-ventilation.
1.12.7.1 Fully controlled three phase, full wave bridge type thyristor
converter facilitating fast and high ceiling performance shall be
provided. They shall be suitable to ensure trouble free service of
the cells under all fault conditions. The converter shall have
redundant thyristors for satisfactory operation even in the event of
failure of any of the thyristors. The thyristors shall be selectively
protected against short circuits by ultra high speed fuses. Suitable
lamp indication shall also be provided to indicate the defective
‘thyristor’.
1.12.8.2 Integrally mounted air fan shall be provided for the cooling of the
exciter.
41
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 17 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.12.9.1 The rotating rectifier assembly shall have the following essential
features :
1.12.11 Instrumentation
42
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 18 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
vi) For all alarms in the system, contacts shall be taken from the
temperature switches, etc. provided at suitable points. The
system shall be provided with transmitters for the above
indicators.
1.13.1.1 The hydrogen gas cooling system comprises a hydrogen circuit for
cooling the stator core, stator winding, lead terminal bushings and
rotor windings, carbon-dioxide scavenging system and compressed
air supply system.
1.13.1.2 The system is required to fill the generator with hydrogen, maintain
it under pressure, monitor and control gas purity and to empty the
hydrogen from generator. Also the system shall permit emptying of
the generator casing with help of CO2 purging. The design has to be
such as to ensure safe filling / emptying by preventing formation of
explosive H2 – air mixture. For filling, air is first displaced by CO2,
which in turn is replaced by H2. While emptying H2 is first displaced
by CO2 before admission of air in the machine in order to obviate
possibility of any explosion. For removing CO2, instrument quality
air supply shall be used.
1.13.1.3 The major system components are H2 and CO2 gas manifolds, CO2
heating system, hydrogen pressure regulator, H2 gas coolers, H2
drying equipment, inter-connecting pipings, fittings, valves, gauges,
thermometers, pressure transmitters and other instrumentations,
control & monitoring panel. Annunciation and electrical instruments
shall be located in a separate electric panel common with seal oil
system outside the hazardous area.
ISSUE
R0
43
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 19 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.13.1.6 The hydrogen coolers shall be provided with 10% excess tubes.
Cooler shall be designed for at least 10 Kg/sq. cm. Gauge pressure
on the gas side irrespective of a lower normal operating casing
pressure.
1.13.1.7 Corrosion resistant tubes with integral fins shall be provided and
arranged in the stator casing so as to avoid the direct fall of water
during leakage, if any, on the winding insulation. It shall be possible
to clean/plug the cooler tubes of a section with the machine under
operation.
44
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 20 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
The arrangement shall be such that one drier can be taken out of
service for reactivation without affecting the system performance in
any way. Glass indicator shall be provided to indicate humidity.
1.13.1.11 To run the gas system for short time during shut down of generator
(at standstill) for which gas circulation arrangement through drier
with blower, piping valves and accessories along with required
control equipment shall be provided. A suitable hot air blowing
system complete with blower, heater and thermostatic control etc.
shall be provided to prevent condensation during long shut down.
1.13.1.12 The design of the drier shall be such that it is possible to reactivate
the drying medium in-situ after isolation from the generator casing
and connecting it to atmosphere. Arrangement for purging out
entrapped air from the drier after regeneration shall also be
provided, as applicable. For controlling the time/regime of
reactivation, suitable thermometers, thermostats, timers etc. with a
local control panel shall be provided.
1.13.1.13 On line dew point monitoring system shall be provided across the
inlet and outlet lines to the drying system along with
alarm/annunciation in case of high moisture content in the
generator casing hydrogen.
1.13.1.15 Seamless steel tubes shall be used for valve piping. Valves shall
be glandless diaphragm type, wherever possible. The valves in gas
system shall be of special design to minimise gas leakage. Safety
relief valves shall be furnished at hydrogen manifold both on low
and high pressure sides of the gas system. A manually operated
vent valve shall be provided for discharging casing hydrogen to
atmosphere (outside the TG hall) in case of emergency. The three
way valves used along with the drier for interconnecting the
hydrogen and airline (as applicable) shall preferably have
mechanical interlocking such that closing of the hydrogen side port
is positively ensured before opening of the air side port.
1.13.2 Instrumentation
ISSUE
R0
45
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 21 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.13.2.2 Dial type thermometers for CO2 vaporiser, and gas drier. Pressure
gauges for gas cylinders, gas manifold, fan differential pressure,
generator casings, gas flow meter.
Required number of temperature, pressure and liquid level detector
switches for alarm and interlock. Necessary sensors/transmitters
for remote indication and recording in DCS.
1.13.3 Annunciation
ISSUE
R0
46
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 22 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
47
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 23 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.14.1.1 A complete seal oil supply and control system including AC and DC
motor operated pump sets, coolers, filters, pressure regulators, oil
tanks, de-gassification tanks, regulating and control valves, gauges,
thermometers and other instruments, interconnecting piping
including hangers and supports, valves and control/annunciation
panel complete with all interlocking relays shall be provided.
1.14.1.2 A shaft seal oil system shall be provided to prevent the leakage of
hydrogen from the generator casing. The seal oil, when maintained
at a pressure suitably in excess of the hydrogen gas pressure in the
generator casing shall provide an effective gas seal and shall
lubricate and cool the seals when the generator is running.
Seamless steel piping shall be used in the system. A diaphragm
operated regulating valve in the seal oil supply line shall control the
seal oil pressure by a constant amount.
1.14.1.3 The differential pressure shall be kept constant once set at the time
of commissioning, at all hydrogen pressures and all regimes of
generator operation. The pressure regulator or the regulating valve
used for the purpose shall be adjustable type.
1.14.1.4 The seal oil system shall be so designed that it is possible to run
the machine at no load in air medium at a slightly positive air
pressure without any modification in the system.
1.14.1.5 The seal oil shall be cooled in two (2) 100% capacity water cooled
heat exchangers along with necessary 3 way valves for isolating or
bringing one cooler in service. These coolers shall be shell and
tube type suitable for using DM water of condensate quality.
1.14.1.6 Seal oil coolers shall be designed to have 15% excess tube surface
area over and above designed tube surface area required for the
rated load conditions while maintaining the design pressure drop on
cooling water side. The oil pressure in the coolers shall be greater
than water pressure under all operating conditions.
48
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 24 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
for make up and also excess return and also shall serve as 100%
back up.
1.14.1.8 For the seal oil system, 2x100% capacity motor driven AC pumps
shall be provided of which one pump shall always be in operation.
Upon failure of the normal service pump due to a mechanical or
electrical fault, the standby pump shall automatically take over the
supply. On of the seal oil pumps shall be fed from the emergency
DG bus. Upon the failure of both AC driven pumps, the seal oil
supply shall be taken over by the emergency DC seal oil pump
without any interruption. The seal oil system shall thus be self-
contained. The auto starting of standby seal oil pumps shall be
interlocked with seal oil pressure.
1.14.1.9 During short time emergency, which may arise due to non
availability of both AC & DC pumps, unit may be tripped and seal oil
supply for such coasting down period shall be from a suitable
arrangement from lubrication oil system or a damper tank.
1.14.1.10 The seals shall be designed so that minimum oil enters the
hydrogen side of the machine and the oil drained from this part of
the machine passes to a suitable hydrogen detraining tank. 2 x
100% Blowers for venting out Hydrogen gas liberated from oil shall
be provided suitably mounted at places where such gas
accumulation is likely to occur. Also H2 diffusion loss through seal
oil shall be minimum to maintain H2 purity level inside generator at a
high level.
Type - Centrifugal/Twin
lobes
ISSUE
R0
49
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 25 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
MATERIAL OF CONSTRUCTION
1.14.1.12 A water detector with sight glass and drain valves shall be mounted
adjacent to the gas manifolds at the end of a pipe connected to the
bottom of the generator casing.
1.14.1.13 The oil which is used for the hydrogen sealing shall be same as the
lubricating oil for the turbine & generator bearing & governing
system.
1.14.2 Instrumentation
ISSUE
R0
50
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 26 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.14.2.1 To ensure efficient and reliable operation of the seal oil system
adequate instrumentation shall be provided. This will include the
following as a minimum: -
1.14.2.2 Local seal oil control panels shall be provided with indicators for
pump discharge pressure, seal oil pressure at the seals (for both
hydrogen and air side streams), thrust oil pressure, hydrogen / seal
oil differential pressure, seal oil flow, seal oil temperature at the
seals and status indications for seal oil pumps.
1.14.2.3 The remote instrumentation at Unit Control Room shall include seal
oil temperature recording and seal oil / H2 differential pressure
recording in DCS.
1.14.3 Annunciation
51
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 27 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.15.1.2 One (1) number primary water tank shall be provided and mounted
on the stator frame on anti-vibration pads and covered by the
generator cladding. The empty space in primary water tank may be
filled with Nitrogen to minimise water evaporation. The Bidder shall
indicate and provide devices to detect, trap, monitor and release the ISSUE
R0
52
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 28 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
hydrogen that leaks into the stator water cooling system, to a safe
place outside the building through suitable safety valves.
1.15.1.3 The make-up water for primary water system shall be tapped off
from condensate extraction pump discharge header (before and
after the condensate polisher) and from DM water make-up line to
the condenser. The level in the tank shall be maintained by means
of suitable valves in the make up line.
1.15.1.4 Two (2) 100% capacity water to water heat exchangers shall be
provided. The water-to-water heat exchanger shall be designed to
accept secondary DM water (condensate quality). The system shall
be so designed that the pressure of primary DM water inside the
cooler is always greater than that of secondary DM water
(condensate quality). The exchanger shall be designed to have
10% excess tube surface area over and above the designed
surface area required for the rated load condition while maintaining
the design pressure drop on cooling water side.
1.15.1.5 Two (2) 100% capacity fine wire mesh filters with magnet bars of
unlimited life shall be provided for removal of all magnetic particles.
The permanent magnet bars shall be protected by sleeves of
stainless steel. It shall be possible to clean easily the ferromagnetic
particles adhering to the magnet bars during capital maintenance.
1.15.1.6 Two (2) 100% capacity AC motor driven cooling water circulating
pumps shall be provided. Standby pump shall cut in automatically
in case the working pump fails or the pressure of circulating water
drops below a certain preset value.
1.15.1.7 One (1) mixed bed demineraliser (MBD) of adequate capacity shall
be provided to maintain the required quality of water. The MBD
shall remain continuously in service in order to retain high purity of
stator cooling water with its associated electrical resistivity. The
Bidder shall indicate in the proposal the capacity of MBD necessary
to maintain the quality water at the desired level for time duration of
six months or more. The system shall be designed such that the
MBD could be taken out of service for refilling without untoward
effect on the system which could necessitate load
reduction/rejection.
1.15.1.8 Alkaliser unit shall be provided alongwith stator water required for
ensuring a corrosion free operation system.
53
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 29 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.15.3 Instrumentation
54
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 30 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
55
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 31 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.15.7 Liquid leakage detector shall be provided at all the low level points
inside the generator casing including end shields along with
provisions of indication and alarm during leakage of liquid in
generator.
1.17.1 Each alarm shall be individually available on the DCS HMI whereas
set of alarms can be grouped into a group alarm on the window of
Local Control Panel. All the required relays / contacts / devices
shall be provided to achieve the same.
1.17.2 All the measurements shown in the protection and metering one
line diagram TCE.5960A-EL-SK-2002 shall be made available in
DCS and also in Local Control Panel.
1.17.4 The turbine generator control VDU in the central control room shall
have graphical display of various generator subsystems,
process/flow diagrams such as seal oil, hydrogen, lube oil,
generator stator and rotor parameters along with display of
generator capability curves and operating points, generator
temperatures and vibration parameters, etc. They shall also have
limiting values for alarm/trips, tag numbers, etc. clearly displayed on
DCS. In addition operator help features for control of these systems
and historical and reference data shall also be made available for
efficient operator guidance of these systems. All inputs including
logics for recommended control and instrumentation system
required to integrate with artificial intelligence based software’s
pertaining to generator and its auxiliary system shall be furnished.
ISSUE
R0
56
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 32 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.18.1 2 nos. Static start-up system for gas turbine unit complete in all
respects shall be offered. Additional thyristors in converter /
inverter units to take care of thyristor failure, redundancy for critical
items and self monitoring features.
1.18.2 The voltage to frequency ratio of the start-up system output shall be
maintained constant throughout the start-up and shall not lead to
overfluxing condition of generator transformer and neutral
grounding transformer. Over fluxing shall be limited to 110%.
1.18.4 The Contractor shall note that all the protection shall be set for
normal operation of the plant and the settings will not be altered
during start-up. To this extent the Contractor shall provide suitable
protections on the start-up system output to protect the generator,
CTs, VTs, etc., and cut off the start-up system in the event of
operation of these protections.
1.19 Tests
ISSUE
R0
57
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 33 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.19.1.1 The following Routine Tests shall be carried out at works on each
generator:
58
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 34 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
1.19.1.2 The field tests to be conducted on each generator at the site shall
include but not be limited to those listed below. Any other test
considered necessary by the bidder shall also be carried out :
1.19.1.3 One generator of each type and rating shall be assembled at works
and shall be tested to verify/ensure design and workmanship in
accordance with IEC-60034/VDE-0539/IEEE-43. The tests shall be
carried out keeping all conditions/parameters as close as possible
to site conditions with all the built in instrumentation (like RTD etc.)
ISSUE
R0
59
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 35 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
The test results of above shall prove that the values are within the
normal operating limits for long satisfactory performance and that
there are no components or parts, which have natural frequency of
resonance near operating frequencies or 100Hz.
1.19.2.1 The following Routine Tests shall be carried out at works on each
exciter and AVR:
60
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 36 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
c) Voltage Regulator
i) Response ratio test
ii) Insulation resistance and high voltage test
iii) Performance test at reduced supply voltage
iv) Auto –1 / Auto –2 channel follow up test
v) Auto – Manual channel follow up test
vi) Thyristor load test (light load test at rated voltage and full
current test)
vii) Functional tests
1.19.2.2 The field tests to be conducted on each AVR at the site shall
include but not be limited to those listed below. Any other test
considered necessary by the bidder shall also be carried out :
i) Accuracy test
ii) Sensitivity test
iii) Performance tests on all limiters
iv) Impulse input response test
v) Auto –1 / Auto –2 channel follow up test
vi) Auto – Manual channel follow up test
vii) Range of voltage adjustment for both auto and manual
channels
viii) Functional tests
61
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 37 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
a) SFC panels
i) Temperature rise test
b) SFC Transformer
62
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.1
SHEET 38 OF 42
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR AND ACCESSORIES TCE.5960A-H-500-001
xi) DGA test on oil before and after temperature rise test
1.19.5 All Type and Routine test certificates shall be furnished to the
Owner for review and approval.
ISSUE
R0
63
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT SECTION: D3.1
COMPANY LTD.
DATA SHEET – A3.1 SHEET 39 OF 42
SPEC. NO.
TCE.5960A-H-500-001
SL. NO. DESCRIPTION UNITS VALUES / REQUIREMENTS
1.1 Generator and Excitation System
1.25 Maximum amplitude of vibrations As per VDE 2063 and shall meet
(peak to peak) requirements as per respective
gas turbine and steam turbine
sections.
(Bidder shall indicate).
1.26 Noise level from the surface of As per IEC 60034 shall meet the
equipment requirements as per respective
gas turbine and steam turbine
sections
(Bidder shall indicate)
1.27.15 Manual control range of AVR 70% of no load to 110% full load of
voltage range
SHEET 1 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST. SPEC NO
ELECTRICAL SYSTEMS - TCE.5960A-H-500-001
GENERATOR CIRCUIT BREAKER
2.2 The voltage class of the Generator circuit breaker shall be same as
that of the generator.
2.3 The continuous current rating of the Generator circuit breaker shall
be arrived at considering the maximum output of the generator and
at specified minimum voltage.
2.8 The short time and momentary current rating of the Generator
circuit breaker shall be decided as follows:
Plus (+)
ISSUE
R0
68
TCE FORM NO. 329 R5
.
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.2
SHEET 2 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST. SPEC NO
ELECTRICAL SYSTEMS - TCE.5960A-H-500-001
GENERATOR CIRCUIT BREAKER
2.9 The basic switchgear module shall include the following minimum
equipment but shall not be limited to the same.
The accuracies of the CTs & PTs shall be as per the enclosed Main
one line diagram TCE.5960A-EL-SK-2003.
2.11 The GCB shall be of SF6, metal enclosed, indoor / outdoor and free
standing type. It shall be provided with three pole gang operation
ISSUE
R0
69
TCE FORM NO. 329 R5
.
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.2
SHEET 3 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST. SPEC NO
ELECTRICAL SYSTEMS - TCE.5960A-H-500-001
GENERATOR CIRCUIT BREAKER
2.14 SF6 gas monitor for each phase shall be provided. Necessary
interlocks are to be arranged to prevent breaker operation on fall of
SF6 gas density.
2.18 The Main One Line diagram enclosed indicates the relays and
meters to be connected to the current transformers and voltage
transformers. The VA burden, knee point voltage, secondary
resistance and the exciting currents of CTs and VA burden of the
VTs shall suit the connected metering/protective equipment.
ISSUE
R0
70
TCE FORM NO. 329 R5
.
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.2
SHEET 4 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST. SPEC NO
ELECTRICAL SYSTEMS - TCE.5960A-H-500-001
GENERATOR CIRCUIT BREAKER
2.20 Duplicate shunt opening release coils suitable for operation with
voltage upto 60% of rated voltage of coils along with status
monitoring shall be provided.
2.24 The operating mechanisum shall be spring operated both for closing
and tripping operations. The stored energy in the spring shall be
sufficient to permit at least two close-open operations. The spring
charging motor shall be suitable for 220V DC and shall be fed from
respective Unit DCDB. The spring charging motor shall be capable
of charging the spring within 30 secs.
2.26 Local control panel shall be provided near GCB to facilitate Local
ON/OFF Control, status indication, alarm and annunciation of the
breaker and all auxiliary equipments shall also be located in local
control panel. Local control panel shall include a Local/Remote
selector switch.
ISSUE
R0
71
TCE FORM NO. 329 R5
.
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.2
SHEET 5 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST. SPEC NO
ELECTRICAL SYSTEMS - TCE.5960A-H-500-001
GENERATOR CIRCUIT BREAKER
2.27 The GCB shall be suitable for synchronizing duty and capable of
withstanding out of phase voltage across open contacts. The
breaker shall also be capable of switching on to a fault and out of
phase switching.
2.28 Main contacts shall have ample area and contact pressure for carrying the
rated current and the short time rated current of the breaker without
excessive temperature rise which may cause pitting or welding.
Contacts shall be easily replaceable and shall have a minimum of
movable parts and adjustments to accomplish these results. Main
contacts shall be the first to open and the last to close so that there
will be little contact burning and wear.
2.29 Arcing contacts, if provided, shall be the first to close and the last to
open and shall be easily accessible for inspection and replacement.
Tips of arcing and main contacts shall be silver faced or have
tungsten alloy tipping.
2.34 The operating mechanism offered for GCB shall be in service for a
minimum of 2 years in any of the power plant with trouble free
operation.
ISSUE
R0
72
TCE FORM NO. 329 R5
.
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.2
SHEET 6 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST. SPEC NO
ELECTRICAL SYSTEMS - TCE.5960A-H-500-001
GENERATOR CIRCUIT BREAKER
2.35 SF6 density monitoring, alarm on low density and close & Trip
blocking on very low density shall be provided.
3.0 Tests
3.1 All acceptable & routine tests as per IEC-60056 and IEEE Std
C37.013a-2007 standards shall be conducted on all the
equipment/components of each of the generator circuit breaker.
3.2 Following type tests shall be conducted on each type & rating of the
equipment.
(ii) Test for rated closing, latching and short time current
carrying capability.
73
TCE FORM NO. 329 R5
.
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.2
SHEET 7 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST. SPEC NO
ELECTRICAL SYSTEMS - TCE.5960A-H-500-001
GENERATOR CIRCUIT BREAKER
3.3 Test reports for the following type tests shall be submitted for each
type & rating of equipment:
ISSUE
R0
74
TCE FORM NO. 329 R5
.
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.2
Technical Parameters
GCB shall comply with the technical particulars given below and the
Contractor shall furnish the details wherever indicated as ‘*’.
(d) Frequency Hz 50
(e) Rated current A Bidder to indicate
(f) Rated short circuit breaking Bidder to indicate
current kA
(g) Rated short time withstand Bidder to indicate
current for 1 sec. kA
(h) Rated short circuit making Bidder to indicate
kAp
current
(i) Degree of protection
• Control cubicles and IP 54
drives
• Enclosure IP 65
(j) Duty CO-30 min-CO
(k) Panel paint shade Opaline Green(external) ,
Semi Glossy white (internal)
ISSUE
R0
SHEET 1 OF 11
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR TRANSFORMERS TCE.5960A-H-500-001
3.2 Three (3) of 50% capacity separately mounted radiator banks shall
be provided. Each bank shall be provided with adequate number of
fans and pumps and one oil pump and one fan spare. Each radiator
bank shall be provided with uni-directional bypass valve to permit
oil to bypass the pump in the event of pump failure. It shall be
possible to completely isolate any one of the radiator banks for
maintenance, while the transformer is in service. Flexible
expansion joints, one each, on top and bottom pipe connections for
each radiator shall be provided. Each radiator bank shall have
atleast two (2) extra radiators to facilitate usage of the same in
case of leakage in the other radiators. If radiators are arranged in
groups, each group of radiator shall have upper and lower shut-off
valves with blanking at either ends. Control scheme shall be
suitable for both manual and automatic operation of each group of
fans and oil pumps.
ISSUE
R0
76
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.3
SHEET 2 OF 11
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR TRANSFORMERS TCE.5960A-H-500-001
3.4.2 The magnetic circuit shall be constructed from high grade cold
rolled non-ageing grain oriented silicon steel laminations. The flux
density shall not exceed 1.7 Wb/m2 at rated voltage and Current
density shall not exceed 3 A/mm2.
3.4.3 For generator transformers the insulation of core to bolt and core to
clamp plates shall be able to withstand a voltage of 10 kV rms for 1
minute.
3.4.5 Tank shall be made of good commercial grade low carbon steel
and shall be of welded construction.
ISSUE
R0
77
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.3
SHEET 3 OF 11
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR TRANSFORMERS TCE.5960A-H-500-001
of Hg while filling the oil under vacuum and also an excess internal
pressure of 0.35 kg/cm2.
3.4.7 Tank shields shall be such that no magnetic fields shall exist
outside the tank. They shall be of magnetically permeable
material. If required, impermeable shields shall be provided at the
coil ends. Tank shield shall not resonate when excited at the
natural frequency of the equipment. Contractor shall conform use
of tank shields in the additional information scheme.
ii) Oil filling plug and drain valve if not hermetically sealed
3.4.11 Busduct termination shall be suitable for high air temperature inside
the bus duct and shall be provided with draining arrangement as
lowest point for leaked oil / water.
3.4.12 Fire protection system shall be provided for the GTs as per the
requirement specified under relevant fire and safety
codes/standards, TAC guidelines and as specified under section
D1.11 of this specification
ISSUE
R0
78
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.3
SHEET 4 OF 11
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR TRANSFORMERS TCE.5960A-H-500-001
3.4.15 A device for measuring the hot spot temperature of the winding shall be
provided.
3.4.17 A flexible oil resistant air bag shall be provided in the conservator to
prevent the air from coming into contact with the oil.
3.4.19 A set of hydraulic jacks suitable for the transformers under supply.
3.4.22 Transformer shall be transported with tank filled with pure inert gas
at pressure of 2 – 2.5PSI. The temperature and pressure at the
time of gas filling shall be marked. Necessary accessories
including filled replenishment N2 shall be maintained at site also till
the transformer is filled with oil.
ISSUE
R0
79
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.3
SHEET 5 OF 11
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR TRANSFORMERS TCE.5960A-H-500-001
two halves, each having one power supply incomer with bus
section between two halves. In case of one power supply failure,
loads shall be automatically transferred to other. Indications are to
be provided at cooler control cabinet and at OLTC cubicle along
with remote annunciation in DCS for failure of normal source and
for transfer to standby source, and also for failure to transfer.
3.6 Each cooling fan and pump motor shall be provided with isolating
switch, starter, thermal overload, single phase preventer and short
circuit protection. Separate on/off switch for each incoming power
supply with MCCB shall be provided. All cooling equipment trouble
shall be indicated in local control panel with repeat alarm in main
control room, with remote annunciation in DCS. Status of each
cooler fan/pump shall be available in DCS.
3.7.2 The tap range shall be decided based on the voltage profile of the
grid and following shall be complied with / provided. It shall permit
operation of generator at full load and at rated terminal voltage &
p.f. over the entire range of variation of grid voltage:
(b) Block reverse tap change command during the forward tap
change in progress.
ISSUE
R0
80
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.3
SHEET 6 OF 11
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR TRANSFORMERS TCE.5960A-H-500-001
(h) Be equipped with Digital type tap position indicator with in-
built transducer for repeating the tap position in DCS.
(j) A sheet steel, dust and vermin proof marshalling box shall
be provided for each transformer and shall be provided with
thermostatically controlled space heaters. The degree of
protection shall be IP 55. All wiring for remote connection for
OLTC control / indication / annunciation from OLTC cabinet
shall be terminated in Marshalling box by providing separate
terminal block.
3.8 Tests
3.8.1 Following type tests and special tests as per IS 2026 (revision as
applicable on date of submitting of offer) shall be conducted on
one transformer :
ISSUE
R0
81
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.3
SHEET 7 OF 11
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR TRANSFORMERS TCE.5960A-H-500-001
(a) Temperature rise test, Dissolved gas analysis of the oil, before
and after the temperature rise test.
(b) Vacuum withstand and deflection measurement on tank and
radiators.
(c) Pressure test on tank with deflection measurement.
(d) Determination of cooler losses.
(e) Partial discharge test.
(f) Radio influence voltage.
(g) Short circuit impedance of each limb with single phase
voltage from each HV & LV sides.
(h) Oil leakage test – 12 hours (this test to be conducted after
heat run test).
(i) Auxiliary power measurement.
3.8.2 All routine tests as per IS : 2026 shall be conducted on each of the
transformer. The following additional routine tests on each of the
transformer shall be conducted.
ISSUE
R0
82
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.3
SHEET 8 OF 11
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
GENERATOR TRANSFORMERS TCE.5960A-H-500-001
3.11.1 Bids will be evaluated based on the formula furnished in Data Sheet-
A3.3
3.11.2 For the purpose of evaluation of Bids, the quoted load losses and
iron losses shall be included to take into consideration tolerance as
permitted by applicable standards.
ISSUE
R0
83
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY SECTION: D3.3
LTD.
DATA SHEET – A3.3 SHEET 9 OF 11
GENERATOR TRANSFORMER SPEC NO:
TCE.5960A-H-500-001
SL. NO. DESCRIPTION UNITS VALUES / REQUIREMENTS
1.0 Generator Transformers
- HV Star
- LV Delta
- Vector Ynd1
- LV * / *
0
1.6 Maximum temperature rise of oil at 110% of C 50
full load for 24 hrs.
0
1.7 Maximum temperature rise of winding at C 55
110% of full load for 24 hrs.
A = Rs. 3,80,000 / kW
B = Rs. 2,60,000 / kW
C = Rs. 2,32000 / kW
1.12.2 Rates of liquidated damages for exceeding the
guaranteed losses
No load loss Rs/kW A = 3,80,000
Load loss Rs/kW B = 2,60,000
Load loss Rs/kW C = 2,32000
SHEET 1 OF 3
The Unit Auxiliary Transformer (UAT) and its accessories shall conform to
the latest editions of national and international standards indicated in
Data sheet - A 3.4. Also, the UAT and its accessories shall comply with
the requirements indicated in Data Sheet–A3.4 and specific requirements
indicated below:
4.1 UAT shall be a * MVA, */6.9kV, three phase, two winding, 50 Hz,
ONAN/ONAF cooled transformer with *% impedance with OLTC ±10% in
steps of 1.25% on HV side (*By Bidder). 6.6kV system shall be suitable
for medium resistance earthing with earth fault current limited to 300A.
4.2 Impedance
4.3.1 UAT
Each UAT shall be able to supply (100%) auxiliary running load of 700
MW power plant. It shall be able to start the largest motor at 80% base
load. The Contractor shall provide the design calculations for arriving at
the capacity of UAT during detail engineering stage. Additional margin of
10% shall be kept over & above all the loads due to variation in the loads
i.e. 110% of the complete station load.
4.4.1 The unit auxiliary transformers shall comply with the specific
requirements indicated in Section D-3.3 except for the following
variations.
4.4.1.1 The tank cover for the UAT can be of conventional type.
4.4.1.2 The UAT shall be provided with 2 x 50% detachable built on radiator
banks and if it is not possible to have built on radiator banks, the same
can be separately mounted. Each radiator bank shall have at-least two
extra radiators for use in case of leakage in any other radiator.
87
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT SECTION : D 3.4
COMPANY LTD.
DATA SHEET – A 3.4 SHEET 2 OF 3
UNIT AUXILIARY TRANSFORMER .
SPEC NO.
TCE-5960A-H-500-001
SL. NO. DESCRIPTION UNITS VALUES / REQUIREMENTS
UAT
1.0 Type Outdoor, two winding
- LV kV 6.9
- HV Delta
- LV Star
- Vector group Dynll
- HV */*
- LV 60 kVP / 20 kV (rms)
- HV (n) ---
0
7.0 Maximum temperature rise of oil C 50
0
8.0 Maximum temperature rise of winding C 55
13.1 Formula for evaluation of Bids Evaluated price + (A x guaranteed no-load loss
A = Rs. 3,80,000 / kW
B = Rs. 2,60,000 / kW
C = Rs. 2,32000 / kW
SHEET 1 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - BUS DUCTS SPEC. NO.
TCE.5960A-H-500-001
The Isolated phase bus duct (IPBD) and its accessories shall conform to
the latest editions of national and international standards indicated in
Data sheet – A 3.5 IPBD. Also, the IPBD and its accessories shall
comply with the requirements indicated in Data Sheet–A 3.5 and specific
requirements indicated below:
5.1 Isolated phase bus duct forming the main current carrying leads shall be
used in following circuits:
5.1.2 Tap-off bus duct for Unit Auxiliary Transformers in the case of GTG.
5.1.3 Tap-off bus ducts for VT and SP cubicle, static excitation transformer (if
applicable)
5.1.5 The CTs etc., to be located in the Isolated phase bus duct shall be as per
the enclosed Main one line diagram – Drg. No. TCE.5960A-EL-SK-2003.
Current transformers as required shall be located in the above bus duct.
5.1.6 If the generator transformer is three numbers single phase units, then the
delta formation of the LV Windings shall be carried out with Isolated Bus
Duct.
(a) Upto 12 kV 12 kV
ISSUE
R0
90
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.5
SHEET 2 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - BUS DUCTS SPEC. NO.
TCE.5960A-H-500-001
5.2.1 Sizing of the bus duct shall be arrived based on the continuous and short
time rating of the respective circuit.
5.2.2 The continuous current rating of the main (generator) bus duct shall be
arrived at considering the maximum output of the generator and at
specified minimum voltage.
5.2.3 Short time current rating of the main busduct shall be for 1 second and
shall be decided as follows:.
Plus (+)
(b) Momentary current rating shall be 2.55 times the short time
current rating arrived as above.
5.2.4 The short time and momentary current rating of all tap-off bus ducts (to
VT and SP cubicle) shall be as follows:
Plus (+)
5.2.5 The bus duct shall be designed to withstand the internal or external
forces resulting from the following:
ISSUE
R0
91
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.5
SHEET 3 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - BUS DUCTS SPEC. NO.
TCE.5960A-H-500-001
5.2.7 The degree of protection shall meet the requirements of water and air
tightness test specified in IS-8084 and the degree of protection shall be
IP-55 or better. The outside of the busduct shall be painted with 631 of
IS-5.
5.3.1 The bus enclosure shall be of continuous bonded type. The material of
bus conductor & enclosure for main run shall be Al alloy grade 19501
(H2) of IS-5082. The material of bus conductor for tap-off shall be Al
alloy grade 63401 WP (range 2) & for enclosure material shall be Al alloy
grade 19501 (H2).
5.3.3 The outdoor portion of the bus duct shall take into account heating effect
due to solar radiation and shall be provided with a continuous rain hood
of non-magnetic material suitably supported from the bus duct support
structure.
5.3.4 The bus conductor shall be given a coat of matt black paint to facilitate
heat dissipation. However, the sizing of the bus conductor shall consider
the conductor as bare.
ISSUE
R0
92
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.5
SHEET 4 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - BUS DUCTS SPEC. NO.
TCE.5960A-H-500-001
5.3.9 The bus conductor shall be designed for welded connections except at
equipment terminations, bolted disconnect links, and bolted flexible.
Detailed welding procedure adopted by the manufacturer should be
furnished along with the offer and approved by the Owner.
5.3.10 Flexible connections shall be provided between bus sections to allow for
expansion and contraction of the conductor. Flexible connections shall
also be provided at all equipment terminations.
5.3.12 The bus support insulator shall be interchangeable, high strength & fine
glazed porcelain manufactured by wet process or high strength epoxy
resin cast. The voltage rating shall depend upon generation voltage.
5.3.13 The spacing of the bus support insulators shall be considered by giving
due factor of safety to withstand the forces due to the momentary short
circuit assigned for the bus duct.
5.3.14 Wall frame assembly and seal-off bushings shall be provided where the
bus duct passes from indoor to outdoor area to prevent condensation
due to air temperature variation between indoor and outdoor portion.
Wall frame assembly shall be fabricated out of aluminium angles and
sheets. It shall be ensured that no load of the bus duct is imparted on
the walls.
5.3.15 The bus duct supports shall be fabricated from standard steel sections.
The support structures shall be hot dip galvanised.
5.3.17 Duplex RTD shall be provided for measurement of ambient air inside the
bus duct. The same shall be hooked upto the DCS.
ISSUE
R0
93
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.5
SHEET 5 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - BUS DUCTS SPEC. NO.
TCE.5960A-H-500-001
5.3.19 If the material of bus conductor and that of the equipment terminal is
different, then suitable bi-metallic connectors shall be provided by the
Contractor.
5.3.20 The electrically continuous bus enclosure shall be used as the grounding
bus. All parts of the bus enclosure, supporting structure and equipment
frames shall be grounded to earthing mat.
5.3.24 Silica gel filters shall be provided both in indoor and outdoor portions of
the bus duct for absorption of moisture.
(b) One set of seal-off bushings shall be provided in the bus duct
after the generator bushings to prevent hydrogen leakage into
the bus duct. Arrangement shall be provided to vent the trapped
hydrogen in the portion between generator bushings and these
seal off bushings (applicable for hydrogen cooled generators).
ISSUE
R0
94
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.5
SHEET 6 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - BUS DUCTS SPEC. NO.
TCE.5960A-H-500-001
5.3.27 All steel supporting structures and hardware shall be hot dip galvanised
after fabrication.
5.4 Pressurisation System
5.5.1 The current transformers shall be epoxy cast-resin, single core ring type,
mounted within the bus duct enclosure and suitable for operation at an
ambient temperature existing within the bus duct enclosure which may
be in range of 900C to 1000C. Mounting arrangement of CT shall be so
designed so as to avoid equalizing connections between live conductor
and CT inner surface.
5.5.4 Protection CTs shall be rated for 5A secondary current and shall be of
Class PS & Class 5P20. Metering CTs shall be rated for 5A secondary
current and shall be of 0.2S accuracy class with instrument security
factor less than 5.
5.6 Voltage Transformer and Surge protection Cubicles
5.6.1 The V.T and S.P cubicles for each phases shall be metal clad, dust and
vermin proof, free standing, dead front assemblies housing VTs, surge
capacitor, lightning arrester, V.T. L.V. side fuses etc.
ISSUE
R0
95
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.5
SHEET 7 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - BUS DUCTS SPEC. NO.
TCE.5960A-H-500-001
5.6.3 A discharge counter along with the ampere meter shall be provided for
each lightning arrester. The discharge counter register & leakage
current measurement meter with suitable environmental protection
covering, shall be visible without having to open the compartment door.
5.6.4 Mineral oil filled/Askarel (PCBS) filled surge capacitor shall not be
acceptable.
5.6.5 The voltage transformer shall be epoxy cast-resin type, suitable for
nominal voltage operation, connected from line to ground, and as per
Technical Parameters given in the specifications.
5.6.6 The secondary side of voltage transformer shall be provided with MCB.
Suitable guide slots and stops shall be provided to ensure easy
withdrawal and positioning. The fixed and draw out contacts of voltage
transformer primary shall be tinned or silver plated.
5.7.1 All cubicle shall be fabricated from cold rolled sheet steel for minimum
2mm thick suitably reinforced to ensure structural rigidly. The degree of
ISSUE
R0
96
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.5
SHEET 8 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - BUS DUCTS SPEC. NO.
TCE.5960A-H-500-001
protection for all indoor cubicle shall be IP:52 except for neutral
grounding resistor enclosure which shall be minimum IP:23.
5.7.3 Each cubicle shall be equipped with space heater with thermostat,
internal illumination lamp, 230 V AC, 5A receptacle. Ground bus
suitable for receiving two (2) numbers of 50x6mm galvanised steel flats
shall be provided on each cubicle.
5.8 Wiring
5.8.1 All wiring shall be done with insulated stranded copper conductor of not
less than 2.5 mm² cross-section with suitable lugs on both sides.
5.8.2 The wiring inside the bus duct enclosure (i.e. for CT etc.) shall be
suitable for operating in the ambient temperature existing inside the bus
duct.
5.8.3 Not more than two wires shall be connected to a terminal. Spare
terminals equal in number to 20% of active terminals shall be furnished
and these shall be uniformly distributed through out the cubicle CT
terminal blocks shall be of stud type and suitable for round type lugs with
a facility for isolation, shorting and grounding. It shall be Elmex type
CATD or equivalent.
5.9.1 Name plates shall be furnished for each equipment, disconnect link,
voltage transformer compartment, lightning arrester compartment and
fuse block, current transformer TB, etc.
5.9.2 Material for nameplate shall be embossed on SS plate & letters filled
with indelible black ink.
5.10.1 Suitable facility shall be provided to blow hot air into the bus duct to
evacuate moisture inside the bus duct during initial start-up and also
after subsequent shutdowns for maintenance on the bus ducts.
ISSUE
R0
97
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.5
SHEET 9 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - BUS DUCTS SPEC. NO.
TCE.5960A-H-500-001
5.10.2 The hot air blowing system shall be open loop type, capable of blowing
hot air simultaneously in the indoor and outdoor portions of the bus duct.
The system shall be suitable for operation at low voltage 3 phase AC
supply indicated under project information.
5.10.3 Ambient air will be drawn in through inlet dampers and dry air filters and
then forced through thermostat controlled heaters. Hot air shall be
distributed by properly sized ducts and dampers to the indoor and
outdoor portions of the bus duct. Hot air shall be let out through suitably
directed outlets provided at the indoor and outdoor portions of the bus
duct and at each equipment suitably.
5.10.4 The hot air blowing system shall be complete with motor blower unit,
combination starter, washable filters, necessary ducting, piping,
dampers, valves, heaters, thermostats, control, instrumentation and
monitoring system, all mounted on a mobile trolley.
5.10.5 A local control cabinet mounted on the trolley, shall be provided with the
necessary control, indication and monitoring devices.
5.10.6 The system shall be sized to completely dry the entire bus duct
installation within two hours. Suitable provision shall be made to isolate
this system after the drying operation is complete.
5.10.7 The mobile trolley shall be common for the specified number of bus duct
units. The bus duct of each unit shall be provided with suitably supported
inlet ducting with blanking plates.
5.10.8 The tap off air ducting from IPB to mobile trolley delivery flange is
included in Bidder’s scope of supply.
ISSUE
R0
98
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.5
SHEET 10 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - BUS DUCTS SPEC. NO.
TCE.5960A-H-500-001
f) Water-tightness test
b) IR measurement
5.12 Bidder shall furnish the following calculations for main run and tap off
run busduct.
a) Conductor size
c) Supporting span
ISSUE
R0
99
TCE FORM NO. 329 R5
5.2
SHEET 11 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - BUS DUCTS SPEC. NO.
TCE.5960A-H-500-001
5.13.1 7.2 kV class segregated phase bus duct and accessories shall be
provided for connection of the two winding unit auxiliary transformer to
6.6 kV switchgear.
5.13.2 The continuous rating of the bus duct from UAT to 6.6 kV Switchgear
shall be same as the rated current of 6.6 kV switchgear bus.
5.13.3 The short time and momentary current ratings of the bus ducts shall be
same as that of associated 6.6 kV switchgear.
5.14.1 1.1 kV class non-segregated phase bus duct and accessories shall be
provided for connection between all service transformers and their
respective 400V switchgear. NSPBD shall also be considered for
connections between other switchgear / MCCs to suit the layout.
5.14.2 The continuous rating of the bus duct shall be same as the rated current
of respective switchgear bus.
5.14.3 The short time and momentary current ratings of the bus ducts shall be
same as that of associated 400V switchgear.
5.14.4 The busbars in the bus-duct shall be sleeved with FRLS heat shrinkable,
colour coded XLPE sleeves.
5.15.1 The bus conductor shall be of Aluminium alloy grade 63401 WP (range
2) as per IS: 5082.
5.15.2 The enclosure shall be rectangular and shall be made of aluminium alloy
sheets for SPBD and for NSPBD the same shall be of mild steel.
ISSUE
R0
100
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.5
SHEET 12 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - BUS DUCTS SPEC. NO.
TCE.5960A-H-500-001
5.15.4 Flexible expansion joints shall be provided for the conductor and
enclosure along the run of the bus duct length to take care of expansion.
Also flexible joints shall be provided at the termination points.
5.15.6 The outdoor portion of the bus duct shall be provided with a continuous
rain hood of non-magnetic material suitably supported from the bus duct
support structure.
5.15.7 The bus conductors shall be given a coat of matt black paint to facilitate
heat dissipation. However the sizing of the bus conductor shall consider
the conductor as bare.
5.15.8 The adjacent sections of the bus conductor shall be welded or bolted.
5.15.9 The joints along the conductors shall be of highest quality and the
temperature rise test shall be conducted including the joints.
5.15.10 The bus support insulators shall be of 7.2 kV class (as required) for
segregated phase bus ducts and 1.1 kV class for non-segregated phase
bus ducts and shall be mounted on resilient pads.
5.15.12 The spacing of the bus support insulators shall be considered by giving
due factor of safety to withstand the forces due to the momentary short
circuit current assigned for the bus duct.
5.15.13 Wall frame assembly and seal off bushings shall be provided where the
bus duct passes through walls (indoor to indoor). These shall be
fabricated out of aluminium angles and sheets. Wall frame assemblies
with seal off bushing shall be provided where bus ducts pass through
walls (outdoor to indoor).
5.15.14 The bus duct supports shall be fabricated from standard steel sections.
The support structures shall be hot dip galvanised.
ISSUE
R0
101
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.5
SHEET 13 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - BUS DUCTS SPEC. NO.
TCE.5960A-H-500-001
5.15.16 At the factory, on one typical section of SPBD containing bends, joints
etc., following type tests shall be conducted
5.15.17 On all the pieces of SPBD & NSPBD applicable routine tests shall be
conducted. Also, test certificates shall be furnished for bought out items.
5.15.18 HV voltage test, air tightness test and water tightness tests shall be
conducted at site on fully assembled bus duct.
5.18.2 Typical calculation for arriving at the size of the conductor and the
insulator spacing.
ISSUE
R0
102
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.5
SHEET 14 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - BUS DUCTS SPEC. NO.
TCE.5960A-H-500-001
5.18.4 Type test report (short circuit, impulse withstand, temperature rise test)
for similar bus duct manufactured by the proposed manufacturer.
ISSUE
R0
103
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT SECTION: D3.5
COMPANY LTD.
SHEET 15 OF 15
DATA SHEET – A 3.5 SPEC. NO.
TCE.5960A-H-500-001
0
3.1 Conductor (Hot spot) C 55
0
3.2 Enclosure (Cold spot) C 30
5.0 Creepage distance for insulators and bushing 25 mm/kV of rated voltage
6.0 Voltage of :
104
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.6
SHEET 1 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – GENERATOR, GENERATOR
TRANSFORMER AND UAT PROTECTIONS SPEC. NO.
TCE.5960A-H-500-001
6.3.1 The protection philosophy of every equipment shall be divided into two
100% groups namely two main protection groups. Complete protection of
the respective equipment shall be fully available even if either of the
group is not available. Hence, both groups shall be mechanically,
physically and electrically separated into two separate and independent
systems. One group shall be receiving all AC and DC signals from one
set of devices and the other from another set of devices. Similarly, these
two groups will derive DC supply from two separate feeders. However,
the relays in each group shall be tripping the circuit breaker through both
trip coils I & II. Monitoring devices such as supervision of DC supplies,
supervision of protective relays, supervision of trip relays, CT and PT
supervision and supervision of both trip circuits shall be provided. Dead
machine protection shall receive their DC power supply from station
DCDB as appropriate.
6.3.2 The generator protection system relays shall be classified into three
categories viz., Class – A trip shall be classified into GCB & field breaker
trips (Class-A1) and GT HV breaker Trip (Class-A2). Class-B shall trip
GCB or GT breaker on reverse power through Class A1 or A2. Class- C
shall trip GT HV circuit breaker. Both groups of protection shall be divided
into these three modes of tripping.
6.4.3 The breaker failure relays connected with 400 kV generator transformer
bay and relays connected with 400 kV bus bar protection shall be housed
in separate relay panels which will form part of 400 kV switchyard
protection system.
ISSUE
R0
105
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.6
SHEET 2 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – GENERATOR, GENERATOR
TRANSFORMER AND UAT PROTECTIONS SPEC. NO.
TCE.5960A-H-500-001
6.4.4 The protections envisaged in GRP are listed below. Also, Main One Line
Diagram drg. No.TCE.5960A-EL-SK-2003 indicates various
protections envisaged. Both the list and the drawing shall be considered
Complementary to each other and all the protections indicated shall be
provided. Contractor shall include any additional protections deemed
necessary by him for the equipment offered even if not indicated in the list
and the drawings.
(d) Generator stator 95% back-up earth fault protection (64 G3).
It shall have a definite time stage for alarm and inverse stage for
trip. In addition they shall have an output of 4-20 mA for remote
indication of negative phase sequence current.
ISSUE
R0
106
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.6
SHEET 3 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – GENERATOR, GENERATOR
TRANSFORMER AND UAT PROTECTIONS SPEC. NO.
TCE.5960A-H-500-001
(p) Islanding protection schemes to isolate power plant from grid for
disturbances in the grid.
(u) Local breaker back up protection (50 LBB) with it’s own trip relay.
ISSUE
R0
107
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.6
SHEET 4 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – GENERATOR, GENERATOR
TRANSFORMER AND UAT PROTECTIONS SPEC. NO.
TCE.5960A-H-500-001
• GT cooler trouble
• GT OLTC trouble
ISSUE
R0
108
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.6
SHEET 5 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – GENERATOR, GENERATOR
TRANSFORMER AND UAT PROTECTIONS SPEC. NO.
TCE.5960A-H-500-001
(bb) UAT – Buchholz (63), winding temperature (49 WT) and oil
temperature (49 OT) protections
(gg) High speed trip relays (86 G1 to GX): Adequate number of high
speed trip relays for each category tripping and separately for
each group shall be provided for the protection of the unit. The
quantity of the trip relays shall also consider the requirement due
to the following:
ISSUE
R0
109
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.6
SHEET 6 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – GENERATOR, GENERATOR
TRANSFORMER AND UAT PROTECTIONS SPEC. NO.
TCE.5960A-H-500-001
(ll) Auxiliary VTs and Auxiliary CTs required for the protection
systems. The parameters of the same shall be selected to suit
the application and the same is subject to approval of Owner.
6.6 The characteristics and relay setting ranges shall be decided by the
Contractor and shall be such as to provide complete protection for the
generator under normal and all abnormal operating conditions.
6.7 Trip Matrix required for implementing class A/B/C tripping schemes shall
be provided by the Contractor and shall be indicated in block interlock
diagrams to be submitted.
6.8.2 Two Nos. DC supplies shall be arranged for the GRP. These supplies
shall be taken through a selector switch with the positions, viz.,
independent, source-1 & source-2. In the Independent position Group-1 &
2 protection system will be fed by source 1 & 2 respectively and the
common services from any one of the sources. In case of failure of any
one source (say source 1) switch shall be changed over to the other
source (source 2) and complete DC supply requirement of GRP will be fed
from the other source.
6.8.3 The relay panels shall be provided with supervisory system facilities to
indicate the location of the failed component when pre-engineered
ISSUE
R0
110
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.6
SHEET 7 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – GENERATOR, GENERATOR
TRANSFORMER AND UAT PROTECTIONS SPEC. NO.
TCE.5960A-H-500-001
6.8.4 Either hand reset mechanically operated operation indicator or LED with
reset push button shall be provided for protective relays. They shall be
arranged to operate only when tripping current passes through output
circuit of the relay.
6.9 In addition to the contacts required as per schemes, Contractor shall wire
out to the terminal block atleast all NO & NC spare contacts of each of the
relays.
6.10 The protection scheme shall include all the necessary contacts to achieve
the schemes required, alarms in Operator Station, annunciation windows,
sequence event recorder and for switchyard control panel annunciation
wherever required. Contact multiplication relays for generator circuit
breaker and associated isolators shall be provided for this purpose.
6.11.1 Two Nos. of test kits shall be offered to test all of generator, transformer,
line and motor protection relays, timers by secondary injection. This is in
addition to self monitoring and watch dog facilities that will be built into
these protective relays.
111
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.6
SHEET 8 OF 8
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – GENERATOR, GENERATOR
TRANSFORMER AND UAT PROTECTIONS SPEC. NO.
TCE.5960A-H-500-001
6.14 Tests
ISSUE
R0
112
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 1 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
7.2 The 400 kV switchyard shall have one and a half breaker switching
scheme. The Main One Line Diagram sketch no. TCE.5960A-EL-SK-
2003 shows the switchyard scheme and arrangement of major
equipment in the switchyard.
7.3 The 400 kV switchyard shall consists of various bays for different
configuration as follows:
7.4 The switchyard equipment shall be supplied and installed with all
accessories to make the switchyard complete in all respects. The
switchyard shall include the equipment indicated below but not limited to
the following.
ISSUE
R0
113
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 2 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
7.4.9 SCADA (Supervisory Control and Data Acquisition) system for entire
switchyard with bay control units for each bay including event logging.
7.4.11 Stand alone disturbance recorders with associated network cabling, PC,
HMI, Printer and evaluation software.
7.4.12 ABT (Availability Based Tariff) meters including necessary software &
hardware for monitoring on dedicated PCs with suitable networking.
7.4.13 RTU (Remote Transmission Unit) for transfer of data to SLDC (State
Load Dispatch Centre) and RLDC (Remote Load Dispatch Centre).
7.4.15 Air conditioning and ventilation system for control building and outdoor
kiosks.
ISSUE
R0
114
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 3 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
7.5.3 The switchyard main buses shall be designed for continuous rating.
Bay buses shall be rated according to the circuit rating. The switchyard
shall be designed for a fault level of 50 kA for 1 sec. and dynamic rating
of 130 kA.
7.5.4 The 400 kV system shall be designed to withstand the power frequency
over voltage to 1.5 p.u and surge over voltage to 2.3 p.u. The busbars
shall be of standard ACSR or tubular aluminium / copper according to
standard metricised iron pipe size (IPS) of suitable size.
7.5.5 The conductor size of tubular bus and stranded conductors shall be
based on the maximum load current, suitability under short circuit
conditions, corona / voltage gradient and effect of solar radiation.
Calculation shall be submitted for Owner’s approval.
7.5.6 The final temperature of the conductor when carrying full load current
shall not exceed 850C with a maximum ambient temperature of 500C.
7.5.7 The size and spacing of strung bus, tubular bus and clamps
connections shall be checked to limit the voltage gradient to 17 kV/cm to
reduce corona effect.
7.5.8 The size of shield wire shall be based on the lightning impulse current
expected and the time duration for which it is likely to flow. Allowance
shall be given in the final size to account for corrosion of the shield wire
during service at rate of 0.03 mm per annum, if galvanised steel wires
are used. However, minimum size of the shield wire shall not be less
than 70mm2.
7.5.9 Insulators
(b) All ferrous parts shall be hot dip galvanized. The associated
metal part shall be permanently secured to the insulator, air tight
and shall be designed to withstand all shocks and stresses to
which they may be subjected to during operation and
maintenance.
ISSUE
R0
115
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 4 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(h) Bus post insulators shall be solid / post insulator anti-fog type and
shall be selected based on the system voltage, insulation level
mechanical strength and pollution level requirements.
7.5.11 The criteria for deciding phase to phase clearance in case of strung
conductors shall take into account that the conductor swing of one of
the conductors (say R phase) with maximum wind velocity and the
adjacent conductor (say Y phase) with 80% of maximum wind velocity
at maximum sag conditions.
ISSUE
R0
116
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 5 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
7.5.12 For the layout proposed by the Contractor the adequacy of the
cantilever strength specified shall be checked considering the following
factors of safety.
(a) Sum of all permanent normal loads (wind load on tubular bus +
wind load on stack + dead weight of the tubes) x 2.5 (factor of
safety).
(b) Combination of all normal loads plus either maximum short circuit
or earthquake load whichever is higher x 1 (factor of safety).
7.5.13 The switchyard shall be designed for the seismic coefficient and wind
pressure as indicated in Section-B.
7.5.14 All structural steel and steel components in the switchyard equipment
shall be of hop dip galvanised.
7.6.1 The Contractor shall adopt bolted type connectors for tubular bus
conductors, fixed type of terminal connectors for isolator terminals,
flexible type of terminal connector for circuit breakers, current
transformers and power transformers and flexible jumper connectors for
connecting lightning arresters and voltage transformers.
7.6.2 The Contractor shall consider suitable bay width, phase spacing,
clearances, etc., depending on the actual dimensions of the equipment
keeping in view the design criteria / requirements and without sacrificing
any maintenance space / conveniences.
7.6.3 In the transformer yard, the power conductor termination shall not be
tapped off directly to the Generator transformer from the strung bus
between the TG building and switchyard. The tap off conductor shall be
routed through a bus post insulator located near the transformer.
7.6.4 The Contractor shall note that the sequence of bays shall be so
arranged that the maximum horizontal angle of deviation of the
incoming power and shielding conductors from Generator transformers
do not exceed 300C. Similarly, the point of anchoring on TG building
shall be such that the vertical angle of deviations is limited to 300C from
horizontal plane.
7.6.5 The switchyard shall be provided with access ways near the current
transformers and circuit breakers.
ISSUE
R0
117
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 6 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
7.6.6 The cable trenches for the equipment shall be run as close to their
foundations as possible even preferably touching.
7.6.7 The switchyard shall be enclosed in fence or wall around for safety and
to prohibit unauthorised persons from entering. Lockable gates for
personnel entry and equipment shall be provided at convenient
locations.
7.6.9 Earth mat of suitable size with closely spaced earth conductor shall be
provided below the operating handle of individual switchyard equipment
As per the allowed step & touch potential values in IS.
7.6.10 Design criteria for civil works and structures shall be as specified in
Section-D4.0, civil works.
7.7.1.1 (a) The 420 kV circuit breakers shall be of SF6 outdoor type. The
circuit breaker and its accessories viz. marshalling box / junction
box shall be with IP 55 degree of protection.
(b) The SF6 circuit breakers shall be single pressure type and utilise
puffer cylinder for interrupting currents. The breaker shall be so
designed that upon loss of pressure, the gap between open
contacts shall be suitable to withstand at least rated voltage at zero
gauge pressure of gas. Each SF6 circuit breaker pole shall be
provided with its own self-contained gas system.
(c) The circuit breakers shall comprise three identical single phase
units with operating mechanism suitable for single pole operation.
ISSUE
R0
118
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 7 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(e) Design of circuit breaker shall be such that contacts shall not close
automatically upon loss of gas / air pressure.
(g) The operating mechanism shall also have pressure switches for
low alarms, high alarm, trip, lock out switches for close, open and
reclose operation.
(h) D.C. circuits for two trip coils shall be separate and each of them
shall be monitored separately.
(i) Manually operated emergency trip push button or any other device,
conveniently located for mechanical tripping of all the three phases
simultaneously shall be provided.
(k) Circuit breakers shall be suitable for rapid auto re-closing duty.
(l) All the circuit breakers in the switchyard shall be of identical make
and type with interchangeable components to maximum possible.
(m) The middle breakers and the outgoing line breakers shall be
provided with PIR.
(ii) Two trip coils shall be provided for greater reliability. The trip
coils shall have sufficient continuous rating to cater to the trip
coil supervision relay current.
ISSUE
R0
119
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 8 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(iii) Separate pole discrepancy circuit with proper relay and other
accessories shall be provided. Disagreement circuit shall be
provided which shall detect pole position discrepancy.
7.7.1.3 One set of SF6 gas filling, evacuation and refilling equipment consisting
of trolley mounted compressed SF6 cylinder, gas regulator with
manometer and necessary coupling for filling gas in the breaker shall be
provided. The equipment shall be trolley mounted. 2 nos. of gas leak
detector shall be included in the scope of supply. Detectors shall be of
reputed make and have Visual as well as Audible sound facility when
leakage is detected. Contractor shall supply spare SF6 gas equal to
20% of the total requirement for the station.
7.7.1.4 All circuit breakers controlling the lines shall be provided with either
closing resistors or proven controlled switching devices to reduce over
voltages and in-rush currents.
7.7.1.5 All routine tests on the circuit breakers shall be carried out as per IEC-
62271-100. Type test certificates for all tests carried out on identical
circuit breaker as per IEC-62271-100 shall be furnished.
(b) Isolators & Earth switch shall be suitable for operation on 400V, 3
phase, AC motor. However, it shall also be possible to operate
them manually in the event of failure of power supply or outage of
the drive motor with proper interlock provision for isolation of motor
in case of manual operation. Earth switches shall be motor
ISSUE
R0
120
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 9 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(d) The design of the auxiliary switches for the isolators shall be such
that signalling of the closed position shall not take place unless the
contact system has reached such a position that the rated current
and the rated short time current can be carried safely; signalling of
the open position shall not take place unless the contact system
has reached a position of at least 80 percent of the clearance
distance of the isolating distance. Contacts used for CT switching
shall make before the isolator closed and starts carrying current.
Similarly they shall open after isolator opens and breaks the
primary current.
(f) The isolator and earthing switch shall be provided with high current
carrying contacts on the hinge and jaw ends and all contact
surfaces shall be of silver faced copper.
(g) Each pole of the isolator shall be provided with two earthing pads
of non-corrodible material at opposite ends, brazed to the channel
base. Flexible copper earth connectors shall be provided for
connecting operating handles of isolators and earthing switches to
the earthing system. The poles of the isolators shall be
mechanically ganged.
ISSUE
R0
121
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 10 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
ISSUE
R0
122
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 11 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(n) All routine tests as per IEC 60129 shall be carried out. Type test
certificates for all tests carried out on identical isolators as per IEC-
60129 shall be furnished.
(d) Separate CT cores for Main-1 and Main-2 Carrier aided Distance
Protection (21) for each line.
(e) The CTs and EMVTs shall be either oil filled hermetically sealed or
SF6 gas filled single phase type. The CVTs shall be oil filled
single phase type.
(f) In case of SF6 filled CTs and EMVTs, gas density monitors with
remote alarm facility shall be provided.
(g) The rated burden for the metering and protection cores shall be
decided considering all the loads/relays connected, future
additions, lead burden etc.
ISSUE
R0
123
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 12 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(h) The knee point voltage for PS class cores shall be decided
considering the total connected burden with adequate margin.
(j) The core lamination shall be of cold rolled grain oriented silicon
steel or other equivalent alloys. The cores shall produce
undistorted secondary current under transient conditions at all
ratios with specified parameters.
(k) Insulator shall be one piece without any metallic flange joint.
(l) Expansion chamber at top shall be provided with oil sight glass.
(m) Shall have provision for taking oil samples from bottom of CT
without exposure to atmosphere to carry out dissolved gas
analysis periodically.
(n) The CVT secondary shall include necessary MCBs with auxiliary
contacts for alarm for protecting the secondary winding. Further,
for the purpose of supervision on remote panel, line terminals of
the CVTs shall be brought out through second set of MCBs. All
the terminal boxes shall be powder coated with IP-55 degree of
protection.
(q) The tank/base and all exposed ferrous parts shall be hot dip
galvanised conforming to applicable standards.
ISSUE
R0
124
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 13 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(z) Neutral of all cores of CTs, CVTs and EMVTs shall be formed in
marshalling box of the respective equipment. Cables with
sufficient number of cores are run from these marshalling boxes to
protection panels. The neutral of CTs, CVTs, and EMVTs shall be
earthed only at protection panels by means of a disconnecting
link.
ISSUE
R0
125
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 14 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
a) 400 kV, 50 MVAR Three Phase Oil Filled Bus Reactors are considered in
the switchyard. However, the exact requirement for these Bus reactors will
be confirmed during detailed engineering based on the system study to be
carried out by the bidder. However, at present, the bidder shall consider
these Bus reactors in their offer.
c) The total harmonic content in the phase current of a star connected reactor
and zero sequence components appearing in the neutral shall be below
3% of the crest value of rated current.
d) The impedance of reactor shall have a constant value upto about 1.5 times
rated highest system voltage. Further the impedance shall be accurately
balanced between the three-phase system.
e) The magnetic circuit of reactor shall be so designed that the audio sound
level shall be minimum.
f) The losses of the reactor shall be limited to the values to permit ONAN type
of cooling.
k) Tank shall be made from good commercial grade low carbon steel and
shall be of welded construction.
ISSUE
R0
126
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 15 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
l) Tank shall be provided with a pressure release device which shall operate
at a pressure below the test pressure for the tank and radiators. The device
shall be rain-proof after blowing and shall be provided with a device visible
from ground to indicate operation. An equaliser pipe connecting the
pressure relief device to the conservator shall be supplied.
p) Bushings shall be of the oil-filled condenser type with a central tube and
draw-in conductor, which shall be connected to the connector housed in
the helmet of the bushings. The pull through lead shall be fitted with a gas
bubble deflector. Condenser type bushings shall be equipped The angle of
inclination to vertical shall not exceed 30 deg.
(a) Provision for power factor testing without disconnecting main leads.
(d) Bushing turrets shall be provided with vent pipes, which shall be
connected to route any gas collection through the Buchholz relay.
q) The Bushing CT’s for protection shall be provided as per the enclosed Main
One Line Diagram TCE.5960A-EL-SK-2002.It shall be possible to remove
turret mounted Bushing CT's from the reactor tank, without removing the
cover.
ISSUE
R0
127
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 16 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(ii) Shall be suitable for circuit breaker duty cycle in the given
system.
ISSUE
R0
128
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 17 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(ix) Surge monitor shall be provided for each arrester and the
same shall be mounted at a suitable height to facilitate easy
reading of the counter mechanism and leakage current
detectors.
(a) Line trap shall be of pedestal mounted, wound coil, broad band
tuned.
(b) Line trap shall prevent undue loss of carrier signal for all
conditions.
ISSUE
R0
129
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 18 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(f) Line trap shall consist of a main coil designed to carry continuously
the rated current without exceeding the limit of temperature rise
limits. It shall be equipped with bird barriers and shall be spray
painted as per IS. It shall be provided with protective device and
tuning device.
(g) Suitable corona rings shall be provided to meet corona and radio
interference performance as specified for 400kV equipment if
required.
(h) Even though the line traps shall be installed in two phases, the
foundation shall be constructed in all the three phases to facilitate
the change of location of line trap between the phases.
(c) Bolts, nuts and plain washers shall be hot dip galvanized mild steel
for sizes M12 and above. For sizes below M12, they shall be
electro-galvanized mild steel.
(e) All castings shall be free from blow holes, surface blisters, cracks
and cavities.
(f) All sharp edges and corners shall be rounded off to meet specified
corona and radio interference requirements.
(g) Shall have same current rating as that of the connected equipment
with temperature rise limited to 350C over 500C.
ISSUE
R0
130
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 19 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(a) Shall be of bolted type and forged steel except for insulator cap,
which can be of malleable cast iron.
(c) In one span, Tension string assembly at one end shall be supplied
with suitable turn buckle.
7.7.9 Spacers
(a) Shall be non-magnetic material except nuts and bolts, which shall
be of hot dip galvanized mild steel.
(c) Design shall take care of fixing and removing during installation
and maintenance.
7.8.1 Bidder shall offer air conditioned outdoor kiosks suitably located in
switchyard, housing various IEDs such as Bay Control Units (BCUs),
Protection Panels, Fault Disturbance Recorders, PLCC/OLTE Panels,
etc. However, SCADA servers and associated equipment, SCADA
Operator Station, RTU for SLDC/RLDC, DC battery, battery chargers,
ISSUE
R0
131
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 20 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
7.8.2 The control and interlocking scheme suitable for one and a half breaker
switching scheme shall be provided. Contractor shall furnish block
interlock diagrams for the switchyard for Owner’s approval. The
scheme as approved by Owner shall be provided. All the auxiliary
relays, timers, switches, hardware, etc., required for the scheme are
deemed to be included in the Contractor scope.
7.8.3 Line bays shall be provided with single phase and three phase auto
reclosing feature. The auto re-closing scheme shall be available in one
of the numerical line protection relays but shall get independently
actuated by the operation of both the protective relays. All the
necessary relays, trip relays, auxiliary relays shall be provided.
Provisions shall be made to accord higher reclosing priority to main
breakers, or to issue reclosing command to both breakers
simultaneously. Rapid reclosing & delayed reclosing features shall be
ISSUE
R0
132
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 21 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
7.8.4 Live line–dead bus closing and dead line-live bus closing facilities shall
be provided using dedicated relays for this purpose. Indicating lamps
for fulfilment of the permissive condition shall be provided.
7.8.5 Synchronizing function shall be through BCU for GTG units and a
separate synchronizing equipment along with check synchronizing
facility to be provided for STG units. Synchronising facility shall be
provided for all lines in DCS. In check synchronising position, the
synchronising criteria shall be fulfilled as indicated by the closing
permissive provided by check synchronising relay. In manual mode,
closure is possible only if either the line or the bus is dead. It shall not
be possible to close in manual mode if both line and bus are live.
7.8.6 Control and indication shall be provided for each of the breaker and
isolator.
7.8.7 The measurement requirements for each of the bays shall be as per
the Main one line drawing TCE.5960A-EL-SK-2003 and Section D2.4 -
I & C requirements.
7.8.9 All relay panels shall be located in outdoor kiosk and these kiosks shall
be located in switchyard.
ISSUE
R0
133
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 22 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
7.8.14 The Contractor shall provide licensed copy of software on CD for relay
setting software and calculations for future use of the Purchaser. Relay
setting calculations shall be furnished by the Contractor to the
Purchaser and the grid authorities for their approvals.
7.8.16 The relay settings, parameterisation and the retrieval of data from the
relay and relay operations shall be possible from SCADA operator
station in addition to the laptop. The communication between the
numerical relays and SCADA system shall be through serial link with
fibre optic cable connection. The communication protocol between the
numerical relays and SCADA system shall be IEC-61850.
7.8.17 The interlocking scheme shall be hard wired and shall be suitable for
one and a half breaker switching scheme. Contractor shall furnish block
interlock diagrams for the switchyard for Purchaser’s approval. The
scheme as approved by Purchaser shall be provided. All the auxiliary
relays, timers, switches, hardware, etc. required for the scheme are
deemed to be included in the Contractor’s scope.
ISSUE
R0
134
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 23 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
135
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 24 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(i) Local breaker back up protection with its own trip relay
(50 LBB for each breaker). LBB in-out switch shall also
be provided.
(ii) Pre and Post close Trip circuit supervision relay for
each trip circuit (98L)
f) Reactor Protection
Over Current Protection (50 and 51)
Neutral Over Current Protection (51N)
High Impedance type Differential Protection (87R)
ISSUE
R0
136
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 25 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
7.9.2 The protective relays shall be of integrated numerical type with serial
interface for communication with SCADA system. The numerical
protective relays shall be based on internationally accepted Open
Protocol IEC-61850. If any of the protections are not covered in the
main numerical relay, separate discrete
numerical/microprocessor/static relays shall be provided. All hardware,
auxiliary relays, timers etc. required for tripping/interlock schemes shall
be provided by the Contractor.
7.9.3 Numerical relays shall have self diagnostics and watch dog feature for
remote annunciation in SCADA. Protective relays shall have adequate
number of site configurable LEDs and output relays. Push buttons for
testing and resetting the LEDs shall also be provided. All protective
relays and meters shall be provided with test terminal blocks for
secondary injection testing of protection relays and meters. In addition
to the contacts required as per the schemes, Contractor shall wire out
to the terminal block at least one NO & one NC spare contacts of each
of the relays.
7.9.4 The protection schemes shall include all the necessary contacts for
interlocks, alarms in SCADA, sequence event recorder wherever
required. Contact multiplication relays for 400kV circuit breakers and
associated isolators shall be provided for this purpose.
7.9.6 All numerical relays and SCADA clock shall be time synchronised with
the GPS master clock. The contact rating of contactors provided in
SCADA Panels shall be suitable for making/breaking of control circuit
currents of the respective devices being controlled.
ISSUE
R0
137
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 26 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
7.10.2 The controller shall be configured with redundant CPU. The redundant
CPU shall be configured to operate as hot standby. The SCADA
system shall be generally in line with the details shown in SCADA
System Configuration Drawing, TCE.5960A-EL-SK-2004. All the
SCADA switches and servers shall be located in switchyard control
room. All SCADA servers & Front End Processor servers (if any) shall
be rack mounted. The Controller shall also be configured with double
redundant power supply units.
7.10.5 The communication between the numerical relays and SCADA system
shall be with fibre optic cable.
7.10.6 SCADA system shall be fail safe design. The Contractor shall furnish
documents to establish and prove that the system is highly reliable with
very high MTBF (Mean Time between Failures).
7.10.7 One (1) no. Operator Station(OS) for SCADA (for control and
monitoring of complete 400 kV switchyard equipment) shall be located
in Central Control Room (CCR) of power plant and one (1) no. in
Switchyard Control Room. One (1) no. Engineering Station shall be
provided in the Switchyard control room to make the SCADA
configuration changes and system settings. The Engineering
Station(ES) located in Switchyard control room shall also be configured
as Operator Station to act as standby in case of failure of the Operator
Station in Switchyard control room. The OS and ES display/monitors
shall be dual headed, 24 inches size, LCD type and the make shall be
finalised during detailed engineering so as to match with those
ISSUE
R0
138
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 27 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
7.10.8 The control location for the switchyard equipments shall be Switchyard
control room by default. But provision shall be made available in the
SCADA to control the switchyard equipments from Centre control room
(CCR) also. It shall not be possible to control the switchyard
equipments from both the locations simultaneously. The required
selection shall be provided in the operator station of Switchyard control
room.
7.10.10 Synchronising facility shall be provided for all lines in SCADA. In check
synchronising position, the synchronising criteria shall be fulfilled as
indicated by the closing permissive provided by check synchronising
relays in-built in BCUs (separate sync check relays are not envisaged).
In dead bus/line mode, closure is possible only if either the line or the
bus is dead. The synchronising of the line shall be possible through
both main breaker and the middle breaker. Display of voltages and
frequencies of incoming and running supplies, synchroscope and the
sync. permissive signal shall be simulated in the SCADA operator
station. The synchronism and energizing check functions shall be bay
oriented and distributed to the bay control units and/or protection
devices. All features shall be available viz. a) Setting voltage, phase
angle, and frequency difference b) Energizing for dead line - live bus,
live line - dead bus or dead line – dead bus with no synchro-check
function c) Synchronising between live line and live bus with
synchrocheck function. The correct voltage for synchronizing and
energizing is derived from the auxiliary switches of the circuit breakers
and the isolators and shall be selected automatically by the bay control
and protection IEDs. The closing operation of line breaker shall involve
the following steps, viz. a) selection of the breaker to be closed, b)
mode of closing operation i.e. whether both the line and the bus are
ISSUE
R0
139
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 28 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
7.10.11 The generator transformer main breaker will be controlled from main
plant DCS. It shall be possible to control the middle breaker from both
DCS (through auto/manual synchronisation) and SCADA with the help
of a selection available in the SCADA software. The selection shall
have two positions i.e. “SCADA” and “DCS”. If “SCADA” is selected, all
the required signals including PT signals for synchronising shall be
transferred to SCADA system. If “DCS” is selected, all the required
signals shall be transferred to DCS/GRP (Generator Relay Panel).
The control of middle breaker from SCADA shall be suitably interlocked
such that its closure is not possible when it is used as generator
synchronising breaker.
7.10.13 All the auxiliary contacts of main equipment such as circuit breakers,
isolators, earth switches shall be brought to the protection panels for
indications, interlocks, SER function, etc. In case of shortage of
auxiliary contacts, contact multiplying relays shall be used. The same
shall be two coil, latching type with electrical reset and shall be
mounted in switchyard protection panels. At least 2NO + 2NC spare
contacts shall be wired to terminal block after fully utilising for control,
protection, annunciation, etc.
ISSUE
R0
140
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 29 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
7.10.16 Mimic
ISSUE
R0
141
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 30 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
7.10.17 Measurement
7.10.18 Event logging and trending facilities shall be provided in SCADA system.
It shall be possible to trend different parameters on the same trend. It
shall be possible to store historical data for a minimum of two years.
SCADA system shall have provision for expansion and shall be capable
of communicating with other systems through open protocol.
7.10.19 The Contractor shall make provision for terminating 4-20 mA analog
signals and potential free digital signals for the following data on a
terminal block in a suitable interface panel located in switchyard control
building for transmission to SLDC (State Load Despatch Centre) and
RLDC (Regional Load Despatch Centre) through RTU (Remote
ISSUE
R0
142
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 31 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
a) The BCU shall be an intelligent unit and shall be state of the art
technology. It shall perform control functions in accordance with
control commands from SCADA and shall also do monitoring of the
respective bays. The BCUs shall be installed in the respective
protection panels of each circuit breaker in the switchyard relay
room (Outdoor Kiosk). The control voltage for the BCU shall be
220V DC. The degree of protection of the panel shall be IP-52. The
BCU shall comply with relevant IEC/BIS standards.
ISSUE
R0
143
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 32 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
d) Atleast one bay control unit (BCU) shall be provided for each
breaker. The analog and digital signals pertaining to a circuit shall
be taken through the BCU provided for that circuit.
i) Monitoring
The following monitoring functions shall be provided as a
minimum :
• Status monitoring and failure monitoring (in SCADA HMI)
of bay equipment like breaker, isolators, earth switches,
instrument transformers, protection relays and ancillary
equipment metering (measured-value acquisition)
• Signal and command indications
• Switching statistics in BCU (breaker ON/OFF, breaker
auto-reclose, pole discrepancies) and data stored in
SCADA server
• Energy metering values
ii) Control
The following control functions shall be provided as a
minimum:
• Control of circuit breakers and isolators
• Interlocking for isolators and circuit breakers, isolators and
earth switches (The interlocks for earth switches shall be
hard wired)
iii) Recording
The event recording function shall be provided and processed
in the BCU and the record stored in SCADA. Each BCU shall
contain an event recorder capable of storing at least 200 time
tagged events.
ISSUE
R0
144
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 33 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
ISSUE
R0
145
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 34 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
All auxiliary contacts of the CBs, isolators and earthing switches shall
be terminated in terminal box section of bay marshalling boxes. All
hardwired interlocking shall be wired in the above box. All auxiliary
contacts and interlocked scheme contacts shall be wired to respective
panels in the control room.
146
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 35 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
number of cores are run from these marshalling boxes to control and
relay panels as appropriate. The neutral of CTs, CVTs, EMVTs shall be
earthed only at control/relay panel by means of a disconnecting link.
ISSUE
R0
147
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 36 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
d) The RTU’s and the PLCC located in the Switchyard control room
for SLDC/RLDC shall be provided with 48V dual DC supply.
(a) The panels shall have a degree of protection not less than IP-
52 and shall be fabricated with 3 mm thick cold rolled sheet
steel for front and rear equipment bearing surfaces and
bottom gland plates, and 2.5 mm for sides and top. The doors
and removable covers shall be gasketed. The panels shall be
provided with anti vibration pads. The paint shade of panels
shall be of shade opaline green (External) and semi-glosy
white (Internal).
ISSUE
R0
148
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 37 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(d) The centre line of switches, push buttons and indicating lamps
shall be not less than 750 mm and centre lines of relays,
meters and recorders shall not be less than 450 mm from the
bottom of the panel. Control switches / push buttons /
selectors and relay resetting knobs shall be located at a
height between 1.0 m and 1.2 m from the bottom of the panel.
(f) All the internal wiring shall be carried out with 1100V grade
stranded copper conductor wires with PVC insulation. For CT
/ PT circuits the wire size shall be 2.5 mm2 / lead and other
circuits it shall be 1.5 mm2 / lead. All wiring meant for power
supply to transducers, recorders shall be suitably MCBs or
designed to limit short circuit currents. Means for detection of
blown or open circuited fuses shall be provided.
ISSUE
R0
149
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 38 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(j) All the push buttons shall be momentary contact type, the
colour of PBs shall be different for various functions. Push
buttons shall be suitably shrouded to prevent inadvertent
operation. All PBs shall have 2 NO + 2 NC contacts.
(k) Each of the control & relay panels shall be provided with
thermostat-controlled space heaters, CFL type cubicle
illuminating lamps and a 5A, 3 pin receptacle.
(l) Each control & relay panel shall be provided with necessary
arrangement for receiving, distributing, isolating and short
circuit protection by use of MCBs/MCCBs of D.C. and A.C.
supplies for various control, signalling, lighting and space
heater circuits.
(n) All the panels shall be equipped with a continuous earth bus
with connectors and clamps between panels for interpanel
connection of the earth bus. All the metallic cases of relays,
instruments and other panel-mounted equipments shall be
connected to the earth bus by 2.5 mm2 copper wires. CT and
PT secondary neutral or common lead shall be earthed at one
point only at the terminal block and such earthing shall be
made through links. Separate copper earthing flat shall be
provided in the panel for cable screens of static equipment.
ISSUE
R0
150
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 39 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(p) Tests
7.15.1 Stand alone Fault Disturbance Recorder with associated cabling, PC,
HMI, Printer and evaluation software shall be provided for the 400 kV
Switchyard. The HMI and PC loaded with evaluation software shall be
located in Switchyard Control Room/Central Control Room. It shall have
8 analog and 16 digital channels. The equipment shall be complete with
disturbance recorder, control / display unit, junction box and accessories
like auxiliary CTs and shunts.
ISSUE
R0
151
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 40 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
(iii) The fault recorder and all its peripherals shall be designed
for operation on 220V DC. Recorders shall be provided
with pre-history recording feature with pre-history
recording time not less than 0.5 or 1 sec. The sampling
rate of the wave shall be between 1.2kHz to 10kHz.
ISSUE
R0
152
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 41 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
Live line-dead bus and dead line / live bus closing facility shall be
provided using dedicated relays on CVT. The closing shall be possible
only in manual position of synchro selection switch.
Live-line / dead bus and dead-line / live-bus relays shall be one set per
CB.
7.17.1 The SER system shall be a part of SCADA system. SER shall be
designed with 1 ms resolution for digital input events with time stamping
from each phase of all breakers, isolators and earth switches, opening
and closing commands, change of positions of switches such as
Local/Remote selection, synchronising selection, voltage selection,
auto re-closing selection, selection of control from SCADA/DCS,
operation of all protection and trip relays, VT fuse fail relay operation,
direct trip send and receive, pole discrepancy relay operation, trip
circuit faulty, trip relay faulty, DC supply fail, SF6 pressure Low, LBB
operated, etc. shall be available in SCADA. Critical interlocks and
ISSUE
R0
153
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 42 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
those SER points which are not covered by numerical relays shall be
hard wired to SCADA. The chronological printout facility shall be
provided for any of the first 100 occurrences. Further occurrences shall
be printed chronologically. This list is only indicative and not
exhaustive. The clock shall have resolution of 1 ms and first up feature.
It shall be possible to synchronise the clock with an external master
clock.
7.17.2 The event recorder shall be suitable for operation on 220V DC supply.
PLCC system shall be provided for four nos. of 400kV outgoing lines.
100% redundancy shall be provided in hardware for protection
signalling. 1 no. dedicated channel shall be provided for speech/data
necessary hardware & software & accessories shall be included,
however exact requirement of APTRANSCO grid authorities shall be
intimated to successful bidder.
7.20.1 ABT compliant energy meters for main & check with accuracy class of
0.2S shall be provided with suitable communication port for interfacing
the same with SCADA system. In SCADA system separate work station
shall be provided for accessing the Energy Meter readings. Separate
core for main & check tariff metering with 0.2S accuracy class shall be
provided for all the lines. Energy meters must be provided with a pair
of suitably rated potential free contacts to generate signal for
annunciation and SCADA, if voltage supply to the meters are
interrupted. Provision shall be made to amount Tariff meters supplied
by grid in the switchyard itself in the grid tie lines as per requirement of
grid authorities.
7.21.1 The Contractor shall conduct all the routine, type and acceptance tests
as per the relevant standards and as specified in this specification in
the presence of the Owner. The test certificates shall be furnished for
Owner’s approval.
ISSUE
R0
154
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.7
SHEET 43 OF 51
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 400 kV SWITCHYARD SPEC. NO.
TCE.5960A-H-500-001
ISSUE
R0
155
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT SECTION: D3.7
COMPANY LTD.
DATA SHEET – A3.7 SHEET 44 OF 51
1.9 Clearances
3.7 Insulators
3.10 Miscellaneous
7.0 INSULATOR
8.2 Generator and Auxiliary Power Supply System Control & Monitoring
8.2.1 Provision in the plant control system shall be made for the starting,
bringing upto rated voltage and speed, initiation of synchronising,
operation and annunciation on GCP and monitoring, alarm, data logging,
recording and sequential event recording for generator and its excitation
system from the Operator stations (plant DCS through HMI). The
minimum requirements of the measurements are indicated in the Main
One Line Diagram drg no. TCE.5960A-EL-SK-2003.
8.2.2 In the GCP, the mimic of the generator, its subsystems and 6.6 kV &
400V auxiliary power supply system shall be provided.
164
TCE FORM NO. 329 R5
SECTION: D3.8
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD.
SHEET 2 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – SPEC. NO.
GENERATOR CONTROL PANEL TCE.5960A-H-500-001
8.2.4 Manual synchronising facility common to all the units shall be provided
for manual synchronisation of the generators. Remote/Manual selection
shall be provided in DCS. When the “Remote” mode is selected,
synchronising shall be initiated from DCS through auto synchroniser.
When the “Manual” mode is selected, synchronising shall be done from
the stand-alone synchronising panel which houses the required
synchronising gear (consisting of dv & df meters with associated
transducers, synchroscope, check synchronising relay, guard relay,
synchronising lamp, etc.), breaker selector switch, breaker control
switches, etc. The synchronising panel shall be located in the control
equipment room.
8.2.5 Hard wired emergency trip push buttons for tripping of generator circuit
breakers of GTGs shall be mounted on the operator console. The push
buttons shall be suitably protected to prevent inadvertent operation.
8.2.4 The GCP shall be provided with all the synchronising switches, selector
switches, push buttons, indicating lamps as needed for the control of the
systems envisaged.
8.2.5 The interlocks for the auxiliary power supply system shall be hardwired
interlocks.
165
TCE FORM NO. 329 R5
SECTION: D3.8
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD.
SHEET 3 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – SPEC. NO.
GENERATOR CONTROL PANEL TCE.5960A-H-500-001
8.3.2.1 CONTROLS
(i) Control of all the Incomers, bus ties of all the electrical
switchboards except outgoing feeders from the main Lighting
Distribution Board, DCDB & UPS DB, shall be carried out from the
DCS. It shall also have the facility to carryout the live changeovers
at all the switchboards at 6.6kV & 400V. Remote position, service
position, breaker health, permissive for interlock set shall be
considered as input to the DCS system. Synchronising gear shall
be housed in the respective switchboards.
(ii) All transformers with OLTC shall have provision for control viz.
issuing raise / lower command to OLTC from plant DCS system.
8.3.2.2 Monitoring
ISSUE
R0
166
TCE FORM NO. 329 R5
SECTION: D3.8
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD.
SHEET 4 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – SPEC. NO.
GENERATOR CONTROL PANEL TCE.5960A-H-500-001
(iv) DC System
167
TCE FORM NO. 329 R5
SECTION: D3.8
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD.
SHEET 5 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – SPEC. NO.
GENERATOR CONTROL PANEL TCE.5960A-H-500-001
(viii) DG Set
(ix) Alarm for the running hours of 30KW & above motors shall
be generated after achieving predefined set points.
8.3.2.3 Measurement
168
TCE FORM NO. 329 R5
SECTION: D3.8
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD.
SHEET 6 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – SPEC. NO.
GENERATOR CONTROL PANEL TCE.5960A-H-500-001
MVAR -MVAR
MVARH* -
Frequency -Frequency
MW trending -
MVAR trending -
pf -pf
MWH * -MWH
(d) 400 kV Bus V(Bus –1& 2) -
Frequency(Bus -
–1& 2)
* By pulse output from TVM /Meters
ISSUE
R0
169
TCE FORM NO. 329 R5
SECTION: D3.8
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD.
SHEET 7 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – SPEC. NO.
GENERATOR CONTROL PANEL TCE.5960A-H-500-001
(g) 6.6kV & 400V Buses V (All phases) All energy metering
F shall be through
the power meters
provided on the
incomers & tie
feeders on the
DCS. These power
meters shall have
the local display
also. Running
hours of the motors
decided during the
detailed
engineering shall
be calculated or
taken from the
numerical relays.
(h) Emergency DG set Running hours, -
electrical
parameters &
Energy reading
shall also be
measured
through
numerical
protection relay
provided at the
DG set. .
(i) DC and UPS System A -
V & Hz for UPS
NOTE :
DCS Input current and voltage shall be considered for all three (3) phases.
The metering data for the 400kV bays shall be through the ABT
compliant energy meter provided except the tariff meters.
8.3.3.4 Event logging shall be provided for all manual operations and relay
operations as detailed below:
170
TCE FORM NO. 329 R5
SECTION: D3.8
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD.
SHEET 8 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – SPEC. NO.
GENERATOR CONTROL PANEL TCE.5960A-H-500-001
(d) Each protective relay, trip relay, alarm relay operation. Event
logging for each phase shall be provided wherever applicable
(eg. 3-poles of line circuit breaker, distance relay output contacts,
generator protections, fuse fail alarm, etc.)
(e) Event logger shall be a part of the DCS with first up feature. It
shall have a time resolution of 1 ms.
8.3.2.6 Synchronising
(b) 6.6 kV Incomer & tie circuit breakers shall have facility for fast and
slow auto changeover/manual synchronising and dead bus
closing.
(c) 400V switch board / MCC incomer and bus coupler breakers shall
have facility for dead bus auto change over / manual live transfer.
ISSUE
R0
171
TCE FORM NO. 329 R5
SECTION: D3.8
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD.
SHEET 9 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – SPEC. NO.
GENERATOR CONTROL PANEL TCE.5960A-H-500-001
(1) Generators
(2) Breakers associated with Emergency DG synchronising
8.3.3 The functional requirement indicated above are minimum, the Bidder
shall provide all necessary controls indications, interlocks & devices
required for the system offered by him. Also, any additional requirement
arising during detailed engineering shall be provided by the Bidder
without any additional cost to the Owner.
8.3.4 The time critical controls and interlocks shall be hardwired system only.
8.3.5 The control / selector switches & meters shall be of miniaturised version.
8.3.6 Check & main Meters – ABT compliant Tri-vector energy meters of
Accuracy class 0.2S for lines, UAT & generator metering shall be
provided.
8.4 Transducers
8.4.1 The Contractor shall provide all the transducers for electrical system
either in respective switchgear / control panels. All the transducers shall
be self-powered.
8.4.2 The transducers shall comply with the requirements specified for
transducers in Electrical section D3.25.
8.5.1 The interposing relays required for the switchgear / equipment being
supplied under this contract shall be located in separate IPR panels
located in the control room.
8.5.2 The coupling relays shall be rated for 0.5 Amp breaking at 220V DC and
6 Amp make and continuous current at 220 V DC.
8.5.3 Interposing relays used for 400 kV circuit breaker closing shall be
adequately rated for the making current.
ISSUE
R0
172
TCE FORM NO. 329 R5
SECTION: D3.8
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD.
SHEET 10 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – SPEC. NO.
GENERATOR CONTROL PANEL TCE.5960A-H-500-001
8.6 Tests
ISSUE
R0
173
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.9
SHEET 1 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 6.6 kV SWITCHGEAR
SPEC. NO.
TCE.5960A-H-500-001
The 6.6 kV switchgear and its accessories shall conform to all latest
editions of national and international standards indicated in Data Sheet –
A 3.9. Also, the switchgear and its accessories shall comply with the
requirements indicated in Data Sheet – A 3.9 and specific requirements
indicated below.
9.1 For feeding the plant auxiliaries rated for 6.6 kV and service
transformers, adequately rated switchgears shall be provided.
9.2.1 The station switchgear shall be provided with manual live changeover
scheme for planned changeover of supply from one incomer to another
and vice versa.
9.2.2 Automatic fast changeover scheme for changeover of supply from one
source to another in the event of supply failure from upstream end shall
be provided. Changeover shall be blocked if incomer has tripped due to
bus fault.
9.2.3 The closure of the unit supply breaker shall be supervised by a synchro-
check relay permanently connected to and energised by the secondary
voltages of the unit bus P.Ts. The high-speed transfer shall be
completed in not more than 40 ms. If fast auto change over fails for
whatever reason, an automatic “slow” transfer shall be initiated. The fast
changeover scheme shall be such that the running motors are not
tripped or there is only allowable inrush current due to motor re-
acceleration.
i) Fast Transfer
The breaker power contacts shall close when the decaying and drifting
bus voltage synchronizes with the incoming source voltage within
acceptable voltage and frequency parameters. The Bus transfer system
ISSUE
R0
174
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.9
SHEET 2 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 6.6 kV SWITCHGEAR
SPEC. NO.
TCE.5960A-H-500-001
shall continuously process the bus voltage and the drifting phase angle
dynamics to determine in real-time the exact moment of sending a
command to the breaker-closing coil to achieve the above.
The breaker power contacts shall close when the falling bus voltage
shall reach an acceptable safe value. The auxiliary drives are selectively
tripped simultaneously to limit the transformer inrush current.
This is a “Make before Break” transfer for a very short duration of the
order of few cycles where, under supervision of the bus voltage and
incoming source voltage for magnitude and phase angle, the new source
breaker is closed before opening the old source breaker. Normally not
recommended for unplanned transfers and auto/protective transfers from
the system safety considerations
One motor and one transformer type spare feeder of highest rating shall
be provided on both sections of Bus-A & Bus-B of 6.6kV switchgear.
Additionally One (1) no. transformer feeder on each bus (colony supply)
for Owner’s use shall be provided.
9.4.1 The fault level for the switchgear, circuit breakers, isolators, earth switch,
bus bars, etc., shall be arrived at, on the basis of short circuit current
contribution from UAT plus short circuit contribution by the motors
running on the bus.
9.4.2 A margin of 5% over higher of the above S.C current, thus calculated
shall be applied and rounded off to the next higher standard ratings and
this value shall be adopted for the breakers and switchgears. The
momentary current ratings shall be 2.55 times this value.
9.4.3 Asymmetrical S.C current breaking capacity of the breaker shall consider
the higher time constant for decay of current in the vicinity of power
generating stations and the breaker offered shall be suitable for this duty.
ISSUE
R0
175
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.9
SHEET 3 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 6.6 kV SWITCHGEAR
SPEC. NO.
TCE.5960A-H-500-001
9.4.4 Calculations for arriving at the time constant at this plant shall be
furnished to justify breaker selection in accordance with IEC-62271-100
and contractor shall furnish calculation during detailed engineering stage
to establish the adequacy of support insulators and busbar sizes for the
declared continuous and short time current rating.
9.5.1 The continuous current rating of the 6.6 kV unit switchgear buses,
incomer breaker shall be the rated LV winding current of UAT's
respectively with 20% margin rounded off to the next higher standard
rating.
9.5.2 The continuous current rating of the feeders shall be based on the name
plate current rating of the connected equipment with 20% margin
rounded off as indicated in 9.5.1.
9.6.1 The switchboard shall be indoor, metal clad having separate metal
enclosed compartments for (a) control, metering and relaying devices,
(b) circuit breakers, (c) phase bus bars, (d) instrument transformers and
(e) power cable terminations and adjacent cubicles (panels) shall have
sheets on either side to ensure complete isolation. The bottom of each
panel shall be covered by sheet steel and necessary glands plates.
Switchgear shall be suitable for extension on both sides. Switchgear
shall be suitable for extension on both sides. The switchgear assembly
shall be rodent and vermin proof.
Door enclosing the cable termination shall be with hinge. A fixed type
checkered net shall be provided between cable termination and door to
avoid accidental contact to live termination. This arrangement is required
to take Thermographic measurement using Infrared thermometer.
9.6.2 Required number of high speed trip relays, supervision relays, auxiliary
relays, timers, contact multiplication relays, etc., shall be provided in the
ISSUE
R0
176
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.9
SHEET 4 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 6.6 kV SWITCHGEAR
SPEC. NO.
TCE.5960A-H-500-001
9.6.3 The circuit breaker shall be drawout type and it shall have test, service
and isolated positions. In test position the circuit breaker shall be capable
of being tested for operation without energising power circuits. At least
5NO+5NC spare contacts shall be wired to the terminal block after fully
utilising for protection, interlocking, annunciation, etc.
9.6.4 The current transformers shall be mounted in the fixed portion of the
switchgear. Adequate space shall be available for termination using heat
shrinkable type cable termination in cable compartment and for mounting
of zero sequence current transformers (core balance current
transformers).
9.6.6 Automatic safety shutters shall cover live parts when the breaker is
withdrawn and all other standard safety features shall be provided.
9.6.7 Earth bus of size 50x6 mm Cu shall be provided at the bottom and shall
extend throughout the length of the switchboard .All non-current carrying
metal work of the switchgear shall be effectively bonded to the earth bus.
Hinged doors shall be earthed through flexible earthing braid for each
type of breaker.
9.6.8 The circuit and bus bar earthing facility with earthing trucks shall be
provided for each type of breaker. Suitable mechanical interlocks shall
be provided to prevent the closing of earth switch on live circuit.
9.6.9 Switchgear shall be supplied completely wired and inter panel wiring
between cubicles of same switchgear shall be provided.
9.6.10 The sizes of wire in the panel shall be stranded copper conductor,
1.5mm² for all circuit and 2.5 mm² for CT circuits.
9.6.11 Terminal blocks shall be of stud type, 650 volts grade, 10 amps rated
complete with insulated barriers. Terminal blocks for CTs and VTs shall
be provided with test links and isolating faciliting and CT terminals with
short circuiting and earthing facility. All spare contacts and terminals of
cubicle mounted equipment and devices shall be wired to terminal blocks
with 20% spare terminals. Not more than 2 wires shall be connected at a
one terminal.
ISSUE
R0
177
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.9
SHEET 5 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 6.6 kV SWITCHGEAR
SPEC. NO.
TCE.5960A-H-500-001
9.6.12 All relays protective, auxiliary, and timers shall be in draw out cases with
built in test facilities. Necessary test plugs shall be supplied loose and is
included in the scope of supply. Externally operated hand reset indicators
shall be provided on all relays and timers. Timers shall be of
electromagnetic or electronic type only. Atleast 1NO + 1NC spare
contacts of all relays / timers shall be wired to terminal block. All relays
shall be of self reset type unless otherwise specified. In the event of
shortage of contacts in circuit breakers, trip relays, contact multiplying
relays shall be used. The same shall be two coil, latching type with
electrical reset, contacts shall be gold flashed with 20 micron thick
plating.
9.6.13 Breaker control switches shall be pistol grip black and selector switches
shall be oval or knob, black. Breaker control switches shall be 3 position
spring return to neutral, instrument selector switches shall be of
maintained stay put type.
9.6.16 Each switchgear panel shall be provided with 230 Volts, 1 phase, 50 Hz,
5 amps, 3 pin receptacle with switch located in a convenient position.
9.6.17 Provision shall be made for receiving, distribution, isolating and fusing of
auxiliary DC and AC supplies for controls, space heating, etc. Two
numbers DC feeders shall be provided for 6.6kV switchgear with selector
switch for selecting any one supply. DC supply supervision lamps (self
coloured clustered LED type of size 22.5 mm) shall be provided and the
same shall be on AC supply. Single phase loads for motor space heating
etc., shall be distributed between different phases to keep the loading on
all the phases uniform.
(a) The CTs shall withstand momentary and short time current
ratings of the associated switchgear. CTs and VTs shall be of
the cast resin type and completely encapsulated.
(b) In case of smaller rated CTs (say 200 Amp and less) at the
expected fault level the CT saturation may result in the non
operation of the instantaneous short circuit protection. In such
cases separate protection CT core with higher ratio shall be
selected to avoid saturation at high fault currents.
ISSUE
R0
178
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.9
SHEET 6 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 6.6 kV SWITCHGEAR
SPEC. NO.
TCE.5960A-H-500-001
9.6.19 VTs shall be single phase, drawout type and housed in a separate sheet
metal enclosure. VTs shall be provided with HRC fuses on both primary
and secondary sides under voltage relays, timers, etc. for motor tripping
and remote annunciation on supply failure. Those terminals required to
be connected to earth shall be earthed by an isolating link without a fuse.
Those terminals required to be connected to earth shall be earthed by an
isolating link without a fuse. Fuses on primary side shall have rupturing
capacity equal to the switchgear rating. Primary fuse replacement shall
be possible with VT in isolated position only.
9.6.20 Switchgear panel shall be suitable for bottom cable entry and provided
with removable gland plates. Adequate space shall be available for the
termination of the heat shrinkable cable termination & mounting of the CT
& CBCT.
9.6.21 Cable lugs for all power, control and instrumentation cables connections
shall be supplied. The lugs shall be tinned copper/Aluminium depending
on cable conductor and of solderless crimping type. The cable glands
shall be of double compression type brass glands.
9.6.23 Bidder shall supply and mount transducers as per Main One Line
diagram and philosophy of control defined elsewhere in the specification,
in the individual switchgear panels.
9.6.24 For the analog parameters (i.e. A, p.f, KW, running hours etc) required in
DCS, 4-20mA outputs for parameters available in numerical relays shall
be used. Wherever not available, separate transducers shall be
provided. The transducers shall have 4–20 mA dual output and accuracy
class shall be less than 0.5%.
9.6.25 Rubber mats suitable for 7.2kV grade shall be provided at front and rear
of switchgear.
ISSUE
R0
179
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.9
SHEET 7 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 6.6 kV SWITCHGEAR
SPEC. NO.
TCE.5960A-H-500-001
9.6.27 Current ratings of all switchgears, circuit breakers, CTs etc. shall be
sufficient for carrying the connected load currents without exceeding the
permissible temperature limits or reduction in service life. Use of two
breakers in parallel to meet the required rating shall not be acceptable.
9.6.28 The connection between the start up transformer and 6.6kV switchgear
shall preferably be by means of segregated phase bus ducts.
9.6.29 Surge arrestors shall be provided for motor and transformer feeders and
shall be as per manufacturer’s recommended type and generally in
accordance with IEC 99-1. They shall be mounted within the switchgear
cubicle between line and earth preferably in cable compartment and
shall be suitable for indoor duty. Surge arrestors shall be suitable for non
effectively earthed system and the maximum switching overvoltage shall
not be more than 2.5 times the peak line to neutral voltage of the
system. Bidder shall furnish temporary overvoltage capability curve and
pressure relief device shall be provided for relieving internal pressure
and preventing violent shattering of the housing following prolonged
passage of follow current or internal flashover of arrestor.
Each circuit breaker cubicle shall be provided with the following minimum
standard accessories:
(a) One control switch `Trip - Neutral - Close' spring return to neutral
position.
(b) One two position control selector switch `Local - Remote' switchgear
control stay put type.
(i) `Red' for breaker `ON' indication and trip coil supervision.
(ii) `Green' for breaker `OFF' indication.
(iii) Blue' for breaker in 'Service' position.
(iv) ‘Amber' for breaker in 'Test' position.
(v) ‘Amber’ for breaker auto trip indication
(v) 'White' for breaker closing spring 'Charged'.
(vi) 'White' supervision lamp for lockout relays.
(vii) ‘Red' for breaker ON indication at the back of the switchgear
at cable box door
ISSUE
R0
180
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.9
SHEET 8 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 6.6 kV SWITCHGEAR
SPEC. NO.
TCE.5960A-H-500-001
(d) Mechanical trip push button to trip the breaker when control
supply is lost. The push button shall be shrouded type.
Mechanical close push button provided shall be accessible only
after opening of the front door.
(f) Closing from local shall be possible only in test position whereas
closing from remote shall be possible in either service or test
position. Tripping from local shall be possible only when
local/remote selector switch is in local position. Tripping from
remote shall be possible only when either breaker in service
position or selector switch being in remote position
(h) One double pole control supply switch and set of fuses.
181
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.9
SHEET 9 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 6.6 kV SWITCHGEAR
SPEC. NO.
TCE.5960A-H-500-001
software for setting all the numerical relays in 6.6 kV switchgear and
generator protection panels shall be loaded in a dedicated operator
station in the main control room. All numerical relays shall be time
synchronized with the GPS master clock. On failure of any of the
numerical relay a contact shall be generated, which shall provide the
annunciation to the DCS. All the protective relays, except for auxiliary
relays shall have – remote/local reset facility, and shall be suitable for
efficient and reliable operation of the protective schemes. A combination
of electromechanical & numerical communicable type relays for main
protections is not acceptable. The Bidder shall include in his bid a list of
installations where the relays offered are in trouble free operation for last
two years. The minimum protections / metering shall be provided
required for various typical feeders shall include, but not be limited to the
following:
9.7.1 Incomers
Protections Metering
Composite numerical feeder Ammeter and voltmeter
protection relay with selector switch
Under voltage relay Wattmeter (or)
Multifunction meter with all
the metering parameters
Local breaker backup Current transducer for
protection each phase
Fuse failure relay 1 no. MW transducer
1 no. MVAR transducer
Protections Metering
Composite numerical feeder Ammeter and voltmeter
protection relay with selector switch
Local breaker backup 1 no. kWh meter
protection
1 no. watt meter (or)
Multifunction meter with all
the metering parameters
1 no. current transducer
(Y-Phase)
1 no. MW transducer
ISSUE
R0
182
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.9
SHEET 10 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 6.6 kV SWITCHGEAR
SPEC. NO.
TCE.5960A-H-500-001
Protections Metering
Under voltage protection Voltmeter with selector
switch
Fuse failure protection Voltage transducers–3
Nos.
Protections Metering
Composite motor protection Ammeter* with selector
relay (99) switch
Differential protection for motor 1 no. kWh meter
feeders (rated 1000kW or
above) 1 no. power factor meter
Local Breaker backup 1 no. watt meter (or)
protection Multifunction meter with all
the metering parameters
Time delayed under voltage 1 no. current transducer
trip (Y Phase)
Protections Metering
Composite numerical Ammeter with selector
transformer protection relay switch
Local Breaker backup 1 no. kWh meter
protection
Winding temperature and 1 no. Wattmeter (or)
Buchholtz protection Multifunction meter with all
the metering parameters
1 no. current transducer
9.9 Tests
ISSUE
R0
183
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.9
SHEET 11 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - 6.6 kV SWITCHGEAR
SPEC. NO.
TCE.5960A-H-500-001
All relevant routine tests and acceptance test shall be conducted as per
applicable standards and typical type test certificates of identical
switchgear shall be furnished.
ISSUE
R0
184
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELPOMENT SECTION: D3.9
COMPANY LTD.
DATA SHEET – A 3.9 SHEET 12 OF 15
SPEC. NO.
TCE.5960A-H-500-001
SL. NO. DESCRIPTION UNITS VALUES / REQUIREMENTS
6.6 kV SWITCHGEAR
1.8 Material of bus bar insulation Heat shrinkable PVC sleeve. Removable bus
bar joints with shrouds of 7.2kV insulation
1.12 Short circuit current rating and duration RMS 44 kA* for 1 sec.
2.2 Thickness of gland plate for 1 core cable mm 3.0, Non-magnetic material
2.4 Colour finished shade (Enamel / epoxy) Interior: Semi glossy white
Exterior: Opaline Green
3.6 Trip free operating mechanism type Motor charged spring. Manual trip and close
facility to be provided.
3.8 Short circuit current rating and duration rms 44 kA* for 1 sec.
(b) For space heaters and lighting and V, Phase 230 V, 1 phase
plug point
4.4 Short circuit withstand current and duration 44 kA* for 1 sec.
4.5 Core balance CT for all outgoing feeders Ratio 50/ 1 (As per consumer rating)
6.0 Meters
6.1 Accuracy class 0.5S for energy meters (0.2 for energy meters
on the switchgear incomers)
1.0 for others
SHEET 1 OF 4
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST. SPEC. NO.
ELECTRICAL SYSTEMS - SERVICE TRANSFORMERS TCE.5960A-H-500-
001
10.1 The number and rating of service transformers shall be decided based
on the geographical location of loads without sacrificing the unit and
common load concept. Adequate number of service transformers shall
be provided as required to meet the demand on 400V system based on
the criteria that each 400 V switchgear / PCC / MCC / Distribution board
shall be fed by 2 x 100% transformer / feeders. Each of the above
boards shall be sectionalised.
10.2 Impedance
The impedance of the transformers shall be selected such that the fault
level on the switchgear do not exceed its short circuit capability including
the motor contributions and also voltage dip while starting any auxiliary
does not exceed the limit acceptable for the equipment concerned but in
no case shall exceed 15%.
All service transformers shall be cast resin dry type (indoor). The service
transformers shall be two winding, three phase, 50 Hz, 6600 / 420 Volts,
with off-circuit taps of + 5% in steps of 2.5%.
11.4.1.1 The cast resin transformers shall be housed in naturally ventilated floor
mounted cubicle with louvers backed by fine brass wire mesh. Degree of
protection of enclosure shall be atleast IP32.
ISSUE
R0
189
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.10
SHEET 2 OF 4
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST. SPEC. NO.
ELECTRICAL SYSTEMS - SERVICE TRANSFORMERS TCE.5960A-H-500-
001
11.4.1.2 The transformer cubicle shall be located right next to respective 400V
switchgear and LV side shall be connected through cables or bus duct.
The HV connections shall be through cables.
11.4.1.3 The dry type transformers shall be provided with core and winding
temperature detectors, with temperature high alarm and very high trip
contacts.
11.4.1.4 The insulation class for cast resin transformers shall be class-F.
11.4.1.5 The core and windings shall be provided with embedded temperature
detectors for remote indication in DCS.
11.4.1.6 Noise level shall not exceed the values specified in NEMA TR-1.
11.4.1.7 Off-circuit tap changers with lockable operating handle, mechanical tap
position indicator, and with a variation of 2.5% per step and a range of
+ 5% shall be provided.
ISSUE
R0
190
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT SECTION: D3.10
COMPANY LIMITED
DATA SHEET – A3.10 SHEET 3 OF 4
SPEC. NO.
TCE.5960A-H-500-001
SL. NO. DESCRIPTION UNITS VALUES / REQUIREMENTS
Service Transformers
5.1 HV Delta
5.2 LV Star
6.1 HV kVp, 60 / 20
kV(rms)
The 400V switchgear and its accessories shall conform to the latest
editions of national and international standards indicated in Data sheet
A 3.11 400 V Switchgear / MCC. Also, the 400 V switchgear / MCC and
its accessories shall comply with the requirements indicated in Data
Sheet – A 3.11 and specific requirements indicated below:
11.3.1 The switchgear / MCC shall be provided with two incomers and a bus
coupler (100% each).
11.3.2 The switchgear / MCC shall be provided with suitable numbers and type
of outgoing feeders as required.
11.3.3 Spare feeders - 20% of each type and each rating with minimum of one
no. feeder. (Above quantity is the minimum requirement at the time of
handing over the plant. Any additional quantity required for any
increase/changes during detailed engineering stage also shall be duly
considered).
11.3.6 230V, 1 phase motor space heating supply module - 1 no. on each bus
ISSUE
R0
193
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.11
11.3.7 Alarm module for common alarm for out going feeder fault - 1 no.
11.3.9 For each auxiliary or load, one feeder shall be provided except for the
following cases:
(a) One feeder for maximum of 2 Nos. 400V, 3 phase plug points.
11.4 Construction
ISSUE
R0
194
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.11
(d) Vertical cable alley covering entire height and minimum 250mm
wide.
11.4.4 Each vertical section shall be equipped with space heater and
thermostat.
11.4.7 All doors shall be with concealed type hinges and captive screws. Stop
Push buttons shall be of latch type with mushroom knobs.
11.4.11 All types of relays and timer shall be flush mounted with connections
from inside, and shall have transparent & dust tight cover, removable
from front, drawout construction for easy replacement and testing facility.
The auxiliary relays and timer may be provided in fixed cases.
195
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.11
prevent access to the live part to avoid accidents during service as well
as maintenance period. Bidder shall bring out the safety means provided
to achieve above. A detailed instruction plate suitable for wall mounting
shall be provided for each switchgear / MCC room describing various
safe operating procedure / safety precautions for safe operation and
maintenance of switchgear / MCC. Rubber mats shall be provided in
front & back of each panel.
11.4.13 All switchgears, MCCs, DBs, panels, modules, local starters and push
buttons shall have prominent engraved identification plates.
Control supply for the SFU operated motor feeders shall be 110V AC
and for all ACB feeders, it shall be 220V DC. Control circuits shall
operate at suitable voltage of 220V DC. The auxiliary bus bars for
control supply shall be segregated from main bus bars. The control
supplies shall be monitored.
11.6.1 The breaker / feeder modules shall have service, test and Isolate
positions. Suitable trolley arrangement shall be provided for breaker
modules. Two trolleys in the main switchgear room shall be provided so
that breaker module of all types, sizes and rating can be withdrawn on
trolley and lowered for maintenance purpose. Additionally one such
trolley shall be kept at each switchgear room.
11.6.2 All air circuit breakers (ACBs) shall be of short circuit performance
category P2 as per IS 2516 parts I & II.
11.6.3 Breakers shall have inherent fault making and breaking capacities. They
shall have shunt trip coils. All breakers shall have built in interlocks for
equipment and personnel safety.
ISSUE
R0
196
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.11
11.6.5 The cable alleys shall be liberally designed considering the size and
number of cables, future additions of cables, easy and safe
maintenance.
11.6.6 For each vertical section a separate set of vertical bus bars shall be
provided to serve the modules.
11.6.7 The switches, contactors and other power devices shall consider a
margin of about 20% over the nameplate current rating of the respective
load.
11.6.8 For breaker control, 2 nos. 220V DC control supply shall be provided
with a manual selection for changing over to either supply. Necessary
voltage monitoring contactors, indication lamps shall be provided.
11.6.9 Minimum of two NO and two NC spare contacts of all contactors & relay
devices shall be wired to terminal block.
11.6.12 Space heater with MCB and thermostat shall be provided for each
vertical panel.
11.6.16 All indicating lamps shall be self-coloured clustered LED type of size
22.5mm.
197
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.11
• 3 phase inverse time over current relays & 1 no. E/F relay
• Indicating lamps for on, off and fault, spring charged, trip
circuit healthy etc
ISSUE
R0
198
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.11
• All incomers for MCC’s and DB’s rated from 630A shall be
ACB’s and for <630A MCCBs shall be provided. However
for MCC’s with important feeders like LOPs and where
auto change over is required, ACB’s shall be provided for
the incomers & Bus couplers.
199
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.11
(b) VT modules
ISSUE
R0
200
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.11
(iii) Earth fault alarm with voltage relay connected to open delta
formed on secondary side of VTs shall be provided on each
bus.
(iv) In case of fuse failure, the under voltage timer operation shall
be blocked.
(d) 230V, 1 phase, space heating module (for motor, panel, space
heating) shall be provided with incoming side switch, fuse, suitably
rated 400/230V cast resin type transformer (expected heating
loads of the switchboard + 30% margin) Secondary fuse, and
supply indicating lamp and connection to the space heating buses
in the particular bus section. The 400V power supply for these
modules shall be obtained from the other bus (i.e the supply for the
module in bus A shall be from bus B and vice versa.)
(e) Suitably rated 400 / 230 V, 1-ph cast resin transformer, incoming
side switch fuse, secondary side fuse, supply indication, 1-ph,
MCB outlets shall be provided for feeding 230 V space heating /
lighting supply required by other panels in the plant.
ISSUE
R0
201
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.11
ISSUE
R0
202
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.11
11.7 The internal wiring shall be with 1.5 mm2 stranded copper conductor for
control wiring and 2.5mm2 for CTs and suitably sized for power wiring
with a minimum of 2.5 mm2 copper.
11.8.1 Bidder shall include in his scope required no. of 400V AC power supply
distribution board/control panel for feeding packaged auxiliary load like
centrifuge, etc. Bidder shall provide one or two (depending on the
ISSUE
R0
203
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.11
criticality of the service) incomer from 400V main switchboard to feed the
distribution board/control panel. All the incoming and outgoing feeders
shall be of switch fuse controlled, if it is <400A other wise ACB shall be
used.
11.8.3 The A.C. distribution board/control panel shall comply with technical
requirements table. Also applicable clauses of 400V switchboard and
MCCs shall be complied with for these boards/panels.
11.9.1 To enable safe unit shutdown during complete A.C supply failure in the
station, certain important plant auxiliaries (such as the A.C. emergency
bearing lube oil pumps, turning gear motor, battery chargers,
emergency lights, essential instrument power supply feeders, etc.) shall
be provided with a reliable A.C. power supply through a separate
source. For this purpose, 400V, quick starting emergency diesel
generator sets with automatic mains failure (AMF) feature shall be
provided. Each DG set shall cater to the emergency loads of each of
the GTG units (i.e. 100%Unit+ 50% STG + 50% station emergency
loads). These DG sets are provided with one stand-by generator of
same rating as a back up.
11.9 Tests
ISSUE
R0
204
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.11
ISSUE
R0
205
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT SECTION : D 3.11
COMPANY LIMITED
DATA SHEET – A 3.11 SHEET 14 OF 17
SPEC. NO.
TCE.5960A-H-500-001
SL. NO. DESCRIPTION UNITS VALUES / REQUIREMENTS
1.1 Rated voltage, phases & frequency V/P/Hz 400, 3ph, 50, 3 wire
2.1 Utilisation category for contactors AC3 for non-reversible & AC4 for reversible
3.5 Control voltage for spring charging motor and V/DC 220
tripping & closing
4.1 Short time withstand current and duration for 50 kA for 1 sec.
CT
5.1 Class of accuracy 0.5 for energy meters and 1.0 for others
0
7.4 Design ambient temperature C 50
SHEET 1 OF 3
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST. SPEC. NO.
ELECTRICAL SYSTEMS - TCE.5960A-H-500-001
NEUTRAL EARTHING EQUIPMENT
12.1 400 kV system is solidly earthed. The neutral of GTs are independently
connected to earth.
12.2 Generator neutral shall be high resistance earthed. The neutral shall be
connected to a suitably rated neutral earthing transformer. The neutral
earthing resistor will be connected across the secondary of the neutral
earthing transformer.
12.3 6.6 kV systems shall be medium resistance earthed. The neutral of the
unit auxiliary transformers shall be independently connected to the earth
through a suitable resistance. The earth fault current shall be limited to
300A.
12.4 400V system shall be a solidly earthed system. The neutral of service
transformers shall be independently connected to the earth.
12.5 230V systems for lighting and the space heating shall be solidly earthed
system. The neutral of the transformers shall be connected to the earth
bus through a link in the respective board, which is in turn connected to
the plant earth grid.
12.6 230V AC control supply shall be a solidly earthed system. The mid point
of the secondary winding of the transformers shall be connected solidly
through a link to the earth bus in the respective modules of switchgear /
control panels.
12.7.1 The neutral grounding resistor ohmic value for generator neutral earthing
shall be so selected that during an earth fault on one of the phases of
the generator, the kW power consumed in the resistor shall be atleast
equal to 1.5 times, the capacitive kVA due to capacitance of generator,
generator bus duct and associated equipment including surge protection
capacitor, generator transformer.
12.7.2 The neutral earthing resistor ohmic value for unit aux. transformer neutral
earthing shall be such that earth fault current is limited to 300A.
ISSUE
R0
210
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.12
SHEET 2 OF 3
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST. SPEC. NO.
ELECTRICAL SYSTEMS - TCE.5960A-H-500-001
NEUTRAL EARTHING EQUIPMENT
12.8.1 Duty rating of the earthing resistor for generator neutral and UATs shall
be 30 seconds.
12.8.2 Cable boxes shall be provided for receiving the cables from the
transformers.
12.8.7 Each neutral earthing resistor unit shall be air cooled and self supporting
type. The minimum degree of protection for the resistor element shall be
IP 34.
12.8.8 The transformer cubicle shall be made of angle frame steel construction
with formed sheet sides. The resistor cubicle shall be made of angle
frame steel construction with hot dip galvanised screen sides.
Alternatively it can be painted with heat resistant paint suitable for 2500C
the neutral grounding equipment shall be completely assembled, wired
and connected to the neutral bus tap through seal-off bushing.
12.8.9 The neutral grounding transformer shall be cast epoxy resin type natural
air cooled single phase connected between generator neutral and
ground.
12.8.11 All alarm, protection and indication leads shall be wired upto terminal
blocks shall be mounted in a IP:54 enclosure suitable for flush mounting
and having a fully hinged cover with lock.
ISSUE
R0
211
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.12
SHEET 3 OF 3
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST. SPEC. NO.
ELECTRICAL SYSTEMS - TCE.5960A-H-500-001
NEUTRAL EARTHING EQUIPMENT
12.9 TESTS
12.9.1 All Acceptance and routine tests as per IS/IEEE shall be conducted on
NGR assembly.
12.9.2 The following tests on resistors shall be performed and test certificate
shall be furnished prior to dispatch:
ISSUE
R0
212
TCE FORM NO. 329 R5
5.5
SHEET 1 OF 14
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - DC SYSTEM SPEC. NO.
TCE.5960A-H-500-001
13.0 DC SYSTEM
The DC System and its accessories shall conform to the latest editions of
national and international standards indicated in Data sheet – A 3.13
Also, the DC system and its accessories shall comply with the
requirements indicated in Data Sheet – A 3.13 and specific requirements
indicated below:
13.1 DC power supply with high discharge plante lead acid cells forming bank
shall be the source of the power supply for control, protection, interlock,
annunciation of the complete plant including I&C system during the
running of the plant as well as for a safe shutdown at the time of the total
power supply failure. For feeding the DC supply for the above, the
following shall be provided.
13.1.1 220V DC, 2 x 100% battery bank with associated float cum boost-
charger, 1 No. DC switchboard having 2 Incomers & one bus coupler
shall be provided for each gas turbine generator (GTG) unit. The GTG
unit DC system shall be sized to cater complete unit GTG loads. The
scheme shall be as per sketch TCE.5960A-EL-SK-2006.
13.1.2 220V DC, 2 x 100% battery bank with associated float cum boost-
charger, 1 No. DC switchboard having 2 Incomers & one bus coupler
shall be provided for each steam turbine generator (STG) unit loads,
HRSG system loads and common station auxiliaries (excluding 400 kV
system auxiliaries). The scheme shall be as per sketch TCE.5960A-EL-
SK-2006.
13.1.3 220V DC, 2 x 100% battery banks with associated float cum boost-
chargers and 1 No. DC switchboard having 2 Incomers & one bus
ISSUE
R0
213
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.13
SHEET 2 OF 14
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - DC SYSTEM SPEC. NO.
TCE.5960A-H-500-001
13.1.4 48V DC, 2 x 100% battery banks with associated float cum boost-
chargers and 1 No. DC switchboard having 2 Incomers & one bus
coupler shall be provided for PLCC system of 400kV switchyard.
13.1.5 24V DC, 2 x 100% battery banks with associated float cum boost-
chargers and 1 No. DC switchboard having 2 Incomers & one bus
coupler shall be provided for catering the I& C and DCS system
application.
13.2 Scheme for earth fault detection shall be provided for each DC bus and
feeders.
13.3 Battery shall be sized to cater for the following loads with minimum
duration as indicated. The voltage at the end of duty cycle shall be
1.85 V/cell for lead acid batteries. Detailed sizing / selection calculation
shall be subject to Owner’s approval.
(a) Tripping / closing load of 400 kV, 6.6 kV & 400V breakers.
214
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.13
SHEET 3 OF 14
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - DC SYSTEM SPEC. NO.
TCE.5960A-H-500-001
13.4 Further, for arriving at the battery capacity, the following shall be
considered.
13.4.1 The temperature correction factor as given in IS. For this purpose,
electrolyte temperature shall be considered as 10 deg. C above the
ambient temperature.
13.4.3 A design margin of 10% shall be considered for each of the GTG Unit
Batteries & Common Station Batteries and 20% margin shall be
considered for the 400 kV System Batteries.
13.5.2 The boost charger unit shall be rated such that the battery can be fully
charged from fully discharged condition within 8 hours.
ISSUE
R0
215
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.13
SHEET 4 OF 14
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - DC SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(a) The battery offered shall be High Discharge plante Lead Acid
batteries confirming to IS: 1652 suitable for indoor application.
(b) The battery shall be of closed top or sealed in type. Open type
cells are not acceptable.
(d) One set of variable resistor load suitable for carrying out
discharge tests at 5 hour discharge rate & suitable shunt for
measuring current on all batteries shall be supplied.
Alternatively, electronic controls for carrying out discharge test of
the batteries at selectable rate can also be provided.
(a) The float cum boost charger offered shall be static type
composed of silicon controlled rectifiers and diodes (complete
with resistor/capacitor network for surge protection) connected in
three phase wave bridge circuit. It shall be provided with an
adequately rated isolation transformer and filters on input to
minimise harmonics on the output to keep ripple factor within
acceptable limits.
(b) Charger shall have provision for manual control if the automode
fails. Load limiting features shall be provided. The same shall be
designed for adequate short time over load to take care of the
starting of the largest DC motor/testing of lamps, etc. with other
DC loads connected to bus. The rectifier shall utilise power
semiconductors and heat sinks rated to carry 200% of the load
ISSUE
R0
216
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.13
SHEET 5 OF 14
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - DC SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(d) The charger shall essentially comprise the following items but not
limited to:
(iii) One (1) moving coil centre zero ammeter, with shunt,
size 96 x 96 mm to read discharge/charge
current of the battery, with suitable range.
(iv) One (1) cubicle space heater suitable for 230V AC,
50Hz, single phase supply.
(vi) Two (2) - On/Off switches with fuses for space heater
and internal lighting.
217
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.13
SHEET 6 OF 14
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - DC SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(f) Type of cooling for the charger panel shall be such that no
external fans are required to dissipate the heat developed within
the panel.
(h) One complete set of all accessories and devices required for
maintenance and testing of batteries shall be supplied for each
battery bank. Each set include at least the following:
ISSUE
R0
218
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.13
SHEET 7 OF 14
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - DC SYSTEM SPEC. NO.
TCE.5960A-H-500-001
13.7.1 For feeding the 220V DC loads 220V DC Switchboard as per clause
13.1.1 to 13.1.3 shall be provided.
13.7.2 The switchboards shall be provided with suitable quantity and type of
outgoing feeders for the auxiliaries, control supplies to various
panels/systems. For each load and auxiliary, one separate feeder shall
be provided. In addition, the following feeders shall be provided in
switchboard.
(a) Spare feeders - 20% of each type and rating with a minimum of
two nos. feeders. This is the minimum quantity at the time of
handing over the plant.
The continuous current rating of the bus bars, incomers, ties for 220V DC
switchboards shall be the maximum D.C. load (excluding the momentary
ISSUE
R0
219
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.13
SHEET 8 OF 14
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - DC SYSTEM SPEC. NO.
TCE.5960A-H-500-001
load) on the bus plus 20% margin rounded off to the next higher standard
rating.
(d) All the DCDB compartments shall have bottom cable entry
through individual cable gland for each power, control and
instrumentation cables. Metallic enclosure shall be provided
between cable tray & cable entry.
(i) Incomer
220
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.13
SHEET 9 OF 14
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - DC SYSTEM SPEC. NO.
TCE.5960A-H-500-001
ISSUE
R0
221
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.13
SHEET 10 OF 14
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - DC SYSTEM SPEC. NO.
TCE.5960A-H-500-001
All tests shall be conducted as per the relevant standards. Tests shall
comprise:
13.8.3 A loading resistor bank which can be automatically controlled using time
and current signals along with the charger shall be supplied to facilitate
discharging of voltages as a part of routine maintenance tests.
13.9.4 Voltage regulation for rated input supply for loads from 0-100%.
13.9.5 Load test to show the charger can deliver the rated duty without the
current limiter device operating.
13.9.9 High voltage test, excluding electronic controller, at 2kV AC for one
minute.
13.9.10 Heat run test shall be conducted at full load for 24 hours at the vendor
works on charger.
ISSUE
R0
222
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.13
SHEET 11 OF 14
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - DC SYSTEM SPEC. NO.
TCE.5960A-H-500-001
13.10.1 All routine tests as per applicable standards shall be conducted on the
board.
ISSUE
R0
223
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT SECTION: D3.13
COMPANY LIMITED
DATA SHEET – A3.13 SHEET 12 OF 14
SPEC. NO.
TCE.5960A-H-500-001
SL. NO. DESCRIPTION UNITS VALUES / REQUIREMENTS
1.0 DC SYSTEM
2.3 Minimum end cell voltage Nickel / Lead Acid 1.85V per cell
3.2 Voltage stabilisation for constant voltage (i) +1% of set DC voltage for + 10%
regulator voltage and +5% frequency variation in
power supply
3.3 DC current adjustment for boost charging 30% to 100% of maximum boost charging
current
4.0 DC BOARD
5.3 Metal clad base material for printed circuits for IS 5921
use in electronic and telecommunication
equipment
SHEET 1 OF 13
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEM -
UNINTERRUPTIBLE POWER SUPPLY SYSTEM SPEC. NO.
TCE.5960A-H-500-001
ISSUE
R0
227
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D.3.14
SHEET 2 OF 13
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEM -
UNINTERRUPTIBLE POWER SUPPLY SYSTEM SPEC. NO.
TCE.5960A-H-500-001
power outages. The UPS shall be sized considering full load plus
spare loops plus 20% margin.
14.3 Static UPS system provided shall be of the type described below:
14.3.1 UPS shall derive power from station service switchgear and
Normal/ Emergency switchgears as shown in the sketch for UPS
scheme Drawing No. TCE.5960A-EL-SK-2005. UPS Battery shall
be High Discharge Lead Acid Plante type with 4 hour duration.
Parallel redundant UPS with static bypass to regulated supply shall
be as per sketch No. TCE.5960A-EL-SK-2005.The system shall
have a combination of two inverters (UPS modules) operating in
synchronism, each having isolating facility from the critical bus by a
static switch. In addition to the two inverter systems, a backup from
a regulated AC supply through transformer and voltage stabilizer
derived from Station service switchgear shall be provided. The
system shall have a selector switch. In the `Normal' position, the
respective UPS loads shall be supplied by its own inverter, sharing
50% load each, with output of both inverters being automatically
synchronized with each other, by using synchronising signal from
the master inverter. If one inverter fails, the healthy inverter shall
supply the full 100% load by the operation of the static switch.
When any one of the UPS is under maintenance, the selector
switch shall be suitably changed and the branch circuit supplying
100% load shall be synchronised with the frequency of the standby
source.
14.3.2 If the frequency of the standby source is beyond the preset limit,
the inverter frequency control shall get disconnected from the
standby synchronising signal. The operating inverter shall
continuously monitor the frequency of standby source and upon
restoration of proper frequency of the standby source, the inverter
shall use the frequency of the standby source as the synchronising
signal. It shall be ensured by the contactor that the bandwidth
selected for the UPS to remain locked with the SCVS frequency
shall be maximum & the downstream instrumentation system
should be capable of accepting the above frequency variations.
14.3.3 When the selector switch is in bypass position the standby source
shall cater 100% load, isolating both inverters from the critical load
bus.
The output of the UPS shall feed all the essential loads through
the ACDB.
ISSUE
R0
228
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D.3.14
SHEET 3 OF 13
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEM -
UNINTERRUPTIBLE POWER SUPPLY SYSTEM SPEC. NO.
TCE.5960A-H-500-001
14.3.4 Rectifier
14.3.5 Inverter
14.3.7 Battery
229
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D.3.14
SHEET 4 OF 13
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEM -
UNINTERRUPTIBLE POWER SUPPLY SYSTEM SPEC. NO.
TCE.5960A-H-500-001
BIDDER shall furnish calculation for sizing of the battery based on the
requirements of entire plant UPS loads.
14.3.11 Protection
14.3.12 Tests
(a) Type and routine tests certificates for all components made
use in the UPS system shall be furnished. Tests for
components shall be as per relevant standards.
230
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D.3.14
SHEET 5 OF 13
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEM -
UNINTERRUPTIBLE POWER SUPPLY SYSTEM SPEC. NO.
TCE.5960A-H-500-001
Sl. Contractor’s
Description Specification Requirement
No. Unit Details
0
4. Ambient temperature C 50
ISSUE
R0
231
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D.3.14
SHEET 6 OF 13
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEM -
UNINTERRUPTIBLE POWER SUPPLY SYSTEM SPEC. NO.
TCE.5960A-H-500-001
Sl. Contractor’s
Description Specification Requirement
No. Unit Details
7. Degree of protection IP 32
12.0
Inverters
12.4 Service
Indoor
ISSUE
R0
232
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D.3.14
SHEET 7 OF 13
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEM -
UNINTERRUPTIBLE POWER SUPPLY SYSTEM SPEC. NO.
TCE.5960A-H-500-001
Sl. Contractor’s
Description Specification Requirement
No. Unit Details
ISSUE
R0
233
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D.3.14
SHEET 8 OF 13
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEM -
UNINTERRUPTIBLE POWER SUPPLY SYSTEM SPEC. NO.
TCE.5960A-H-500-001
Sl. Contractor’s
Description Specification Requirement
No. Unit Details
13.5 Frequency Hz 50
ISSUE
R0
234
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D.3.14
SHEET 9 OF 13
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEM -
UNINTERRUPTIBLE POWER SUPPLY SYSTEM SPEC. NO.
TCE.5960A-H-500-001
Sl. Contractor’s
Description Specification Requirement
No. Unit Details
a) Static switch
connected to
alternate source
b) Alternate source
voltage deviation
greater than ± 2%
from nominal.
ISSUE
R0
235
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D.3.14
SHEET 10 OF
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST. 13
ELECTRICAL SYSTEM -
UNINTERRUPTIBLE POWER SUPPLY SYSTEM
SPEC. NO.
TCE.5960A-H-500-001
Sl. Contractor’s
Description Specification Requirement
No. Unit Details
16.0 ACDB
Note:
‘*’ indicated above shall be filled by the Contractor.
ISSUE
R0
236
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT SECTION: D3.14
COMPANY LIMITED
DATA SHEET - A3.13 SHEET 11 OF 13
SPEC. NO.
TCE.5960A-H-500-001
SL. NO. DESCRIPTION UNITS REQUIREMENTS
SHEET 1 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
15.1.1 For 6.6 kV services, XLPE cables with following specification shall be
provided.
15.1.2 For 400 V power supply services, space heating, outdoor lighting, lighting
in the hazardous areas, power supplies to lighting panels etc., XLPE
power cables with the following specifications shall be provided:
ISSUE
R0
240
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 2 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
15.1.4 For low voltage digital signals to instrumentation and control system and
for the analog signals, instrumentation cables with following specification
shall be provided :
15.1.5 Cables for important auxiliaries such as emergency lube oil pump motors,
jacking oil pump motors, barring gear motors, Trailing power and control
cables for cranes & hoist, DC cables from battery to charger and DCDB
etc. shall be of fire survival type (FRLS cables).
15.2 The HV & LV power cables shall be selected on the basis of current
carrying capacity, short circuit rating and permissible voltage drop.
The cable shall be able to carry the full load current of the circuit
continuously under the specified ambient temperature and other
conditions of installation. For this purpose, suitable derating factors shall
be considered due to:
(c) Derating factor for grouping of cables over the current ratings at
normal conditions given in standards. The design ambient air
temperature and ground temperature for this plant shall be considered
as 500C and 300C respectively.
ISSUE
R0
241
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 3 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
The cables for circuit breaker controlled circuits shall withstand the fault
currents for the following fault clearing times.
For circuits, which are protected by fuse, short circuit rating capability
need not be checked.
400V System: Voltage drop in cables between the transformer and the
switchgear (PCC) or between PCC and MCC for full load current shall be
limited to 2%. Further, the voltage drop in cables between PCC/MCC to
the motor terminals for full load motor current shall be limited to 3%.
However, these voltage drops may be adjusted in specific cases so that
total voltage drop is within 5%. The screen of the 6.6kV cable shall be
capable of carrying the earth fault current of 6.6kV system for 2 sec.
(a) 400V system: The voltage dip during starting of individual 400V
motors shall be limited to less than 15% of the full load voltage.
(b) 6.6kV system: The voltage drop during starting of HRSG cooling
pump motors shall be limited to less than 20% of the full load
voltage, for all other motors it shall be 15%.
15.2.6 All D.C. power supply cables shall be single core cables.
ISSUE
R0
242
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 4 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
15.3.1 Current transformer leads shall be checked for lead burden, VA capacity
and knee point voltage. In case 2.5 mm2 Copper Conductor is not
adequate, 4 mm2 cross-section cables shall be used.
15.4.1 The cross sectional area shall be 0.5mm2 based on the requirement of
I&C system employed.
15.4.2 The instrumentation cables carrying digital signals shall have overall
screening along with drain wire and analog signal carrying cables shall
have each pair screening and overall screening along with each pair drain
wire and overall drain wire.
Colour coding shall be acceptable for all cables upto 5 cores. Cables with
more than 5 cores shall have printed numerals on each core. In addition
to manufacturer's identification on cables as per IS, following marking
shall also be provided over outer sheath:
(a) Cable size and voltage grade - To be embossed
15.5.2 Core numbers with a minimum letter size of 3 mm shall be printed serially
on each core of the control cable at intervals of not more than 200 mm.
15.5.3 Core numbers with a minimum letter size of 2 mm shall be printed serially
on each core of the Instrumentation cable at intervals of not more than
200 mm and each core shall be colour coded as per IEC-60189 Part-2
15.5.4 FRLS PVC compound for outer sheaths of all the cables shall meet the
following performance requirements and cables shall pass these tests.
ISSUE
R0
243
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 5 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(d) The cables shall pass the hydrolytic stability and ultraviolet test as
per DIN 53387. The measured values of ultimate tensile strength
and elongation after the test shall not be less than 60% of that
measured before the test.
15.5.5 The finished cables shall pass the flammability test as per IEC-60332-1
and IEC-60383. In addition it shall also pass flammability test as per
class F3 of Swedish Standard S5-424-1475.
15.5.6 In plant repairs to the cables shall not be accepted. Pimples, fish eye,
blow holes etc. are not acceptable.
15.5.8 Each drum shall carry manufacturer's name, Owner's name, address and
contract number, item number and type, size and length of cable and net
gross weight stenciled on both sides of the drum. A tag containing same
information shall be attached to the leading end of the cable. An arrow
and suitable accompanying wording shall be marked on one end of the
reel indicating the direction in which it should be rolled.
15.5.9 The cross-sectional area of the metallic screen strip/tape shall be
considered in design calculations.
ISSUE
R0
244
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 6 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
15.6 Tests
15.6.1 The Contractor shall conduct the routine tests on each drum length,
acceptance test on the cables as per applicable standards. Tests
certificates of all type tests as per applicable standards conducted on
similar cables shall be submitted for review. Also special tests for critical
oxygen index, temperature index values, acid gas generation, smoke
generation, flammability test, effects of light and water test as specified
shall be conducted on specimen, from different batches. Routine tests
shall include but not limited to the following for instrumentation cables.
15.6.2 Test for dielectric strength for one minute (as per IEC-60189-1)
15.6.4 The vendor shall carry out all routine tests as per IEC.60189-1 for
instrumentation cables
(a) Cables shall be always laid above ground to all locations including
outgoing areas with cable trays supported on overhead steel
structure works. Cable tranches shall be provided in switchyard and
transformer yard. Any deviation may e subjected to Owner’s approval.
Following cable carrier system shall be adopted in various areas as
indicated below.
ISSUE
R0
245
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 7 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
ISSUE
R0
246
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 8 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(iv) The spacing of rungs for ladder type of trays shall be not
more than 250 mm.
ISSUE
R0
247
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 9 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
ISSUE
R0
248
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 10 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
conforming to IS.
(iv) The hume pipes/RCC pipes shall comply with IS: 458.
ISSUE
R0
249
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 11 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(ii) In trenches & tunnels the width of the cable tray shall be
limited to 600 mm. In case of horizontal trays it shall be
limited to 800 mm.
(vi) Vertical trays (raceways) and all outdoor cable trays shall
be provided with removable 16 guage galvanised MS
sheet covers.
ISSUE
R0
250
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 12 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(x) No cables shall be mounted near hot zones like hot flue
gas duct, steam pipe, etc.
15.7.1 Cables to each circuit shall be laid in one continuous length. Cable
jointing and splicing shall be avoided. Jointing will be allowed only for the
cases where the route length is more than the maximum possible drum
length.
(a) Where cables cross roads and water, oil, gas or sewage pipes, the
cables shall be laid in hume or steel pipes. For road crossings, the
pipe for the cable shall be buried at not less than 600 mm. Hume
pipes shall be preferred to steel pipes from the point of view of
corrosion.
(b) The cables shall be tied to tray rungs by means of 3mm dia. nylon
cord at an interval of 5000 mm and also at bends.
ISSUE
R0
251
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 13 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(a) Different voltage grade cables shall be laid in separate trays. When
trays are arranged in tiers, HV cables shall be laid in top trays and
cables of subsequent voltage grades in lower tiers of trays.
(c) 1100V grade power cables of 120 mm² size and above shall
normally be laid in single layer in trays/on racks.
(d) Smaller 1100V grade power cables below 120 mm² may be run in
double layers, where required, due to space restrictions.
(g) Control cables and small power cables on racks shall be run in
ladder type cable trays supported on rack carrier arms. The cables
shall be tied to tray rung by means of 3 mm dia. nylon cord at an
interval of 5000 mm and also at bends.
ISSUE
R0
252
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 14 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
The bending radii for various types of cables shall not be less than those
values specified by the cable manufacturer.
(a) Cable entry to motors, push button stations and other electrical
devices shall be from the bottom as far as possible or from the
sides. Top entry of the cables is not acceptable particularly for
outdoor equipments.
(c) All cable terminations shall be done with solderless crimping type
lug. Cable terminations shall be done with double compression
type brass cable glands.
ISSUE
R0
253
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 15 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
15.7.6 Termination and jointing kits for 6.6 kV grade XLPE insulated cables shall
be of proven design and make which have already been extensively used
and type tested. Termination kits and jointing kits shall be heat shrinkable
type/push on type. 6.6 kV grade joints and terminations shall be type
tested as per IS:13573. Cable jointing shall be carried out only by
Raychem certified jointers only. Straight through joint and termination
shall be capable of withstanding the fault level for the system. 1.1 kV
grade Straight Through Joint shall be of proven design.
(a) Cables shall be checked for insulation resistance before and after
jointing.
All cables of 1.1 kV grade 400 mm² and above and all HV cables
shall be subjected to DC or AC (preferably DC) high voltage test
after terminating but before commissioning as per Table 4 in
IS: 1255.
15.7.8 Earthing
(a) Metallic sheaths, screens and armour of all multicore cables shall
be earthed at both equipment and switchgear end.
(b) Sheath and armour of single core power cables shall be earthed at
switchgear end only. For long lengths of cables multiple earthing
may have to be adopted to safeguard against the presence of
standing voltages under normal as well as fault conditions.
ISSUE
R0
254
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 16 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(b) The FPS system shall also include all the necessary accessories
and equipment required for supporting, holding in position, fixing
and installation of the fire-stop/fire-break.
(c) The FPS system shall comply in all respects with the
requirements of the codes and standards listed below
IEEE-634
ASTM-E-814
ANSI-IEEE-383
IEC-60331
IEC-60332
ISSUE
R0
255
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 17 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
ISSUE
R0
256
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 18 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
15.7.10 Contractor shall furnish the test certificates for the fire stops and fire
breaks after award of contract for Owner’s review. If the certificates are
not satisfactory all the tests shall be conducted free of cost. The offered
system i.e. fire stops and fire breaks shall be identical (or better) with the
system which is successfully type tested for the specified rating i.e. the
composition density of the material, thickness of coating in case of fire
breaks and any other properties of the material / system offered shall be
identical or better than the tested system and shall be subject to Owner’s
approval.
(a) The fire stops shall be subjected to the following type tests:
During the fire rating test, the transmission of heat through the
cable penetration fire stop shall not raise the temperature on its
unexposed surface above the self ignition temperature of the
outer cable covering, the cable penetration fire stop material, or
material in contact with the cable penetration fire stop, with a
maximum temperature limit on the unexposed surface of 200oC.
ISSUE
R0
257
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.15
SHEET 19 OF 19
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - CABLING SYSTEM SPEC. NO.
TCE.5960A-H-500-001
ISSUE
R0
258
TCE FORM NO. 329 R5
5.7
SHEET 1 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
Lighting system shall be provided for the proposed plant covering all the
buildings, outdoor areas, roads, yards, boundary, etc. The lighting
system shall be to owner’s approval, having good aesthetics and
designed to provide the required illumination levels in all areas and to
meet the fire and safety codes.
16.1.1 The plant lighting system shall comprise the following four (4) categories:
In this system, the lighting circuits shall be fed by the 400V, 3 phase, 4
wire, normal AC supply available from the normal lighting distribution
boards. All the lighting fixtures connected to this system shall be
available as long as supply is available from normal source viz., auxiliary
transformer.
ISSUE
R0
259
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 2 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
(c) Lighted exit signs shall be provided and installed in the control &
switchgear room, relay room, maintenance area etc.
ISSUE
R0
260
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 3 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
(b) AC lighting panels shall have 3 phase, 4 wire incomer with ELCB
and number of 1 phase outgoing circuits controlled by MCBs.
Lighting panels feeding the Lighting fixtures in indoor areas shall
be controlled from the respective lighting panels located in
various buildings in the plant. Road, yard lighting and aviation
warning lights also shall be contactor controlled. All outdoor
lighting system and aviation warning lighting system shall be
automatically controlled through photoelectric controllers.
Provision to bypass the timer or photocell shall be provided in the
panel. Also manual switching `on and off' facility shall be
provided. The Infrared sensing system shall be used for the
control of lighting in unmanned substations.
261
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 4 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
262
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 5 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
263
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 6 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
(c) Equipment room (Pump house, 250 Industrial high bay / medium 1x400W / 1x150W
Compressor & DG house) bay depending on height Metal Halide Lamp
(HPMV)
6. DM Plant / Filtration Plant
(a) General 250 Corrosion proof 1 X 70 WHPSV
7. Road and yard lighting
(a) Main roads 20 Street light with clear acrylic 1 x 70W / 150W
cover cut-off type with integral HPSV
Secondary roads 10
mounted control gear or LED
fixtures with control gear.
(b) Perimeter (compound) lighting 20 - do - - do -
(c) Parking area (Indoor / sheds) 70 General purpose flood light, 1 x 250 W HPSV
high/medium beam flood light
8. Workshop building 300 Industrial type with vitreous 2X36W F.L x
enamel reflectors/industrial 250W HPSV
high bay
9. Administration Building
(a) Main office areas cabins (air 200-250 Decorative recessed type with 2 x 36W F.L.
conditioned areas) mirror optic reflector
(b) Main office areas, cabins with 200-250 - do - - do -
false ceiling but non-air-
conditioned
(c) Main office areas, cabin non air- 200-250 Decorative with wide angle - do -
conditioned areas without false mirror optic reflector
ceiling
(d) Warehouse, canteen, medical 150 Industrial type with vitreous 2 x 36W F.L.
centre enameled reflector
10. General
(a) Corridors, walk-ways, staircase, 150 Industrial type with vitreous 2 x 36 W F.L.
etc. enamel reflectors/channel
mounted box type compact
flourescent lamp
(b) Lockers, toilets, wash rooms, 100 Channel mounted box type 2 x 36 W F.L.
etc.
(c) Building periphery lighting - Industrial well glass with 1 x 70 W HPSV
integral mounted control lamp
gear/industrial bulk head with
ISSUE
R0
264
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 7 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
The illumination levels for areas, which are not specifically covered
above, shall be decided based on illumination levels indicated for similar
areas or in relevant standards.
The lighting system design shall comply with the acceptable norms and
the best engineering practices. The system design shall consider
principles of lighting specified in following paragraphs. The lighting layout
shall be designed to provide uniform illumination with minimum glare.
The layout design shall meet all the statutory requirement, local rules etc.
The illumination level for various areas in the plant is indicated in the
table above. Following factors shall be considered while arriving at the
utilisation factor to determine the number of fixtures for each
area/building in the plant.
ISSUE
R0
265
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 8 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
(c) The value of the ratio of spacing (S) to mounting height (H) shall
be commensurate with the type of fittings selected, uniformity of
illumination. The suspension height for suspended fixtures shall
not exceed 1 metre.
(d) The control room lighting shall be designed such that no glare
from the lighting appears on the DCS-CRT from any angle.
(d) The control gear for street light shall be of non integral type i.e.,
the control gear of the light fixture shall be mounted at the foot of
the pole.
16.4.3.1 The type of luminaires and accessories like switches, receptacles etc.,
shall be selected based on the plant area in which they are intended to
be used. Lighting fixtures shall be explosion proof in hazardous and fuel
oil areas.
ISSUE
R0
266
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 9 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
16.4.3.2 All fluorescent fixtures, shall have electronic chokes with low harmonics &
energy efficient 'T5' type fluorescent lamps except the fluorescent fixtures
used for division 2 hazardous area. The louvers of these fixtures shall be
designed for 'T5' type fluorescent lamps. All fluorescent lamps shall be
have "Cool day light" colour designation. The mirror optics type
fluorescent fixtures shall have no iridescence effect.
16.4.3.3 All HPSV and HPMV lamp fixtures or LED fixtures shall be provided with
wire-wound ballasts. All fluorescent fixtures except for Class-I, Div-II
fittings/ increased safety fittings (Div-II/Hazardous Area) shall be provided
with electronic ballasts.
16.4.3.4 Conduits, Pipes and Accessories Galvanised heavy duty steel conduits
for normal area and galvanised heavy duty steel conduits with an
additional epoxy coating for corrosive area shall be offered.
16.4.3.5 Rigid steel conduits shall be heavy duty type, hot dip galvanised
conforming to IS : 9537 Part-I & II shall be suitable for heavy mechanical
stresses, threaded on both sides and threaded length shall be protected
by zinc rich paint. Conduits shall be smooth from inside and outside.
16.4.3.6 Flexible conduit shall be water proof and rust proof made of heat resistant
lead coated steel.
16.4.3.7 Pull out boxes shall be provided at approximately 4 (four) metre interval in
a conduit run. Boxes shall be suitable for mounting on Walls, Columns,
Structures, etc. Pull-out boxes shall have cover with screw and shall be
provided with good quality gasket lining. Pull out boxes used outdoor
shall be weather proof type suitable for IP :55 degree of protection and
those used indoor shall be suitable for IP :52 degree of protection. Pull
out box & its cover shall be hot dip galvanised.
16.4.3.8 The poles shall be of ERW tubes of specified lengths, swaged tubular and
joined together. The complete pole shall be hot dip galvanised. The
terminal boxes for the lighting pole shall be IP55 protected & of glass
reinforced epoxy type.
16.4.3.9 Lighting Mast shall be of continuously tapered polygonal cross section hot
dip galvanised. The Mast shall be of 30M height with lantern carriage to
enable raising/lowering for ease of maintenance, including the Head
Frame, Double Drum Winch, continuous stainless steel wire rope, in built
power tool, luminaries, suitable aviation warning light, lightning along with
necessary power cables within the mast. The mast shall be delivered only
in three sections & shall be joined together by slip stressed fit method at
site. No site welding or bolted joints shall be done on the mast.
ISSUE
R0
267
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 10 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
(a) In the plant areas, the lighting circuits shall be controlled directly
from the MCBs in the lighting panels. Wherever the lighting panel
is not in the same area, separate switches shall be provided. For
cabins, rooms etc., separate switches shall be provided for each
point. Similarly for entrances, building periphery lighting separate
switches shall be provided.
(b) Receptacles with MCB (5A and 15A) shall be provided in all
building/areas of the plant. Also inside a building, receptacles
shall be provided at regular intervals so that any point of the
building is not more than 10 m with a minimum of 2 nos., in an
enclosed area. Inside each cabins atleast two receptacles shall
be provided. The same shall be indoor/outdoor/flameproof as per
the location. Suitable no. of 63A, 3 phase, 400VA.C industrial
heavy duty receptacles shall be provided for outdoor plant for
welding purpose. The industrial receptacle shall be provided at
an average distance of 50 mts. At-least two 63A, 3 phase, 400V
industrial heavy duty type receptacle shall be provided in each
building. It shall be metal enclosed with SFU and housed inside
with suitable connection for cabling and receptacles.
Each of the LDBs shall be provided with voltmeter and ammeter along
with selector switches, `Supply On' indicating lamps, etc. The LDBs and
LPs shall be sheet steel enclosed and shall be fully dust and vermin
proof, with a degree of protection of IP 54. Outdoor panels shall be
weather proof type with IP - 54 degree of protection. LDBs, LPs shall be
explosion proof wherever provided in hazardous and fuel oil areas. The
ISSUE
R0
268
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 11 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
16.4.7 Wiring
(b) Minimum size of wires in case of conduit wiring shall be 2.5 mm2
in case of lighting and 4 mm2 in case of receptacle wiring.
Minimum cable size in case of cable wiring shall be 4 mm2 for
lighting and 6 mm2 for receptacles.
(e) The wiring in the conduit shall be such that 20% space in the
conduit is free.
269
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 12 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
(c) The voltage drop from LDB and any fixture shall not exceed 3%.
(d) The contractor shall submit design calculation for sizing of LDBs
and also provide lumen contour for the main road and other
areas. Contractor shall demonstrate the same at location
decided by Owner.
16.4.9 Earthing
(b) For fixtures in hazardous areas, the third core of each single-
phase armoured cable circuit shall be used as earthing
conductor.
16.5 Tests
16.5.1 Type test reports of the following items as per relevant standards shall be
submitted for approval.
i. Lighting fixtures of each type
ii. Lamps of each type and rating.(life cycle and rating test
only)
ISSUE
R0
270
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 13 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
16.5.2 All acceptance tests & routine tests for the lighting fixtures and
accessories covered in this specification shall be carried out as per the
relevant standards listed under "Codes and Standards” given below for
the respective fixtures/ components. Type test certificates shall be
furnished for review.
ISSUE
R0
271
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 14 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
ISSUE
R0
272
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 15 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
ISSUE
R0
273
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.16
SHEET 16 OF 16
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - LIGHTING SYSTEM TCE.5960A-H-500-001
16.6.62 Fittings for Rigid Steel Conduits for Electrical Wiring IS 2667
ISSUE
R0
274
TCE FORM NO. 329 R5
5.8
SHEET 1 OF 7
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
EARTHING & LIGHTNING PROTECTION SYSTEM TCE.5960A-H-500-001
Earthing system shall consist of earth grids and electrodes buried in soil
in the plant area, embedded in concrete inside the buildings to which all
the electrical equipment, metallic structures are connected to have earth
continuity for safety reasons.
ISSUE
R0
275
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.17
SHEET 2 OF 7
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
EARTHING & LIGHTNING PROTECTION SYSTEM TCE.5960A-H-500-001
17.2.1 The earthing system design and installation shall generally comply with
IS-3043, IEEE-80 and Indian Electricity Rules.
17.2.2 General
(a) Metallic frames of all current carrying equipment, supporting
structures adjacent to current carrying conductors, lightning
ISSUE
R0
276
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.17
SHEET 3 OF 7
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
EARTHING & LIGHTNING PROTECTION SYSTEM TCE.5960A-H-500-001
(c) All cable trays in the plant buildings as well as inside the
trenches shall be connected to earth grid at an interval of about
10 m.
ISSUE
R0
277
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.17
SHEET 4 OF 7
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
EARTHING & LIGHTNING PROTECTION SYSTEM TCE.5960A-H-500-001
(f) Earthing grid design shall be done in such a manner that the grid
resistance is less than 0.5 ohm.
(b) In case, the building has more than one floor, each floor shall be
provided with earth grid. Floor earthing grids shall be
interconnected.
(d) Cable trays, steel pipes / conduits, steel columns, etc., shall not
be used as earth continuity conductors.
ISSUE
R0
278
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.17
SHEET 5 OF 7
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
EARTHING & LIGHTNING PROTECTION SYSTEM TCE.5960A-H-500-001
(g) Earthing grid design shall be done in such a manner that the grid
resistance is less than 0.5 ohm.
17.3.1 The spacing between two electrodes shall be atleast equivalent to twice
the length of the electrode.
17.3.3 The earthing conductor crossing the road / track shall be laid in hume
pipe or laid at a greater depth to avoid damage.
17.3.4 When earth conductor passes through floors, walls, etc., suitable pipe
sleeves shall be provided and the same shall sealed after installation.
17.3.5 The connection between earthing pads / terminal to the earth grid shall
be made short and direct and shall be free from kinks & splices.
17.3.6 Metallic conduits and pipes shall not be used as earth continuity
conductor.
17.3.7 Street lightning poles, flood light poles & towers, their junction boxes
shall be connected to the earthing conductor to be run along with supply
cable. This earth conductor shall be in turn connected to earth grid at two
extreme points.
17.3.9 Equipment bolted connection after being checked and tested shall be
painted with anti-corrosive paint / compound.
17.3.10 Connection between the equipment earth lead and the grid conductor
shall be welded. For rust protection, the welds shall be treated with zinc
chromate primer and coated with zinc rich paint.
ISSUE
R0
279
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.17
SHEET 6 OF 7
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
EARTHING & LIGHTNING PROTECTION SYSTEM TCE.5960A-H-500-001
17.3.11 The cable sheaths, screens armour shall be earthed at both ends for
multi-core cables. For single core cables the same shall be done at one
end (switchgear end) only.
17.3.13 Alternate switchyard fence posts shall be connected to the earth grid.
280
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.17
SHEET 7 OF 7
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - SPEC. NO.
EARTHING & LIGHTNING PROTECTION SYSTEM TCE.5960A-H-500-001
ISSUE
R0
281
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.18
SHEET 1 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(b) The quantity of the trunk cards and extension cards shall be
selected in such a way so as to provide 10% spare capacity.
Electronic cards with intelligent processors shall be provided.
The system shall have compatibility for analogue telephone
instruments, digital (key) telephone instruments, and the special
feature telephones. The system shall be supplied with the
operator console as an in-built feature. Operator console shall be
equipped with a PC with tracking provision for all calls, call times
etc. and PC shall have provision to come over office automation
LAN. One spare port for operator console shall be provided.
ISSUE
R0
282
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.18
SHEET 2 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(v) Two (2) dial testers for DC pulsing and DTMF telephone
instruments.
(vi) Three (3) line man hand held telephone sets with DC
pulsing and DTMF switchable with built in ringer unit and
crocodile clip.
ISSUE
R0
283
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.18
SHEET 3 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(g) EPABX shall have full self-diagnostic feature. All faults, besides
being annunciated by high intensity LED on the EPABX and
audio alarm, shall be displayed on the PC with component level
fault being displayed in English.
(h) The EPABX shall be provided with 120% capacity main power
supply unit with 100% standby power supply unit. On failure of
main unit, standby unit shall automatically cut-in. Annunciation
(audio and visual) shall be provided for each power supply unit
fail and also auto-changeover fail. Changeover time shall not
affect the EPABX/its allied systems in any way.
(j) The Bidder shall provide all the telephone instruments in the
plant areas at each working areas. The locations shall be
decided during detailed engineering. But the Bidder shall supply
at least 200 telephone instruments.
(ii) All desk type instruments for all subscribers shall have
keypad with push buttons.
ISSUE
R0
284
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.18
SHEET 4 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
ISSUE
R0
285
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.18
SHEET 5 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(b) Twenty (20) Nos. hand held two way transmitter receiver sets.
(d) The system shall be capable of being coupled with the EPABX
and PA systems such that any wireless set can be contacted
from any of the EPABX-intercom extensions or PA system and
from the DTMF keypad of the portable radios it should be
possible to contact any of the EPABX – intercom number
through the EPABX.
(e) The wireless sets shall be addressable type and light weight.
(g) The power supply to the entire base stations shall be through the
UPS, to allow the radio communications during “Black Out”
conditions also.
286
TCE FORM NO. 329 R5
5.9
SHEET 6 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
18.1.4 Cables
The type of cables and their technical particulars shall be as per the
requirement of the system for giving best performance.
18.1.5 Tests
(a) The Public Address System shall consist of zones, sub-zones and
Exchanges to interface all these zones among them selves. The
zones shall also cover all off-site Plant Auxiliary Systems and shall
be finalized during detailed engineering, taking into consideration
the configuration of the combined cycle plant.
ISSUE
R0
287
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.18
SHEET 7 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(d) The equipment furnished under this section shall meet the
requirements of all-applicable codes and standards as specified or
their equivalent international codes and standards.
(e) The Public Address System (PAS) offered by the Bidder shall be
from reputed manufacturer who should have designed,
manufactured, tested and commissioned a distributed amplifier
type industrial Public Address systems as specified in power
plants or large industrial installation as on the date of bid opening.
(f) The system shall be adequately protected from signal and power
line noise and meet the Surge Withstand Capability (SWC)
requirements of ANSI C37.90.1/ IEEE standard 472-1989
equivalent.
(i) All the items, including Public Address system erection hardware,
cables, cable erection hardware, telephone cables etc. as may be
required to make the PA system complete and functional are to be
furnished by the Contractor on as required basis.
The Bidder shall provide power to the Public Address System from UPS
system as detailed in Section D3.14 of technical specifications. The
details shall be finalized during detailed engineering stage. In case the
Bidder's offered equipment is operating at any other voltage level, the
Bidder shall provide all required hardware, to make the offered system
compatible with specified power supply arrangement. The system shall
be fully functional during the total power supply failure of the plant.
ISSUE
R0
288
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.18
SHEET 8 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(i) PAS shall have two modes, i.e., Paging mode and Party
mode. Each of the two modes shall be open line, common
talking type. Paging mode shall be used for locating a
person and for general instructions. Party mode shall be
used for conversation between individuals without
broadcasting the same over the loudspeaker.
ISSUE
R0
289
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.18
SHEET 9 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(ii) The Central Exchange shall have one master control unit
for each of the modules and one more master control unit
for Shift In charge Room. All the master control units shall
be connected in parallel. Any inter-zone communication
shall be possible through this master control unit. The exact
type of the same shall be decided during detailed
engineering. Further, it shall be possible to broadcast
recorded speech, music etc. over the loudspeakers.
ISSUE
R0
290
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.18
SHEET 10 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(f) All handset stations shall have a compact, robust, rust resistant,
shock-resistant body made of high impact polystyrene or
ISSUE
R0
291
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.18
SHEET 11 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(h) The handset stations in the noisy areas like Turbine Hall, BFPs,
etc., shall be housed in Acoustic hoods. An industrial type free
standing, floor mounted hood shall be used for providing the above
requirements. The design noise level within the hood shall be
limited to a maximum of 60 dB SIL.
18.2.5 Amplifiers
(a) Amplifiers shall be solid state, class-B, Push-pull type, in built with
the handset fully conforming to IS: 1301 & IS: 10426 or equivalent
international standard.
(b) Amplifiers shall have 0-100% volume control setting. with facility
for coarse and fine setting along with following controls which shall
be located inside the Handset Station.
18.2.6 Loudspeakers
ISSUE
R0
292
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.18
SHEET 12 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
ISSUE
R0
293
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.18
SHEET 13 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(ii) Amplifiers
(iii) Microphones
ISSUE
R0
294
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.18
SHEET 14 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(iv) Loudspeakers
18.2.11 The quantities for PA system mentioned below are minimum required
and will be finalised at the time of detailed engineering.
-----------------------------------------------------------------------------------------------
S.No Item Description PAS For Common Plant
(for each module)
--------------------------------------------------------------------------------------------------
1. Handset Stations
2. Loudspeakers
ISSUE
R0
295
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.18
SHEET 15 OF 15
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS – COMMUNICATION SYSTEM SPEC. NO.
TCE.5960A-H-500-001
(i) Sockets-(nos.) 10
5. Cables
ISSUE
R0
296
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.19
SHEET 1 OF 5
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS -
FIRE DETECTION AND ALARM SYSTEM SPEC. NO.
TCE.5960A-H-500-001
19.2 The equipment/system supplied shall comply with the standards listed
below:
19.2.1 IS - 2189
19.2.3 IS - 2175
19.3 The system shall be approved by any or all the following bodies besides
Tariff Advisory Committee (TAC) and Local Fire Authorities, National Fire
Protection Association (NFPA), Underwriters Laboratory (UL), Fire
Officer’s Committee (FOC), Factory Mutual (FM), Central Mining
Research Institute (CMRI), Dhanbad.
19.5 The type of detectors to be provided in the various areas of the plant shall
be as indicated below:
ISSUE
R0
297
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.19
SHEET 2 OF 5
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS -
FIRE DETECTION AND ALARM SYSTEM SPEC. NO.
TCE.5960A-H-500-001
These shall be resettable type i.e., the same detector shall be capable of
being reset after it goes to the alarm state.
19.7.1 This detector shall be capable of detecting a fire both in its incipient or
smouldering stages as well as visible flames. To meet this requirement
the detector shall respond to visible combustion products in the form of
smoke as well as in visible particles, aerosols and pyrolysis products from
a clear burning fire.
19.9.1 Linear heat detection system shall be provided in area below false floor
& in cable galleries.
19.9.2 Linear heat detection system shall essentially comprise sensor cables,
interface units and necessary hardwares required for installation.
ISSUE
R0
298
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.19
SHEET 3 OF 5
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS -
FIRE DETECTION AND ALARM SYSTEM SPEC. NO.
TCE.5960A-H-500-001
19.9.4 Linear heat sensor cables shall be run on all the trays below the false
floor of the control room. The sensor cables in cable vault end shall be
supported from ceiling to cover the top most tray and from underside of
the cable trays for bottom tiers.
19.10 The quantity of fire detectors and call points to be installed in each of the
areas shall be based on an average coverage area mentioned below.
The zones of individual detectors shall overlap and no blind zone shall be
left. However, the actual quantity of detectors required, taking into
consideration the obstruction due to floor beams, etc., so as to obtain
complete coverage, shall be worked out by the Contractor based on the
final drawings of the various buildings during detailed engineering.
19.10.2 15 to 20 sq.m per detector for I&C panel room, control room, relay room,
etc., in view of value concentration.
19.11 Each detector shall be provided with an indicating lamp glowing steadily
to indicate that it has operated which will otherwise flash intermittently to
indicate the healthy condition of the detector and sensing circuits.
19.12 When the detectors are mounted below the false floor or in inaccessible
position, response indicator for each of the detectors and test switch shall
be mounted on a separate box, which shall be suitable for mounting on
the wall. If the detectors are mounted above the false ceiling, response
indicators with test switch shall be mounted directly below the detector
(on the false roof).
19.13 Manual call points shall be provided as per the guidelines listed in NFPA
72E/IS 2189. Also, they shall generally be located near all the
entrances/exists for all buildings.
299
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.19
SHEET 4 OF 5
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS -
FIRE DETECTION AND ALARM SYSTEM SPEC. NO.
TCE.5960A-H-500-001
modules, etc. for satisfactory operation of the system. The panel shall
be located in the control room. Necessary interface shall be provided
between the fire alarm panel and plant DCS for monitoring the system.
A dedicated operator station shall provide in the Main control room. The
paint shade of panel shall be shade Opaline green (External) and semi
glossy white (Internal).
19.15.2 The main fire alarm panel will continuously monitor the status of the
detectors and the connecting lines. The annunciation system shall have
visual and audible alarms, with acknowledge, test, reset, lamp test, etc.
push buttons. The panel shall have 'ON / OFF' PBs for operation of fire
siren.
19.15.3 Main fire alarm panel shall be provided with necessary contacts for
performing the following functions.
19.15.5 High discharge plante Lead Acid batteries and battery chargers adequate
capacity shall be provided. The battery shall supply the normal power
requirements for a period of 48 hours from the instant of charger AC
supply failure, after which sufficient capacity would still be available to
provide full load operation for atleast 30 minutes. Full load being defined
as the load of all hooters sounding simultaneously along with operation of
all the associated visual signals, interlocks etc.
19.15.6 The detectors proposed to be provided for 400kV switchyard area shall
be connected to an independent fire alarm panel (with battery back-up)
located in Switchyard control room. This panel shall be suitably interfaced
with the main fire alarm panel in power plant control room. All the
constructional/functional features of this panel shall be same as the main
fire alarm panel.
ISSUE
R0
300
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.19
SHEET 5 OF 5
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS -
FIRE DETECTION AND ALARM SYSTEM SPEC. NO.
TCE.5960A-H-500-001
19.15.7 Visual alarm shall be povided in all the Control rooms, Electronic cubicle
room, Canteen, offices, conference halls and any other place where the
sound of the fire siren is not audible.
19.15.8 Suitable size & number of the sirens shall be used so that is audible in all
the direction & parts of the station.
19.15.9 All the fire alarm panels in the plant shall be of the same make.
19.15.10 The main fire alarm panel in the control room shall communicate with all
the fire alarm provided in the Gas / Steam Turbine area & in any other if
any.
19.18 Cabling
19.19 Tests
19.19.2 Performance tests shall be conducted at site on the system to prove that
the guarantees indicated for the individual components shall completely
satisfy all specific requirements. All tests required by the relevant
standards shall be conducted.
ISSUE
R0
301
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.20
SHEET 1 OF 10
1X700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - MOTORS SPEC. NO.
TCE.5960A-H-500-001
20.0 AC Motors
20.1 The motor and its accessories shall generally comply with the requirements
specified in the national and international standards indicated in Data sheet-
A3.20. Also Motors shall additionally comply with the specific requirements of
data sheet – A3.20 and specific requirements indicated below:
20.1.1 All HT motors shall be suitable for 6.6 kV, 3 phase, 50 Hz and LV motors shall
be suitable for 400 V, 3 Phase, 50 Hz power supply. The supply voltage and
frequency variation for 6.6 kV & 400 V shall be ±10% and +3/-5%
respectively. The combined voltage and frequency variation shall be of 10%.
20.1.2 The motors rated 175 kW and above shall be 6.6kV and motors rated upto
175 kW shall be 400 V. All LT motors shall be energy efficient. Motors shall
be continuously rated (S1). However, crane motors shall be rated for S4 duty,
40% cyclic duration factor. Motors shall be capable of starting and
accelerating the load with the applicable method of starting without exceeding
acceptable winding temperatures when supply voltage is 80% of the rated
voltage for HT motors and 85% for LV motors. HT motors shall also be
capable of satisfactory operation at full load at a supply voltage of 80% of the
rated voltage for 5 min. commencing from hot condition. The motors shall be
suitable for starting at 110% of the rated voltage.
20.1.3 Motors shall be capable of developing the rated full load torque even if the
supply voltage drops to 70% of the rated voltage. If such operation is
envisaged for a period of one second, the pull out torque of the motor shall be
atleast 205% of full load torque.
20.1.4 Motors shall withstand for 1 second the voltage and torque stresses
developed due to the vector difference between the motor residual voltage
and the incoming supply voltage equal to 150% of the rated voltage during
fast change over of buses.
20.1.5 Locked rotor current of motors rated 1500 kW and below shall be limited to
600% inclusive of 20% tolerance of the full load current of the motors and
motor rated above 1500 kW shall be limited to 450% (inclusive of 20%
tolerance) of full load current of the motor.
20.1.6 The locked rotor withstand time under hot condition at 110% rated voltage
shall be more than the starting time at minimum permissible voltage specified
above by atleast three seconds or 15% of the accelerating time whichever is
greater. Provision of speed switch shall be avoided to the extent possible.
ISSUE
R0
302
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.20
SHEET 2 OF 10
1X700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - MOTORS SPEC. NO.
TCE.5960A-H-500-001
20.1.7 The degree of protection for the motor enclosure shall be IP-55 and IP-54 for
outdoor & indoor respectively and outdoor and indoor cable boxes shall be
provided with IP-55 and IP-54 respectively.
20.1.8 All HT motors shall be provided with vibration pads (in both X & Y directions
and at both DE & NDE) for mounting vibration detectors. Requirements of
vibration monitoring system shall be as specified in relevant I&C section of
specification.
20.1.9 Motors rated 1000 kW and above shall be provided with differential
protection. These motors shall be provided with star connected stator
windings. The 3 nos. current transformers, one for each phase shall be
mounted in a separate compartment in the neutral side terminal box. The
three phases shall be connected to form the star point after they pass
through the CTs. The CTs shall be of relay accuracy and the CT
characteristics shall be compatible with the differential relay. The additional
3 nos. CTs of identical characteristics shall be provided in the 6.6 kV
switchgear panel.
6.6kV & 400V motors wherever their protection is through the numerical
relay then energy meter reading shall be taken through relay itself by
communicating with it.
20.1.10 The ring oiling system shall be adequate for starting and continuous
operation of the motor for atleast one half hour without pressure oiling
system in operation.
20.1.11 For 6.6 kV motors, 6 nos. duplex RTDs for winding shall be provided. Each
bearing shall be provided with duplex thermocouple for bearing temperature
monitoring. These motors shall be designed to withstand atleast 2%
unbalance in supply voltage. In addition to temperature monitoring & alarms
in DCS local temperature indicators shall be provided for motor bearings.
Motor bearing shall not be subjected to external thrust loads.
20.1.12 The maximum double amplitude vibrations for motors upto 1500 rpm shall be
25 microns and 15 microns upto 3000 rpm. For 400 V motors, maximum
double amplitude vibrations upto 1500 rpm shall be 40 microns and 15
microns upto 3000 rpm.
20.1.13 Maximum noise level measured at a distance of 1.5 metre from the outer
surface of the motor shall not exceed 85 db(A).
ISSUE
R0
303
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.20
SHEET 3 OF 10
1X700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - MOTORS SPEC. NO.
TCE.5960A-H-500-001
20.1.14 Cable boxes of all 6.6 kV motors shall be provided with quick disconnecting
type terminal connectors to facilitate easy disconnection and removal of the
motors without requiring unsealing or otherwise disturbing the external cable
connections and leaving the phase segregated terminal box intact.
20.1.15 Terminal boxes shall have fault withstand capacity equal to at least rated
short circuit level of the system voltage for 0.25 sec. The terminal boxes
shall be reversible to suit cable entry from bottom or top.
20.1.16 Separate terminal boxes to be provided for space heater, RTDs for winding
bearings temperature, vibration monitors etc. All terminal boxes shall be
provided with two earthing studs for termination of protective earth
conductor. Double compression type brass cable glands and crimping type
copper lugs shall be provided for termination.
20.1.17 The insulation system for 6.6 kV AC motors shall withstand the negative or
positive 0.3 / 3.0 microsecond wave (2.7 pu rated peak line to earth
operating voltage) switching surges originating from non-effectively earthed
power system. All 6.6 kV AC motors shall have BIL of 36 kV (Peak) 1.2 / 50
microsecond wave and shall withstand a power frequency voltage of 14.2 kV
(rms) for one minute.
20.1.19 Variable frequency controller shall be provided for motors requiring speed
control.
20.2 DC Motors
20.2.1 DC motors shall be suitable for the DC system voltage available in the plant.
Motor shall be capable of starting and accelerating the load with the
applicable method of starting, without exceeding acceptable winding
temperatures, when the supply voltage is in the range of 85% to 110% of
rated motor voltage.
20.3.1 The actuator motors shall be designed for short time duty (S2) in accordance
with IEC 60034-1.
ISSUE
R0
304
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.20
SHEET 4 OF 10
1X700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - MOTORS SPEC. NO.
TCE.5960A-H-500-001
20.3.3 The DC and AC actuator shall be provided with accessories viz., torque limit
switch, end of travel switch, adjustable limit switch, hand wheel motor,
thermostat, integral starter, etc. Complete actuator shall be tested at factory
as per IS 9334.
20.3.4 Two normally open and two normally closed or two changeover potential free
contacts corresponding to open and close positions of the valve shall be
provided. Open / Close limit switches used for interlock operation shall be of
proximity type.
20.3.5 Degree of protection for actuator motor enclosure shall be IP-55 and IP-67
for indoor and outdoor respectively.
20.3.6 The remote position of the valve along with its status indication with trip shall
also be shown in the DCS & local.
20.3.8 All the valves shall be of Integral type with field bus compatible.
20.4.1 For small rating motors cooling shall be of TEFC type but for higher rating
motor TETV, CACA & CACW type cooling shall be considered.
20.4.2
All electric motors shall be chosen from the supplier’s standard
manufacturing program and in accordance with the absorbed load of the
driven machine, using the API Recommendation No.610, 617 and 618 for
the overrating ratio.
20.5 Tests
20.5.1 Tests on all types of motors shall be conducted as per relevant standard.
20.5.2 For 6.6 kV, 400 V motors and DC motors, if type test certificates are
available for the same rating of the motors offered, the same shall be
furnished, else it shall be conducted. However, all routine and acceptance
tests shall be conducted on all 6.6 kV, 400V and DC motors as per relevant
standards.
ISSUE
R0
305
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.20
SHEET 5 OF 10
1X700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - MOTORS SPEC. NO.
TCE.5960A-H-500-001
20.5.3 For 6.6 kV AC motors, in addition to all the tests specified above, partial
discharge, C & Tan delta and polarisation index test shall be carried out as a
routine test on each motor (the minimum value of polarisation index for all
motors shall be 2 when determined according to IS : 7816).
20.5.4 Noise level measurement test shall be conducted on one motor of each type.
The following type tests shall be conducted on each type and rating of HT
motor:
(a) No load saturation and loss curves upto approximately 115% of rated
voltage
(b) Measurement of noise at no load.
(c) Momentary overload test (subject to test bed constraint).
(d) Full load test
(e) Temperature rise test at rated conditions. During heat run test,
bearing temp., winding temp., core temp., coolant flow and its temp.
shall also be measured. In case the temperature rise test is carried
at load other than rated load, specific approval for the test method
and procedure is required to be obtained. Wherever ETD's are
provided, the temperature shall be measured by ETD's also for the
record purpose.
(f) Surge withstand test on the sample coil after placing it in stator core
at (4U + 5 KV) and with at least five impulse of 1.2/50 micro sec.
wave, for HV motors only, where U is the line to line voltage in kV.
(g) Surge-withstand test at 20 kV with 0.3/3 micro sec. wave on each
type of motor coils with at least five such impulses, followed by one
minute power frequency high voltage test on turn to turn insulation,
after cutting the coil and bringing out the turns suitably. The power
frequency test voltage shall be decided during detailed engineering.
ISSUE
R0
306
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.20
SHEET 6 OF 10
1X700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - MOTORS SPEC. NO.
TCE.5960A-H-500-001
(a) Degree of protection test for the enclosure followed by IR, HV and no
load run test.
(b) Terminal box-fault level withstand test for each type of terminal box
of HT motors only.
ISSUE
R0
307
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT SECTION: D3.20
COMPANY LTD.
DATA SHEET – A3.20 SHEET 7 OF 10
SPEC. NO.
TCE.5960A-H-500-001
1.0 AC Motors
1.2 Supply
0
1.6 Ref. Ambient temperature C 50
0
1.7 Temperature rise by winding C 70 for class-B
resistance
1.8 Location
2 DC Motors
4.7 Type of duty & duty designation for Short time (15 minutes) or twice
motor the valve stroking time whichever
is higher
4.9 Class of insulation for motor Class of insulation for motor Class
F but limited to Class B
SHEET 1 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - ELEVATORS SPEC. NO.
TCE.5960A-H-500-001
21.0 ELEVATORS
21.1 One (1) no. passenger lift of capacity 600 kg and speed of 0.75 m/sec
shall be provided for proposed Control and Switchgear building.
21.2 The lift for control building shall cater to various floors of the control room
building. Accordingly, Bidder shall decide the number of landings
required and the total rise of the lift for both control building and HRSG
area elevators.
21.3.1 The capacity of the lift shall be 600 kgs (8 passengers) for passenger lift
and 1500 kgs for goods cum passenger lift.
21.3.3 An enclosed machine room shall be provided for the control panel of the
lift.
21.3.4 The A.C motors of the lift shall comply with Section D3.20 of this
specification.
21.3.5 The car and counter weights shall be suspended by stainless steel wire
ropes. Chain shall not be used for suspension. Not less than 4 (four)
independent standard steel wire suspension ropes shall be used for car
or counter weight and all these ropes shall be in one piece and without
intermediate joints. The minimum diameter of the standard rope shall not
be less than 12.5 mm and the minimum factor of safety shall not be less
than 12. The suspension ropes shall conform to IS: 2365 latest edition
"Specification for steel wire suspension ropes for lifts and hoists", or
equivalent international standard.
21.3.5 Special care and precaution shall be taken regarding handling of lift
cable loops between the points of suspension as the loops are prone to
twist / distortion.
ISSUE
R0
312
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.21
SHEET 2 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - ELEVATORS SPEC. NO.
TCE.5960A-H-500-001
21.3.6 The car shall be provided with fittings & accessories. Glass shall not be
used in the roof except to protect electric light, which is to be fitted with
safety glass / plastic transparent cover mounted inside the car. Glass
exceeding 930 cm² in area shall be of laminated type.
21.3.7 The car floor shall be of smooth non-slip surface. The car platform shall
be robust in construction and elegant in appearance. If there is any
change/changes in the elevations of landing, the same shall be informed
to successful Contractor. The successful Contractor shall comply with
the changes in the elevation without claiming extra price.
21.3.8 The car door shall be of hollow metal construction, 16 gauge thick
stainless steel. Sides of the door shall flush with all seams continuously
welded. Guide shoes shall be rubber of roller type designed for operation
on un-lubricated guides. The car entrance shall be able to withstand the
thrust of 35 kg. The entrance shall be securely fitted with car floor and
frame in order to become working loose or becoming displaced during
the service.
21.3.9 The car door shall be provided with locking gear of heavy and robust
construction so arranged mechanically and interlocked that the doors
cannot under any circumstances be opened unless the lift car is within a
particular landing zone.
21.3.10 Conversely the lift will not move until all the landing doors are closed and
interlocked properly. Car doors & landing doors shall be electrically
operated by torque motor.
21.3.11 The car doors shall be so designed that their closing and opening is not
likely to injure a person, with scratch resistant coating. A retractable
safety shoe shall extend to the full height and project beyond the front
edge of each car to open the closing door if and when it touches a
person or object that is Bidder to provide "Electro-Mechanical Pressure
Detection". Besides this Bidder is also to provide "Electronic Door
Detector". In the first method, slight body contact pressure is detected by
sensors incorporated into door drive mechanisms. Actuation will check
and reverse door movement, allowing passengers to pass.
21.3.12 The second method will also take carry by the screen of Infrared beams
as a safety curtain across the door entrance detects an obstacle when
the doors are closing, the doors then revert to an open position.
21.3.13 A load plate displaying the rated load of the lift in terms of persons and
kilograms shall be fitted in the lift car in a conspicuous position.
ISSUE
R0
313
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.21
SHEET 3 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - ELEVATORS SPEC. NO.
TCE.5960A-H-500-001
21.3.14 All sheaves and pulleys fixed to and revolving with the shaft shall be
fixed by means of sunk keys of sufficient strength and quality. Sheaves
and pulleys shall be made of cast steel to IS:1030 and free from cracks,
sand holes and other injurious defects. They shall have suitable flanges
and smoothly machined rope grooves. The diameter of the sheave of
pulley shall be as specified in the latest edition of Indian Standard of
equivalent International Standard.
21.3.15 Shafts and axles shall be of forged steel. They shall have sufficient
rigidity and bearing surface. Any shaft when stepped, shall be turned to a
reasonable radius at the point of reduction in diameter.
21.3.16 The elevator shall be provided with suitable counter weights located in
the lift shaft. The counter weight shall be designed for smooth and easy
operation of the lift and shall be in accordance with Indian Standards
referred earlier or equivalent. International Standards. The counter
weight shall be provided in the lift shaft. The counter weight shall consist
of cast iron weight contained in structural steel frame. It should
preferably be equal to that of the car weight plus 40% of the rated load.
The traction should be such that no appreciable slip may occur but that
slip shall be free to take place upon the landing of either the car or the
counter weight.
21.3.17 Guide rails for the car and counter weights shall be machined 'T' sections
and continuous throughout the entire length and shall be provided with
adequate steel brackets or equivalent fixing of such design and spacing
that avoid any deflection during the normal operation. Guide rails section
shall be adequate to withstand the forces resulting from the application of
the safety gear when stopping the counter weights or fully loaded car.
The guide shoes or their lining shall be easily renewable, adjustable and
self lubricated guides shall be of such length that it shall not be possible
for any of the car or the counter weights shoes to run off the guides.
21.3.18 Sufficient number of buffers of spring loaded/oil type shall be fitted below
lift car and counter weights. The buffers shall be capable of stopping the
car or counter-weights without permanent damage or deformation to
itself or any part of the lift equipment. The number of buffers shall be so
fixed as to ensure proper sharing of the impact loads by all of them.
21.3.19 The lift shall be provided with safety device attached to the lift car frame
and placed beneath the car. The safety device shall be capable of
stopping and sustaining the lift car up at governor tripping speed with full
rated load in car. The application of safety device shall not cause the lift
platform to become out of level in excess of 3 cm/m measured in any
direction. Slack rope switches if necessary, shall also be provided.
ISSUE
R0
314
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.21
SHEET 4 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - ELEVATORS SPEC. NO.
TCE.5960A-H-500-001
21.3.21 Governors shall be located where there is sufficient room for their proper
operation and where they cannot be struck by the lift car or
counterweight in the event of overrun. Each governor shall be marked
with a tripping speed in terms of car speed in m/sec. and the motor
control and brake control circuit shall be opened before or at the time of
governor trips. Governor ropes shall not be less than 8mm in diameter
and shall be of steel or phosphor bronze and of suitable construction.
The ropes shall run clear of the governor jaws during normal operation of
the lift.
21.3.22 The drive system for the elevator should be variable voltage variable
frequency Drive system.
21.3.23 The lift drive controller and all other apparatus and equipment for lift
installation, except such apparatus and equipment which function in the
lift well or other portion shall be placed in the machine room which shall
be located at the top of the lift well. Sound reducing materials shall be
provided under the machine base by the bidder. The maximum load
transmitted by the single heaviest equipment both during erection and
maintenance of the lift to the machine room floor and other structures like
guides etc. shall be furnished by the contractor within 30 days of placing
the award letter.
21.3.24 The lift drive shall be equipped with brakes. The lift shall be driven by a
drive suitable for method of control offered by the bidder. No friction
gearing or clutch mechanism shall be used for connecting the main
driving gear to the sheaves.
21.3.25 The lift shall be provided with upper and lower normal terminal switches
arranged to stop the car automatically within the limit of top car clearance
and bottom run from any speed attained in normal operation. Such limit
switches are to act independently of the operating device, the final limit
switches and buffers.
21.3.26 Final limit switches shall be provided to stop the car automatically within
the top and bottom clearance independently of the normal operating
device and the terminal limit switches. The final limit switch shall not act
to prevent motion of the car under power in both direction of travel and
ISSUE
R0
315
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.21
SHEET 5 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - ELEVATORS SPEC. NO.
TCE.5960A-H-500-001
shall after operation, remain open until the lift car has been moved by a
hand winding within the limit of safe operation.
21.3.27 Emergency safety device and over speed governor and buffers shall be
provided.
21.3.29 The lift shall be provided with automatic levelling device to take care of
over run and under run of the car and rope stretch such that any floor is
within 6 mm from the landing level.
21.3.31 The scope of the bidder also includes supply of erection consumables,
arranging the materials for scaffolding and for any other functional
requirement of erection.
21.3.32 The elevator is to provide service in power station. It is necessary for the
equipment to be specifically treated. This shall include application of anti-
corrosion paint/zinc plating. The electrical equipment shall have
enclosure meeting IP-54 and other relevant protection.
21.3.33 An electric contact for the car door shall be provided which shall prevent
elevator movement away from the landing unless the door is in the
closed position. The mechanical interlock with auxiliary door closing
device shall be provided so that the elevator can be operated only after
the interlock circuit is established.
21.3.34 The car door shall be provided with a protective device extending to the
full height and shall be so arranged that should it touch a person or any
obstruction in its path while the door is closing, it shall automatically
cause the car door and hoistway door to return to open position.
21.3.39 The contractor shall carryout all the tests necessary & take the
clearances / permissions from the Electrical inspector or any other
agencies who certify the operation of lift.
ISSUE
R0
316
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.21
SHEET 6 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - ELEVATORS SPEC. NO.
TCE.5960A-H-500-001
21.3.40 The following operating devices / indications shall be provided in the car /
on the landing / in the machine room as indicated below:
Up push button Up PB Up PB Up
(PB)
230V 1φ
receptacle
Door open PB - - -
Door close PB - - -
Alarm PB - - -
Emergency stop - - -
PB
Key operated - - -
selector for
attendant
operation
317
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.21
SHEET 7 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - ELEVATORS SPEC. NO.
TCE.5960A-H-500-001
(g) Hoist way machine room & pit lighting: To be provided by lift
supplier.
(j) The contractor shall carryout all the necessary tests & take the
clearances / permissions from the Lift inspector or any other
agencies who certify the operation of lift.
The material of doors and lift rope shall be stainless steel. The enclosure
for electrical equipment located outside the machine room shall be dust
tight and the car shall be provided with fluoroscent lighting, blow out
panels, etc. Emergency DC light shall be provided in car. Any other
equipment / accessories required for satisfactory operation of the lift shall
be supplied by the Contractor.
ISSUE
R0
318
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.21
SHEET 8 OF 10
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS - ELEVATORS SPEC. NO.
TCE.5960A-H-500-001
The interior decor of the lift shall be aesthetically pleasing, and the same
shall be subject to approval by Owner.
ISSUE
R0
319
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT SECTION: D3.21
COMPANY LTD.
DATA SHEET – A3.21 SHEET 9 OF 10
SPEC. NO.
TCE.5960A-H-500-001
SL. NO. DESCRIPTION UNITS VALUES / REQUIREMENTS
Passenger Lift
1.0 Installations Indoor
9.1 Specification for electric passenger and goods IS:14665 (Latest edition)
lift.
9.1 Specification for electric passenger and goods IS:14665 (Latest edition)
lift.
SHEET 1 OF 7
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS –
ELECTRICAL LABORATORY EQUIPMENT SPEC. NO.
TCE.5960A-H-500-001
(d) Digital Earth resistance tester with 0.01 Ohms, 500 1 No.
resistivity test facility Ohms in three
ranges
322
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.22
SHEET 2 OF 7
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS –
ELECTRICAL LABORATORY EQUIPMENT SPEC. NO.
TCE.5960A-H-500-001
ISSUE
R0
323
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.22
SHEET 3 OF 7
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS –
ELECTRICAL LABORATORY EQUIPMENT SPEC. NO.
TCE.5960A-H-500-001
ISSUE
R0
324
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.22
SHEET 4 OF 7
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS –
ELECTRICAL LABORATORY EQUIPMENT SPEC. NO.
TCE.5960A-H-500-001
(iii) Mobile base with adequate no. of rollers for easy transport of the
testing unit.
(b) The insulating material used for bushings and top covers shall be as per
BS for Class F/A installation.
22.2.2 Category – II
(ii) The test set shall be so designed that the short circuit current drawn
from the system exceeds 8 times the rated current. The transformer
test set impedance shall be such that the input MCCB trips within a
suitable time (0.02 sec.) for a secondary short circuit.
The rheostats shall be 650V grade wire wound type of copper nickel alloy
having a low temperature co-efficient, totally enclosed type with louvers.
Solid copper / graphite brushes with pressure springs shall be provided to
ensure low contact resistance.
ISSUE
R0
325
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.22
SHEET 5 OF 7
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS –
ELECTRICAL LABORATORY EQUIPMENT SPEC. NO.
TCE.5960A-H-500-001
Portable cable fault locator which shall identify the fault in a LT cable
distinctly. This kit shall work on in-built batteries. This kit shall include
Time Domain Reflectometer (TDR) and cable identifying kit and all
necessary accessories & transport cases.
The hot sticks shall be supplied in different ratings viz. For 6.6 kV, 400 kV.
The insulating handle of stick shall be with Class F / H insulation as per
IEC / BS specifications with scaled detector having high quality viewing
windows. The hot stick should be light weight and portable. Should give
audio visual indication of pressure of voltage.
ISSUE
R0
326
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.22
SHEET 6 OF 7
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS –
ELECTRICAL LABORATORY EQUIPMENT SPEC. NO.
TCE.5960A-H-500-001
This shall be suitable for testing 3 phase 400V supply and shall be suitably
marked for clockwise and anti-clockwise directions. Any conducting part
of the meter/ shall withstand 2 kV for 1 minute. The operative range of the
meter shall be 100V to 600V.
The meter shall have a large digital display unit and the jaws shall open
adequately to facilitate introduction of the conductor having a size
corresponding to the maximum current range.
22.2.4 Category – IV
Relay test set shall be suitable for input voltage 230 V, 1 Phase, 50 Hz.
Output current range shall be 1-5-50-100A. Overload and short circuit
protection shall be provided. Phase angle adjustment shall be 0-360 deg.
The kit shall be computerised, portable unit and used to test various types
of protective relays quickly and more accurately. The software for testing,
measurement and analysis of the different types of the relays shall be
included.
ISSUE
R0
327
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.22
SHEET 7 OF 7
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS –
ELECTRICAL LABORATORY EQUIPMENT SPEC. NO.
TCE.5960A-H-500-001
Voltage range
(continuously controlled) - 0 to + 300 V DC
Current range
(continously variable) - 0 to 2A DC
Indication - Digital voltage/current
meters integral with the unit
These meters shall have built in overload protection and protection against
HV transients. They shall have an audio alarm for continuity testing, a
peak hold feature on current and voltage ranges, automatic polarity and
over range indications. The instrument shall be complete with
rechargeable batteries and charging equipment, adapters, probes, leads,
padded carrying case, etc. It shall have safety features to prevent damage
to instrument if voltage is applicable inadvertently current or resistance
measuring range.
ISSUE
R0
328
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.23
SHEET 1 OF 3
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS -
MISCELLANEOUS ELECTRICAL EQUIPMENT SPEC. NO.
TCE.5960A-H-500-001
23.1.6 50 nos. first aid charts shall be provided for display in the plant area.
23.1.7 Minimum of fifty (50) nos. First aid boxes shall be provided at various
locations in the plant.
23.1.8 Sufficient quantity of gas masks shall be provided in line with rule no. 43
of IE rules.
23.2.1 Local push button stations shall be provided for all the drive motors of the
plant.
23.2.2 LPB’s for outdoor installation shall be weather proof type provided with a
GI canopy and those intended to be used in hazardous areas shall be
flameproof type and the degree of protection shall be IP 55 for both out-
door and indoor application. The LPBs shall be power coated with shade
Opaline green (External) & semi glossy white (Internal).
23.2.3 All stop push buttons shall be lockable type (provided with key for
locking)
23.2.4 Following types of LPBs shall be provided for the various drives as
applicable.
(a) Push button station type A - which shall comprise Three, Push
buttons viz., `Open', `Close' and `Stop' for control of reversible
motors.
(b) Push button station type B - which shall comprise two push
buttons viz., `Start' and `Stop' for control of the rest of the drives
in the plant.
ISSUE
R0
SHEET 2 OF 3
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS -
MISCELLANEOUS ELECTRICAL EQUIPMENT SPEC. NO.
TCE.5960A-H-500-001
(c) Type-C push button station: With start, stop & ammeter.
23.3.1 Junction boxes as required for the power plant shall be supplied as
required for marshalling cables of devices located in an area/equipment.
Junction Boxes with IP:55 degree of protection, shall comprise of a case
with hinged door constructed from cold rolled sheet steel of minimum
thickness 2mm. Top of the boxes shall be arranged to slope towards rear
of the box. Gland plate shall be 3mm thick sheet steel with
neoprene/synthetic rubber gaskets. All junction boxes shall be of
adequate strength and rigidity, hot dip galvanised as per relevant IS, and
suitable for mounting on wall, columns, structures etc. The boxes shall
include brackets, bolts, nuts, screws M8 earthing stud etc. required for
installation.
23.3.2 Terminal blocks shall be 650 volts grade, rated for 10 Amps and in one
piece moulding. The JBs used in outdoor areas shall be weatherproof
type. Sheet steel thickness of the JBs shall be minimum 2 mm. JBs / MBs
shall be hot dip galvanised and shall be powder coated with paint shade
Opaline green (External) & Semi glossy white (Internal).
23.3.3 Cable entry shall be bottom/side entry for indoor as well as outdoor
mounted junction boxes. The junction boxes shall be installed at 1 m
accessible height.
23.5.1 32 A and 63 A, 3 phase, 4 pin heavy duty type power receptacles shall be
provided in proposed building plant areas, transformer yard, 400 kV
switchyard such that distance between any two of each rating in indoor
and outdoor area does not exceed 15 m and 30 m respectively.
SHEET 3 OF 3
700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
ELECTRICAL SYSTEMS -
MISCELLANEOUS ELECTRICAL EQUIPMENT SPEC. NO.
TCE.5960A-H-500-001
when the switch is in OFF position. Also cover can be opened only when
the switch is in OFF position. Wiring shall be carried out with 1100 V
grade PVC insulated stranded aluminium/copper wire of adequate size.
The Terminal blocks shall be of 750 V grade.
23.5.1 Danger boards and rubber mats shall be provided as required by the
statutory Authorities. The thickness and length of the rubber mats shall
be as per the guidelines of Indian Electricity Rules / local electrical
inspectorate.
ISSUE
R0
SHEET 1 OF 4
1X700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS – CONSTRUCTION POWER SUPPLY TCE.5960A-H-500-001
24.1 Construction power shall be made available at a single point at 11kV inside
the plant premises from nearest substation of APTRANSCO by the Owner.
The power shall be further extended by the Contractor to different users by
armoured cables or overhead lines. All the equipments used in construction
power shall ensure full safety to the working personnel and no live parts
which are accessible shall be exposed. The Contractor shall estimate the
construction power requirement and indicate the same to Owner to enable
them to enter into an agreement with APTRANSCO for its supply. The
Contractor shall obtain all necessary statutory clearance for the purpose. GA
and layout drawings required for getting clearance from local electrical
inspector / Electricity Board shall be prepared by the contractor and it will be
the complete responsibility of the Contractor to obtain the approval for the
installation and all related works in this regard. The Owner will not be
responsible for power cuts, Power failure for whatever reason, fluctuation in
voltage and frequency and consequences thereupon. To take care of failure
of this supply, Contractor shall provide suitable DG sets. Contractor shall
provide necessary protection for the construction power supply arrangement
to ensure that any fault in his system, should not disturb 11kV power supply
arrangement.
24.2 The Contractor shall provide metering arrangement consisting of two CT, PT
units and two trivector meters of suitable accuracy which shall have MD
registering facility. The contractor shall be responsible for periodic payment
of bills for the energy consumed by him.
24.3 The Contractor shall make arrangements to receive power from the Owner
line through DP structures with fuse protection. 2 x 100% suitably rated
11kV / 420V transformers, 400V switchgear with two incomer ACBs, two bus
sections and bus coupler & required number of outgoing 400V, 3φ, 4 wire
distribution lines to distribute power around plant area. Adequate metering
and protection shall be provided for transformers and incomer feeders.
24.5 Contractor shall supply and install fire fighting equipment as per the
regulations of the local electrical inspectorate / statutory bodies for the
electrical installation.
ISSUE
R0
SHEET 2 OF 4
1X700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS – CONSTRUCTION POWER SUPPLY TCE.5960A-H-500-001
24.6 On award of contract, the Contractor shall furnish the electrical scheme, for
Owner’s approval.
24.8.1 In general, these shall meet the requirements covered in D3.11 section.
However, the board shall be provided with outer enclosure so that access to
individual compartments, busbar and cable alley shall be available only after
the outer door is opened.
24.9 CABLES
24.9.1 Cables shall be armoured and suitable for direct underground buried
installation. Cable armour shall be suitable for carrying system earth fault
current. HT cables shall be XLPE insulated type.
24.10.1 Earthing of all substation equipment and overhead line shall be carried out
as per IS:3043. Earthing system shall consist of adequate number of earth
electrodes interconnected. Earth electrodes shall be of 40mm dia.
galvanised steel pipe, buried in earth pit.
24.10.3 All non-current carrying metal parts shall be connected to earth system at
two points, each of 100% rating. Metallic supports, fencing, etc. shall also be
connected to earth system.
ISSUE
R0
SHEET 3 OF 4
1X700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS – CONSTRUCTION POWER SUPPLY TCE.5960A-H-500-001
24.11 INSTALLATION
24.11.1 The electrical installation shall generally be carried out as per Indian
electricity rules and acts.
24.11.2 For road crossing, protective guarding shall be provided. The clearance for
the lowest conductor from ground shall be decided keeping in view the
vertical clearance required for movement of vehicles/cranes, etc.
24.11.3 The LT substation area shall be graded and sloped to prevent any stagnation
of rain water. Surface shall be covered with gravel of 15 to 20 mm size.
24.11.4 The LT substation shall be enclosed by barbed wire fencing on mild steel
angle iron posts to a height of not less than 2500mm with suitable gates for
entrance.
24.11.5 All cable connection parts within the switchgear shall be shrouded with
insulating materials.
24.11.6 The extension boards provided for hand held equipments shall have 3 wire
system i.e. phase, neutral & earth as per IE rules. The plug & socket
arrangement provided shall be of industrial type with switch provided for
proper isolation at the time of insertion or withdrawal of plugs.
24.11.7 The flexible cable used shall have heavy duty insulation.
24.11.8 All equipment used for construction activities shall be fed from separate
switching/isolating devices.
24.11.9 All the working areas shall be adequately illuminated for safe working with
proper fittings/fixtures. The wire shall be laid with proper fixing without any
hindrance to personnel or vehicular movement.
ISSUE
R0
SHEET 4 OF 4
1X700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS – CONSTRUCTION POWER SUPPLY TCE.5960A-H-500-001
24.12.1 Adequate safety equipments shall be provided to all the workers, like hand
gloves, head gear, etc. Meggers & testers shall be provided in sufficient
quantity.
24.12.2 Only ITI qualified workers shall be allowed to handle the electrical or
electrically operated equipments.
ISSUE
R0
SHEET 1 OF 2
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - TRANSDUCERS TCE.5960A-H-500-001
25.1 Bidders shall note that each and every device/equipment mounted in panels,
switchgears, MCCs, chargers, distribution boards, etc,, shall be properly
tagged, both inside and outside (if the equipment is mounted on door) for
identification.
25.2 Transducers
336
TCE FORM NO. 329 R5
ANDHRA PRADESH POWER DEVELOPMENT COMPANY LTD. SECTION: D3.25
SHEET 2 OF 2
1X 700 MW CCPP AT NEDUNOOR, KARIMNAGAR DIST.
SPEC. NO.
ELECTRICAL SYSTEMS - TRANSDUCERS TCE.5960A-H-500-001
25.3 Digital LED displays for the following parameters shall be provided in two (2)
locations in the Main control room and three (3) locations in the
administration building (*)
(a) Total plant load for each block
(b) Frequency
(c) Ambient temperature
25.4 For all outdoor equipment, which are not protected by sun cover, the heating
effect due to solar radiation shall be considered while considering the
temperature rise.
ISSUE
R0
337
TCE FORM NO. 329 R5
5.11 TECHNICAL SPECIFICATION
FOR SPECIFICATION NO. PE-TS-I59-888-E001
INSULATING MATS
1.0 SCOPE
1.1 The scope includes design, manufacturing, inspection, testing, packing and delivery to
site of protective mats for placing in front of all 6.6kV/400V/220V Switchboards.
3.1 All type, routine and sampling tests shall be as per IS: 15652.
3.2 Dispatch of materials shall be permitted only after acceptance of type test certificates,
and inspection and testing of materials.
3.3 The successful bidder shall submit the Quality Assurance Plan (QAP) in attached
format for BHEL/ Customer approval after the award of contract.
Bidder shall confirm total compliance to the specification without any deviations from
the technical requirements stipulated. As a mark of technical conformance, all sheets
of the specification shall be furnished by each bidder with the signature and company
seal affixed thereon.
5.0 Wherever required, soft copy of all approved technical/ quality documentation shall be
submitted as specified without any additional commercial implication. Soft copies may
be required both in native file format (e.g. MS Word/ MS Excel) as well as PDF files.
338
5.12 TECHNICAL SPECIFICATION
FOR SPECIFICATION NO. PE-TS-I59-888-E001
CATHODIC PROTECTION
2. GENERAL REQUIREMENT:
2.1 All the metallic structures which are in contact with sea water & underground metallics shall be
provided with Cathodic Protection (CP) system irrespective of the material of structures, to
prevent corrosion due to any pin holes / holidays.
2.2 The CP system shall only be of impressed current type. Preferably LIDA type anode shall be
used.
2.3 If the soil is very corrosive, all underground structures shall be protected against corrosion by
providing suitable CP system.
2.4 Bidders shall furnish in their BID a brief write up indicating the type of CP system
envisaged for various metallic structures in contact with sea water & under ground metallics.
2.5 During detailed engineering the Contractor shall furnish the following for Purchaser’s approval :
2.5.1 Calculations for arriving at the number and dimension of anodes.
2.5.2 Calculations for arriving at the rating of transformer–rectifier set.
2.5.3 Layout of CP system.
2.5.4 Mounting arrangement of anode and reference electrode.
The following minimum design documentation [not essentially limited to these only] shall be
furnished by the successful vendor (for review and approval) at contract stage.
339
5.12 TECHNICAL SPECIFICATION
FOR SPECIFICATION NO. PE-TS-I59-888-E001
CATHODIC PROTECTION
Note : The list of deliverables shall be finalised during kick-off meeting at contract stage.
340
ANNEXURE-II
341
342
343
344
345
346
Doc. No. PE-TS-I59-888-E001
700MW KARIMNAGAR CCPP
TECHNICAL SPECIFICATION FOR Rev. : 0
GENERAL ELECTRICAL WORKS
Page : of
ALL MATERIALS, COMPONENTS AND EQUIPMENT’S COVERED UNDER THIS SPECIFICATION SHALL BE
PROCURED, MANUFACTURED, INSPECTED AND TESTED AS PER THE BHEL/ CUSTOMER APPROVED
QUALITY PLAN. THERE SHALL BE NO COMMERCIAL IMPLICATION TO BHEL ON ACCOUNT OF QP
APPROVAL. BHEL QPs ARE ENCLOSED FOR REFERENCE.
347
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-007/2 TITLE
SHEET 1 OF 9 SYSTEM ITEM: AC ELECT. MOTORS 75KW & ABOVE (LV & MV) SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.0 RAW MATERIAL & BROUGHT
CONTROL
1.1 SHEET STEEL, PLATES, 1.SURFACE MA VISUAL 100% - FREE FROM LOG BOOK 3 - -
SECTION, EYEBOLTS CONDITION BLINKS,
CRACKS,
WAVINESS
ETC
2.CHEM. & MA CHEM & MECH 1/HEAT NO. MANFR'S RELEVENT SUPPLIER'S 3 - 2 HEAT NO. SHALL BE
PHY. PROP. TEST DRG./SPEC IS/ TC VERIFIED
1.4 PAINT & VARNISH 1.MAKE, SHADE, MA VISUAL 100% MANFR'S MANFR'S LOG BOOK 3 - -
SHELF LIFE & CONTINUOUS DRG./SPEC DRG./SPEC
TYPE
1 2 3 4 5 6 7 8 9 10 11
1.5 SHAFT 1. SURFACE MA VISUAL 100% - FREE FROM -DO- 3 - - VENDOR'S APPROVAL
(FORGED OR ROLLED) COND. VISUAL IDENTIFICATION SHALL BE
DEFECTS MAINTAINED
2. CHEM. & MA CHEM. & 1/HEAT NO. MFG. DRG. RELEVANT SUPPLIER'S 3 - 2
PHYSICAL PHYSICAL OR HEAT SPEC. IS TC
PROPERTIES TESTS TREATMENT
BATCH NO
1.6 SPACE HEATERS, CONNEC- 1. MAKE & MA VISUAL -DO- MANUFR'S MANUFR'S -DO- 3 - -
TORS, TERMINAL BLOCKS, RATING DRG. SPEC. DRG. SPEC.
CABLES, CABLE LUGS,
CARBON BRUSH TEMP.
DETECTORS, RTD, BTD'S
349
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-007/2 TITLE
SHEET 3 OF 9 SYSTEM ITEM: AC ELECT. MOTORS 75KW & ABOVE (LV & MV) SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.ELECT. PROP, & MA ELECT. & SAMPLES RELEVANT IS/ RELEVANT IS/ SUPPLIERS 3/2 - 2
MECH. PROP MECH.TEST BS OR BS OR TC &
OTHER OTHER VENDOR'S
STANDARDS STANDARDS INSPN.
REPORTS
350
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-007/2 TITLE
SHEET 4 OF 9 SYSTEM ITEM: AC ELECT. MOTORS 75KW & ABOVE (LV & MV) SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.10 BEARINGS 1.MAKE & TYPE MA VISUAL 100% MANFR'S DRG. MANFR'S DRG. -DO- 3 - -
1.12 OIL SEALS & GASKETS 1.MATERIAL OF MA VISUAL 100% MANUF'S MANUF'S -DO- 3 - -
GASKET DRG/SPECS DRG./ SPECS.
351
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-007/2 TITLE
SHEET 5 OF 9 SYSTEM ITEM: AC ELECT. MOTORS 75KW & ABOVE (LV & MV) SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.0 IN PROCESS
2.1 STATOR FRAME WELDING 1.WORKMANSHIP MA VISUAL 100% -DO- GOOD FINISH LOG BOOK 3 - -
(IN CASE OF FABRICATED & CLEANNESS
STATOR )
2.2 MACHINING 1.FINISH MA VISUAL 100% -DO- GOOD FINISH LOG BOOK 3 - -
352
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-007/2 TITLE
SHEET 6 OF 9 SYSTEM ITEM: AC ELECT. MOTORS 75KW & ABOVE (LV & MV) SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.4 SHEET STACKING 1.COMPLETENESS MA MEASUREMENT SAMPLE MANUFR'S MANUFR'S Log Book 3 - -
SPEC. SPEC.
3.CORE LOSS & MA ELECT.TEST -DO- -DO- -DO- Log Book 3 - 2 (FOR MOTORS OF 2MW
HOTOPOT AND ABOVE)
6.SURGE WITH CR -DO- -DO- -DO- -DO- Log Book 3 2 1 FOR MV MOTOR
STAND AND
TAN. DELTA
TEST
2.6 IMPREGNATION 1.VISCOSCITY MA PHY. TEST AT STARTING -DO- -DO- Log Book 3 - -
3.NO. OF DIPS MA -DO- -DO- -DO- -DO- Log Book 3 - 2 THREE DIPS TO BE
GIVEN
353
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-007/2 TITLE
SHEET 7 OF 9 SYSTEM ITEM: AC ELECT. MOTORS 75KW & ABOVE (LV & MV) SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.7 COMPLETE STATOR 1.COMPACTNESS MA VISUAL 100% -DO- -DO- Log Book 3 - -
ASSEMBLY & CLEANLINESS
2.9 COMPLETE ROTOR 1.RESIDUAL CR DYN. BALANCE -DO- MFG SPEC./ MFG. DWG. Log Book 3 2 1 VERIFICATION FOR MV
ASSEMBLY UNBALANCE ISO 1940 MOTOR ONLY
354
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-007/2 TITLE
SHEET 8 OF 9 SYSTEM ITEM: AC ELECT. MOTORS 75KW & ABOVE (LV & MV) SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
3.0 TESTS 1.TYPE TESTS MA ELECT.TEST 1/TYPE/SIZE IS-325/ IS-325/ TEST 3 1 1,2 NOTE - 1
INCLUDING BHEL SPEC./ BHEL SPEC./ REPORT
SPECIAL DATA SHEET DATA SHEET
TESTS AS PER
BHEL SPEC.
8.PAINT SHADE, MA VISUAL & SAMPLE BHEL SPEC. BHEL SPEC. TC 3 2,1 - SAMPLING PLAN TO BE
THICKNESS MEASUREMENT & DATA & DATA DECIDED BY INSPECTION
& FINISH BY ELKOMETER SHEET SHEET AGENCY
355
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-007/2 TITLE
SHEET 9 OF 9 SYSTEM ITEM: AC ELECT. MOTORS 75KW & ABOVE (LV & MV) SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
NOTES:
1 DEPENDING UPON THE SIZE AND CRITICALLY, WITNESSING BY BHEL SHALL BE DECIDED.
2 ROUTINE TESTS ON 100% MOTORS SHALL BE DONE BY THE VENDOR. HOWEVER, BHEL SHALL WITNESS ROUTINE TESTS ON RANDOM SAMPLES.
THE SAMPLING PLAN SHALL BE MUTUALLY AGREED UPON.
3 IN CASE TEST CERTIFICATES FOR THESE TESTS ON SIMILAR TYPE, SIZE AND DESIGN OF MOTOR FROM INDEPENDENT LABORATORY ARE AVAILABLE,
THESE TEST MAY NOT BE REPEATED.
4 WHEREVER CUSTOMER IS INVOLVED IN INSPECTION WITH THE CUSTOMERS, AGENCY (1) SHALL
MEAN BHEL AND CUSTOMERS BOTH TOGETHER.
356
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-006/0 TITLE
SHEET 1 OF 2 SYSTEM ITEM AC ELECT. MOTORS BELOW 75KW (LV) SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.O PAINTING 1.SHADE MA VISUAL SAMPLE MANUFR'S BHEL SPEC. LOG BOOK 3 - -
SPEC/BHEL SAME AS
SPEC./RELEVANT COL.7
STANDARD
2.0 ASSEMBLY 1.WORKMANSHIP MA VISUAL 100% MANUF'S SPEC MANUF'S SPEC -DO- 3 - -
3.0 TESTS 1.ROUTINE MA -DO- 100% IS-325/ SAME AS TEST 3 2,1 2,1 NOTE -1
TEST INCLUDING BHEL SPEC./ COL.7 REPORT
SPECIAL TEST DATA SHEET
AS PER BHEL
SPEC.
357
CUSTOMER : PROJECT SPECIFICATION :
QUALITY PLAN TITLE NUMBER :
BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-006/0 TITLE :
SHEET 2 OF 2 SYSTEM ITEM AC ELECT. MOTORS BELOW 75KW (LV) SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
NOTES:
1 ROUTINE TESTS ON 100% MOTORS SHALL BE DONE BY THE VENDOR. HOWEVER, BHEL SHALL WITNESS ROUTINE TESTS ON RANDOM SAMPLES. THE
SAMPLING PLAN SHALL BE MUTUALLY AGREED UPON
2 WHERE EVER CUSTOMER IS INVOLVED IN INSPECTION, (1) SHALL MEAN BHEL AND CUSTOMERS BOTH TOGETHER.
3 FOR EXHAUST/VENTILATION FAN MOTORS OF RATING UPTO 1.5KW , ONLY ROUTINE TEST CERTIFICATES SHALL BE FURNISHED FOR SCRUTINY.
358
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-013/00 TITLE
ITEM : CABLE TRAY SUPPORT MATERIAL & ACCESSORIES
SHEET 1 OF2 SYSTEM SECTION VOLUME III
(BOLTABLE)
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.1 ROLLED SHEET 1.CHEM.& PHY. MA VERIFICATION 100% IS1079 (for hot rolled) IS1079 (for hot rolled) MILL TC 3/2 - - AS PER CONTRACT & AS
PROPERTIES OF TC'S IS-513 (for cold rolled IS-513 (for cold rolled) APPLICABLE IN TECH.
SPECIFICATION
IS-1730/ IS-1730/
2.DIMENSIONS MA MEASUREMENT 100% QC RECORD 3/'2 - -
SPECIFICATION SPECIFICATION
3.SURFACE MA VISUAL 100% IS1079 (for hot rolled) IS1079 (for hot rolled) QC RECORD 3/'2 - -
FINISH IS-513 (for cold rolled IS-513 (for cold rolled)
1.2 ZINC CHEM.COMP. MA CHEM TEST EACH HEAT IS-209 IS-209 QC RECORD 3/2 - 1/2
2.0 IN-PROCESS
2.1 FABRICATION 1.DIMENSIONS MA MEASUREMENT 100% APPD. DRGS. APPD. DRGS. QC RECORD 2 - 1
2.WELDING MA VISUAL 100% GOOD WELDING FREE FROM QC RECORD 2 - 1 WELDING IS TO BE DONE BY
QUALITY PRACTICE DEFECTS & QUALIFIED WELDERS
SLAG
359
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-013/00 TITLE
ITEM : CABLE TRAY SUPPORT MATERIAL & ACCESSORIES
SHEET 2 OF 2 SYSTEM SECTION VOLUME III
(BOLTABLE)
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
3.1 SINGLE / DOUBLE CHANNELS, 1.DIMENSIONS MA MEASUREMENT IS-2500 APPD. DRG APPD. DRG INSP. REPORT 3 2, 1 - FASTENERS SHALL BE OF
CANTILEVER ARMS, CLAMPS DISTORTION LEVEL IV REPUTED & APPROVED MAKE
3.1.1 TYPE TESTING CR TEST 1 SAMPLE SPECIFICATION./ SPECIFICATION./ APPD. INSP. REPORT 2 1 -
APPD. TYPE TEST TYPE TEST
PROCEDURE PROCEDURE
3.1.2 WELD INTEGRITY TEST SOUNDNESS CR MPI SAMPLE TESTED SPECIFICATION. NO DEFECT INSP. REPORT 2 1 - AFTER CARRYING OUT TYPE
DURING TYPE TEST, WELD INTEGRITY TEST TO
TESTING CHECK THE WELD SOUNDNESS/
ACCEPTANCE SHALL BE DONE
BY MANUFACTURER
NOTE: INSTRUCTIONS FOR QUALITY PLAN IS ATTACHED AS ANNEXURE-1.
BHEL PARTICULARS BIDDER/VENDOR
NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
360
ANNEXURE – 1
The Quality Plan shall include all the Quality Control Measures and Checks adopted by the Vendor to ensure that the
material/component/assembly/services supplied by him meet/will meet the requirements as per specifications and good practices.
They shall include all stages of operation such as materials, processes, manufacture, assembly, packing and despatch. The following
guide lines may be noted:
NOTES :
1. In absence of correlation with the test certificate(s) (e.g. material identification) samples shall be drawn bgy BHEL and all tests as per
relevent specifications shall be carried out in their presence or in recognized Government Laboratory.
2. When materials and components are initially identified and stamped by BHEL QS engineer, the identification marks shall be
presserved till despatch. Wherever this is not possible, the identification mark shall be transferred to the components in the presence
of BHEL QS Engineer unless other wise agreed.
3. For castings and forgings integral test specimens shall be provided, When this is not possible for casting, they shall be poured in the
presence of BHEL QS Engineer unless otherwise, if witnessing of test by BHEL is called for.
4. When welders qualified by reputed inspection agencies or statutory bodies are not available, qualification tests shall be conducted in
the presence of BHEL QS Engineer.
5. This Quality Plan is liable to be modified as per the requirements of approved drawings and changes in technical
specifications/drawings. If there are contradictions in respect of column 7 & 8 between this Quality Plan and the approved drawings
specifications, the latter shall prevail.
6. Wherever inspection by BHELs Purchaser/Third Party/Statutory authorities are mandatory, this shall be compiled with.
7. Inspection reports, log sheets, test reports/certificate. etc. shall be furnished to BHEL at the approproate stages or at the time of final
inspection, as required.
8. This Quality Plan is also applicable to spares, if any, under scope of supply of Vendor.
9. The quality plan shall be submitted in minimum 4 copies with a soft copy of the same or in line with contract requirements.
361
FOREM NO. PEM-6041-0
CUSTOMER : PROJECT SPECIFICATION
TITLE NUMBER
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-002/01 TITLE
SHEET 1 OF 3 SYSTEM ITEM :BOUGHT OUT ITEMS SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.0 MATERIAL
1.1 SECTIONS, HARDWARES, 1. DIMENSIONS MA MEASUREMENT SAMPLE BHEL TECH. SPEC./ BHEL TECH. SPEC./ TEST 3/2 - 2 NO VISUAL DEFECT
FLATS, ANGLES & CHANNEL DRG. /DATA SHEETS/ DRG. /DATA SHEETS/ CERT. &
RELEVANT. IS RELEVANT. IS INSPN.
REPORT
1.2 SWITCHGEAR COMPONENTS 1. TYPE TESTS MA ELECTRICAL EACH TYPE BHEL SPEC./ BHEL SPEC./ TEST 3/2 - 2,1
SWITCH SFU'S
A) SWITCH, SFU'S. RELEVENT IS RELEVENT IS CERTIFICATE
INSTRUMENT, TRANSF,
FUSES, CONTACTORS AIR 2. ROUTINE TESTS MA ELECTRICAL 100% -DO- -DO- ROUTINE 3/2 - 2 IF THESE ARE TAKEN
CIRCUIT BREAKERS, (FOR METERS TEST FROM BHEL APPROVED
ISOLATORS. BIMETAL CT'S & PT'S) CERTIFICATE SOURCE THEN TC
THERMAL RELAYS, MCB.S NOT REQUIRED
& MCCB.S
3. PHYSICAL MA VISUAL 100% NO BREAKAGES/ NO. BREAKAGES/ INSPN. 2 - -
CONDITION DAMAGES DAMAGES REPORT
4. MAKE TYPE MA VISUAL 100% BHEL SPEC./ BHEL SPEC./ -DO- 2 - - TO BE PROCURED
RATING ETC. APPD. DRGS APPD. DRGS FROM APPROVED
MAKE
5. FUNCTIONAL
TEST MA ELECTRICAL 100% RELEVENT IS RELEVENT IS -DO- 2 - -
362
FOREM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
TITLE NUMBER
QUALITY PLAN BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-002/01 TITLE
SHEET 2 OF 3 SYSTEM ITEM :BOUGHT OUT ITEMS SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
B) INSTRUMENTS, GAUGES,
INSTRUMENTS GAUGES 1. PHYSICAL
1 MA VISUAL 100% NO BREAKAGES/ NO BREAKAGES/ INSPECTIONN 2 - -
CONNECTORS, LUGS, GLANDS CONDITION DAMAGES DAMAGES REPORT
SPACE HEATER,THERMOSTAT,
TERMINAL BLOCKS, LAMPS, 2. MAKE, TYPE, MA VISUAL 100% BHEL SPEC./ BHEL SPEC./ -DO- 2 - - TO BE PROCURED FROM
PUSHBUTTONS, SMALL , RATING ETC APPD. DRGS. APPD. DRGS. APPROVED MAKE
SWITCHES, NAMEPLATES,
FERRULES, LABELS, 3. FUNCTIONAL MA ELECTRICAL 100% RELEVANT IS RELEVANT IS -DO- 2 - -
STICKERS, PVC SLEEVES/
CHANNELS
2. MAKE, TYPE, MA VISUAL 100% BHEL SPEC./ BHEL SPEC./ -DO- 2 - - TO BE PROCURED FROM
RATING ETC APPD. DRGS. APPD. DRGS. APPROVED MAKE
1.3 INSULATING MATERIALS 1. ELECTRICAL CR ELECT. TEST SAMPLE BHEL SPEC./ BHEL SPEC./ TEST 2 - 1
(FRP,SMC,DMC,ETC.) RELEVANT IS RELEVANT IS CERTIFICATE
MANUFS. STD. MANUFS. STD.
363
FOREM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
TITLE NUMBER
QUALITY PLAN BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-002/01 TITLE
SHEET 3 OF 3 SYSTEM ITEM :BOUGHT OUT ITEMS SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.5
15 BUSBARS 1.
1 DIMENSION MA MEASUREMENT SAMPLE BHEL SPEC
SPEC.// BHEL SPEC
SPEC.// LOG BOOK/ 2 - -
APPD. DRGS. APPD. DRGS. INSP. REPORT
4 CONDUCTIVITY
4. CR ELECT TEST
ELECT. -DO-
DO -DO-
DO -DO-
DO -DO-
DO 2 - 1
17
1.7 TRANSFORMER & REACTORS 1 ROUTINE TESTS
1. MA ELECT TEST
ELECT. 100% STD &
RELEVANT STD. STD &
RELEVANT STD. CERT
TEST CERT. 3 - 12
1,2
BHEL SPEC. BHEL SPEC.
1.8 PAINTS SHELF LIFE MA VISUAL 100% ….AS PER PAINTS MANUF'S. SPEC……. INSPN 2 - -
REPORT
1.9 GASKETS ((SYN. RUBBER 1. DIMENSION MA MEASUREMENT SAMPLE MANUFACTURER'S MANUFACTURER'S INSPN 2 - -
ONLY) DRGS. DRGS. REPORT
364
CUSTOMER : PROJECT: SPECIFICATION :
TITLE : NUMBER :
QUALITY PLAN
BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-006/02 TITLE :
SHEET 1 OF 1 SYSTEM ITEM : GALVANISED RIGID STEEL CONDUITS & PIPES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
365
ANNEXURE – 1
The Quality Plan shall include all the Quality Control Measures and Checks adopted by the Vendor to ensure that the
material/component/assembly/services supplied by him meet/will meet the requirements as per specifications and good practices.
They shall include all stages of operation such as materials, processes, manufacture, assembly, packing and despatch. The following
guide lines may be noted:
NOTES :
1. In absence of correlation with the test certificate(s) (e.g. material identification) samples shall be drawn bgy BHEL and all tests as per
relevent specifications shall be carried out in their presence or in recognized Government Laboratory.
2. When materials and components are initially identified and stamped by BHEL QS engineer, the identification marks shall be
presserved till despatch. Wherever this is not possible, the identification mark shall be transferred to the components in the presence
of BHEL QS Engineer unless other wise agreed.
3. For castings and forgings integral test specimens shall be provided, When this is not possible for casting, they shall be poured in the
presence of BHEL QS Engineer unless otherwise, if witnessing of test by BHEL is called for.
4. When welders qualified by reputed inspection agencies or statutory bodies are not available, qualification tests shall be conducted in
the presence of BHEL QS Engineer.
5. This Quality Plan is liable to be modified as per the requirements of approved drawings and changes in technical
specifications/drawings. If there are contradictions in respect of column 7 & 8 between this Quality Plan and the approved drawings
specifications, the latter shall prevail.
6. Wherever inspection by BHELs Purchaser/Third Party/Statutory authorities are mandatory, this shall be compiled with.
7. Inspection reports, log sheets, test reports/certificate. etc. shall be furnished to BHEL at the approproate stages or at the time of final
inspection, as required.
8. This Quality Plan is also applicable to spares, if any, under scope of supply of Vendor.
9. The quality plan shall be submitted in minimum 4 copies with a soft copy of the same or in line with contract requirements.
366
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED 509 00 Q 001/01
PED-509-00-Q-001/01 TITLE
SHEET 1 OF 3 SYSTEM ITEM : EARTHING COND. & ELECTRODES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.1 MILD STEEL & COPPER 1.CHEMICAL & MA CHEM & PHYS 1/ LOT/SIZE APPD. DRGS/ APPD. DRGS/ MILL TEST 2 - -
(AS SPECIFIED) PHYSICAL TESTS DATA SHEETS/ DATA SHEETS/ CERTIFICATE
PROPERTIES TECH. SPEC. TECH. SPEC.
3.DIMENSIONS
3 SO S MA MEASUREMENT
SU 1// LOT/SIZE
O /S -DO-
O -DO-
O -DO-
O 2 - -
1.2 HARDWARES 1.DIMENSIONS MA MEASUREMENT 100% TECH. SPEC. TECH. SPEC. -DO- 3/2 - 2
APPD. DRGS/ APPD. DRGS/
DATA SHEETS DATA SHEETS
1.3 ZINC FOR GALVANISATION 1.CHEM.COMP. MA CHEM.TEST SAMPLE RELEVANT IS. RELEVANT IS. TC 3/2 - 2
2.0 IN-PROCESS
2.1 CUTTING, DRILLING 1.WORKMANSHIP MA VISUAL & 100% APPD. DRGS/ APPD. DRGS/ IR 2 - -
DIMENSIONS MEASUREMENT TECH. SPEC. TECH. SPEC.
& DISTORTION
2.3 SURFACE PREPARATION FOR 1.CLEANING MA CHEM. & PERIODIC IS:2629/ IS:2629/ IR 3/2 - -
GALVANISING PICKLING & MEASUREMENT IN EACH RELEVENT:IS RELEVENT:IS
RINSING, BATH SHIFT
STRENGTH/
PURITY &
TEMPERATURE
367
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-509-00-Q-001/01 TITLE
SHEET 2 OF 3 SYSTEM ITEM : EARTHING COND. & ELECTRODES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.5 PAINTING 1.SURFACE MA CHEM. TEST 100% TECH.SPEC. TECH.SPEC. LOG BOOK 2 - -
PREPN.
DEGREASING &
DERUSTING
368
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-509-00-Q-001/01 TITLE
SHEET 3 OF 3 SYSTEM ITEM : EARTHING COND. & ELECTRODES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
369
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-509-00-Q-001/02 TITLE
SHEET 1 OF 3 SYSTEM ITEM : EARTHING & LIGHTNING PROTECTION MATERIALS SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.1 MILD STEEL (FLATS & RODS) 1.CHEMICAL & MA VERIFICATION, 100% IS:1079 IS:1079 MILL TC 3 - 2 STEEL SHALL BE
AS PER SPECIFICATION PHYSICAL OF TC'S PROCURED FROM SAIL/
PROPERTIES TISCO/ RINL/ AUTHORISED
RE-ROLLERS/
MANUFACTURERS AS PER
BHEL APPROVED
SOURCES.
1.2 ZINC 1.CHEM.COMP. MA CHEM.TEST SAMPLE IS - 209 IS - 209 QC RECORD 3/2 - 1/2
2.0 IN-PROCESS
370
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-509-00-Q-001/02 TITLE
SHEET 2 OF 3 SYSTEM ITEM : EARTHING & LIGHTNING PROTECTION MATERIALS SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
371
ANNEXURE – 1
The Quality Plan shall include all the Quality Control Measures and Checks adopted by the Vendor to ensure that the
material/component/assembly/services supplied by him meet/will meet the requirements as per specifications and good practices.
They shall include all stages of operation such as materials, processes, manufacture, assembly, packing and despatch. The following
guide lines may be noted:
NOTES :
1. In absence of correlation with the test certificate(s) (e.g. material identification) samples shall be drawn bgy BHEL and all tests as per
relevent specifications shall be carried out in their presence or in recognized Government Laboratory.
2. When materials and components are initially identified and stamped by BHEL QS engineer, the identification marks shall be
presserved till despatch. Wherever this is not possible, the identification mark shall be transferred to the components in the presence
of BHEL QS Engineer unless other wise agreed.
3. For castings and forgings integral test specimens shall be provided, When this is not possible for casting, they shall be poured in the
presence of BHEL QS Engineer unless otherwise, if witnessing of test by BHEL is called for.
4. When welders qualified by reputed inspection agencies or statutory bodies are not available, qualification tests shall be conducted in
the presence of BHEL QS Engineer.
5. This Quality Plan is liable to be modified as per the requirements of approved drawings and changes in technical
specifications/drawings. If there are contradictions in respect of column 7 & 8 between this Quality Plan and the approved drawings
specifications, the latter shall prevail.
6. Wherever inspection by BHELs Purchaser/Third Party/Statutory authorities are mandatory, this shall be compiled with.
7. Inspection reports, log sheets, test reports/certificate. etc. shall be furnished to BHEL at the approproate stages or at the time of final
inspection, as required.
8. This Quality Plan is also applicable to spares, if any, under scope of supply of Vendor.
9. The quality plan shall be submitted in minimum 4 copies with a soft copy of the same or in line with contract requirements.
372
FORM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
TITLE NUMBER
QUALITY PLAN BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-003/01 TITLE
SHEET 1 OF 2 SYSTEM ITEM ELECTRICAL IN-PROCESS SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT GENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.0 FABRICATION 1. DIMENSION MA MEASUREMENT 100% APPD. DRG. APPD. DRG. INSP.REPORT 2 - -
2.0 SURFACE PREPARATION 1. PROCESS CR PROCESS PERIODIC MFR. STD./ MFR. STD./ LOG BOOK 2 - -
& PRE-TREATMENT PARAMETERS CHECK BHEL SPEC./ BHEL SPEC./
(SOLUTION RELEVANT IS RELEVANT IS
STRENGTH,
TEMPERATURE
DIPPING TIME ETC.)
3.0 PRIMER & PAINTING 1. SURFACE MA VISUAL 100% -DO- -DO- -DO- 2 - -
(SPRAYED & STOVED) FINISH &
COVERAGE
373
FORM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
QUALITY PLAN TITLE NUMBER
BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-003/01 TITLE
SHEET 2 OF 2 SYSTEM ITEM ELECTRICAL IN-PROCESS SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT GENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
4.0 MOUNTING OF VARIOUS 1. RIGIDITY MA VISUAL 100% MANUFACTURER MANUFACTURER LOG BOOK 2 - -
ITEMS DRAWINGS DRAWINGS
6.0 PRE-FINAL INSPECTION 1. ALIGNMENT MA VISUAL 100% BHEL SPEC. BHEL SPEC. TEST 2 - -
& RELEVANT. STD. & RELEVANT. STD. CERTIFICATE.
374
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-557-00-Q-002/01 TITLE
SHEET 1 OF 2 SYSTEM ITEM ELECTRONIC PCB ASSEMBLY SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.1 ELECTRONIC COMPONENTS 1. MAKE/RATING MA VISUAL SAMPLE BHEL SPEC, BHEL SPEC, INSPC. 2 - 2
ACTIVE, PASSIVE ICS, CMOS LCSO/ BARC LCSO/ BARC REPORT
ETC. COMPONENT TO COMPONENT TO
BE USED BE USED
1.2 POWER DIODES/THYRISTORS/ 1. MAKE/ RATING MA VISUAL 100% BHEL SPEC./DRG. BHEL SPEC./DRG. -DO- 2 - 1
TRANSISTORS 2.ROUTINE MA ELECT. & 100% RELV. IS/ RELV. IS/ -DO- 2 - 1
TEST MECH BS/ BHEL SPEC BS/ BHEL SPEC
1.3 PCB CONNECTORS 1. MAKE/TYPE MA VISUAL SAMPLE BHEL SPEC, BHEL SPEC, -DO- 2 - 2
LCSO/ BARC LCSO/ BARC
COMPONENT TO COMPONENT TO
BE USED BE USED
2.0 PROCESS
2.1 COMPONENTS MOUNTING 1. CORRECTNESS MA VISUAL SAMPLE MANFR. STD MANFR. STD -DO- 2 - -
& SOLDERING OF COMPONENTS
375
CUSTOMER : PROJECT SPECIFICATION :
QUALITY PLAN TITLE NUMBER :
BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-557-00-Q-002/01 TITLE :
SHEET 2 OF 2 SYSTEM ITEM ELECTRONIC PCB ASSEMBLY SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.2 ASSEMBLED PCBS (INTER- 1. FUNCTIONAL CR 1. ELECTRICAL 100% BHEL SPEC./ BHEL SPEC./ TEST 2 - 1 SOAKING AT 700C FOR
CONNECTED TOGETHER CHECK BEFORE MFR. STD. MFR. STD. CERT 72 HRS. AT ENERGISED
AS SYSTEM/ EQUIPMENT) SOAKING CONDITION
2.
2 ELECTRICAL 100% DO
-DO- DO
-DO- DO
-DO- 2 - 1 DO
-DO-
AFTER
SOAKING
OR
3. ELECTRICAL 100% -DO- -DO- -DO- 2 - 1 TEMP. CYCLE: RAPID TEMP.
AFTER CYCLE AT+ 700C-200C FOR
TEMP. CYCLE 30 MINTS. AT EACH TEMP.
TEST FIVE SUCH CYCLE
2. HV/ IR/ HV/ SWC MA ELECT. TESTS 100% RELEVANT IS/ -DO- -DO- 2 1 -
ANSI-C-37-90-
197
376
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED
PED-558-00-Q-001/01
558 00 Q 001/01 TITLE
SHEET 1 OF 3 SYSTEM ITEM :ILLUMINATION SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.0 CABLES & WIRES 1.SURFACE MA VISUAL SAMPLE BHEL SPEC. BHEL SPEC. INSPN. 3/2 2 1 TO BE PROCURED FROM
DEFECTS IS:694 IS:694 REPORT APPROVED SOURCE
IS:1554 IS:1554 & TEST
REPORT
FROM
MANUFACTURER
3 TYPE TESTS
3.TYPE CR ELEC TESTS
ELEC.TESTS ONE/TYPE BHEL SPEC.
SPEC BHEL SPEC.
SPEC TEST CERT
CERT. 3 2 1
& SIZE IS:694 IS:694
IS:1554 IS:1554
2.1 JUNCTION BOXES 1.DIMENSIONS MA MEASUREMENT 100% BHEL DRG. BHEL DRG. INSP. REPORT 3 - 2 COMPONENTS TO BE OF
APPROVED MAKE
2.PAINT SHADE/ MA VISUAL/MEAS. SAMPLE BHEL SPEC/DRG BHEL SPEC/DRG -DO- 3 - 2
THICKNESS
377
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-558-00-Q-001/01 TITLE
SHEET 2 OF 3 SYSTEM ITEM :ILLUMINATION SECTION VOLUME III
SL.
SL COMPONENT/OPERATION CHARACTERISTIC CAT.
CAT TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.2 LIGHTING PANELS AND 1.DIMENSIONS MA MEASUREMENT SAMPLE BHEL DRG. BHEL DRG. INSPT. REPORT 3 2,1 - COMPONENTS TO BE OF
LIGHTING DISTRIBUTION APPROVED MAKE
BOARDS 2.PAINT SHADE/ MA VISUAL/ -DO- BHEL SPEC/DRG BHEL SPEC/DRG INSPT. REPORT 3 2,1 -
THICKNESS MEASUREMENT
3.DEGREE OF MA TESTS 1/SIZE BHEL SPEC/ BHEL SPEC/ TEST CERT - - 2,1
PROTECTION RELEVANT IS RELEVANT IS
(INCLUDING
EXPLOSION
PROOF IF ANY)
4.PERFORMANCE MA ELECT. 100% BHEL SPEC. BHEL SPEC. INSPT. REPORT 3 2,1 - BHEL SHALL WITNESS ON
TESTS RANDOM ONE SAMPLE,
THOUGH EACH ITEM
SHALL BE CHECKED BY
THE MANUFACTURER
5.HV/IR/HV MA ELECT 100% 2.5KV AC FOR 2.5KV AC FOR INSPT. REPORT 3 2,1 - -DO-
1 MINUTE 1 MINUTE
3.0 TUNGSTEN FILAMENT LAMPS, 1. ACCEPTANCE MA TESTS SAMPLE BHEL SPEC/ BHEL SPEC/ TEST CERT 3/2 - 1
TUBULAR FLUORESCENT TESTS RELEVANT IS RELEVANT IS
LAMPS, HP MERCURY
VAPOUR LAMPS, SODIUM
VAPOUR LAMPS, BALLASTS,
LUMINAIRES
378
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-558-00-Q-001/01 TITLE
SHEET 3 OF 3 SYSTEM ITEM :ILLUMINATION SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
5.1 MATERIAL 1.CHEMICAL MA CHEM. SAMPLE IS-2713 IS-2713 -DO- 3/2 - 2,1
COMP. ANALYSIS IS:228 & IS:228 &
IS:1894 IS:1894
5.2 FINAL INSPECTION 1.WORKMANSHIP MA VISUAL & MEAS SAMPLES BHEL DRG./ BHEL DRG./ -DO- 3/2 2,1 -
AND FINISH IS:2713 IS:2713
NOTE:
IN CASE TYPE TEST CERTIFICATE FOR DEGREE OF PROTECTION/EXPLOSION PROOFNESS FROM INDEPENDENT LAB. IS NOT
AVAILABLE, THE ITEM SHALL BE TESTED AT AN INDEPENDENT LAB.
379
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-507-00-Q-004/01 TITLE
SHEET 1 OF 5 SYSTEM ITEM :INSTRUMENTATION CABLES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.1 PVC Compound(for insulation 1. Physical properties MA Physical Tests Sample IS-5831/BHEL IS-5831/BHEL Log Book/ 3/2 - 2
and sheath) Specification Specification Test Cert.
3. Make & Type MA Visual 100% Plant Std. Plant Std. -do- 2 - -
1.2 Galvanised steel wire/strip 1. Phy.and Elec. MA Physical & Sample* IS-3975 BHEL IS-3975/BHEL -do- 3/2 - 2 * Sample from each
Properties Electrical Tests Specification Specification Batch/Lot.
1.3 Copper/Aluminium Rods/ 1. Physical Properties MA Physical Tests -do- IS-613 IS-613 -do- 3/2 - 2
IS-5484 IS-5484
Wires IS-8130 IS-8130
AND BHEL AND BHEL
Specification Specification
2. Chemical
Composition & purity MA Chemical analysis -do- -do- -do- -do- 3/2 - 2
1.4 Screen & drain wire 1. Surface MA visual sample BHEL SPEC. BHEL SPEC. TC & IR 3/2 - 2
Finish
380
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-004/01 TITLE
SHEET 2 OF 5 SYSTEM ITEM :INSTRUMENTATION CABLES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
3.. Mech. Prop. MA Mech test -do- MFRS. STD. MFRS. STD. TC & IR 3/2 - 2
2.0 IN PROCESS
2.1 Wire Drawing , Tinning and 1. Physical, Electr. CR Phy.&Elect. Tests Sample BHEL Specn. BHEL Specn. Log Book 2 - 1
Annealing Finish & dimension Visual & Meas. IS-8130 IS-8130
2.2 Stranding of wires 1. No.of wires MA Counting Sample Vendors/BHEL Vendors/BHEL -do- 2 - -
Specn. & Apprd. Specn. & Apprd.
Data Sheet & Data Sheet &
Relevant IS Relevant IS
2.3 Core Insulation 1. Surface finish MA Visual 100% - Free from bulging -do- 2 - 1
(No repair permitted) burnt particles
lumps, cuts &
Scratches.
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
381
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-004/01 TITLE
SHEET 3 OF 5 SYSTEM ITEM :INSTRUMENTATION CABLES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
3. Concentricity # CR Measurement Sample Mfr's Std./Appd. Mfr's Std./Appd. Log Book 2 - 1 # To be checked at
data sheet data sheet starting & finish end of
Extruded Length
4 Dia over insulation MA Measurement Sample -do- -do- -do- 2 - -
5. Spark Test or Water CR Electrical 100% Mfr's Std. Mfr's Std. -do- 2 - 1
Immersion test
2.4 Core pairing, screening 1. Pair identification MA Visual 100% BHEL Spec. BHEL Spec. Log Book 2 - -
(provision of drain wire & appd. Data & appd. Data
& laying) sheet sheet
2.5 InnerSheath Extrusion 1. Surface finish MA Visual 100% -- Free from bulging, -do- 2 - -
burnt particles,
lumps cuts &
scratches.
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
382
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-004/01 TITLE
SHEET 4 OF 5 SYSTEM ITEM :INSTRUMENTATION CABLES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
3.Dia over inner sheath MA Measurement Sample IS-5831, IS-1554 IS-5831, IS-1554 -do- 2 - -
data sheet data sheet
2.6 Armouring 1. No.of wires/Strips MA Counting At the start of BHEL Specn./ Appd. BHEL Specn./ Appd. -do- 2 - -
the process Data sheet Data sheet
IS-3975 & IS-1554 IS-3975 & IS-1554
3. Lay Length MA Visual, Meas. At the start of BHEL Specn./Appd. BHEL Specn./Appd. Log Book 2 - -
the process Data sheet Data sheet
IS-3975 & IS-1554 IS-3975 & IS-1554
2.7 Outer Sheath Extrusion 1. Surface Finish MA Visual 100% - Free from Bulging Log Book 2 - -
Burnt particles,
lumps, cuts &
scratches
2.Sheath thickness MA Measurement Sample IS-5831 & IS-1554 IS-5831 & IS-1554 Log Book 2 - -
Appd. Data Sheet Appd. Data Sheet
4. Marking MA Visual 100% IS-1554 & BHEL IS-1554 & BHEL Test Report 2 - - Sequential marking shall
Specn. Specn. be done by printing
2.8 Finished Cable 1. Routine Test CR Elec. & Meas. 100% IS-1554 & BHEL IS-1554 & BHEL Test Report 2 - 1
Specn Specn
2. Type & FRLS Tests CR Elec., Phy & Meas. Sample * -do-/Apprd.data -do-/Apprd.data Test Report 2 - 1 * One Drum/Size/Lot
sheet sheet
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
383
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-004/01 TITLE
SHEET 5 OF 5 SYSTEM ITEM :INSTRUMENTATION CABLES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
3.0 Final Inspection 1. Finish & Length MA Visual (See remark) BHEL specn. Free from Bulging Test Report 2 1 - One drum in a Lot
IS-1554 Burnt particles,
lumps, cuts &
scratches
6. Acceptance Tests CR Phy & Elect. Tests 20% -do- -do- -do- 2 1
7. Type & FRLS Tests CR Measurement Sample# BHEL Specn. BHEL Specn. -do- 2 1 - #Type Test shall be
Apprd.Data Sheet Apprd.Data Sheet witnessed on one sample
of every lot
NOTES:-
(A) JOINTS IN WIRE SHALL BE AS PERMITTED BY IS / BHEL SPECIFICATION. VENDOR TO CERTIFY THE SAME.
(B) NO REPAIR OF CORE INSULATION PERMITTED
(C) CABLE ENDS SHALL BE SEALED AS PER BHEL SPECIFICATION
(D) PURCHASER SHALL HAVE RIGHT TO WITNESS THE SPARK TEST AT CORE STAGE
(E) RECORD OF RAW MATERIAL, PROCESS & ALL STAGES SHALL BE CERTIFIED BY VENDORS QC. AND ARE LIABLE TO AUDIT CHECK BY PURCHASER.
(F) FILLERS/DUMMY CORES ETC. SHALL BE AS PER BHEL SPECIFICATION
(G) WHEREVER EXTENT OF CHECK FOR STAGE IS MENTIONED AS SAMPLES, THE SAME SHALL BE AS PER VENDORS SAMPLING PLAN
(H) VENDOR SHALL FURNISH COMPLIANCE CERTIFICATE TO THE INSPECTION AGENCY CONFIRMING THE PACKING AS PER BHEL SPECIFICATION.
LEGEND : P : PERFORMER W: WITNESSER V: VERIFIER (1) BHEL/BHEL's CUSTOMER: 2-VENDOR : 3 SUB VENDOR
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
384
CUSTOMER PROJECT SPECIFICATION
TITLE NUMBER
QUALITY PLAN BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-005/01 TITLE
SHEET 1 OF 6 SYSTEM ITEM :LCC'S / M. BOXES/ JN. BOXES SECTION VOLUME III
SL. ONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT GENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.1 SHEET STEEL/CHANNELS 1. DUCTILITY CR BEND TEST SAMPLE IS-1079/IS-513/ IS-1079/IS-513/ LOG BOOK 3/2 - 2 FOR SHEET STEEL
IS-226 IS-226
1.2 WIRES 1. SURFACE MA VISUAL 100% BHEL SPEC./ BHEL SPEC./ -DO- 3/2 - - ONLY APPROVED MAKES
DEFECTS. IS-1554/IS-694/ IS-1554/IS-694/ TO BE USED
RELEVANT. IS RELEVANT. IS
1.3 ZINC INGOT FOR CHEM. COMP. MA CHEM. TEST EACH IS-209 IS-209 TEST CERT 3/2 - 1,2
GALVANISING
385
FORM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
TITLE NUMBER
QUALITY PLAN BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-005/01 TITLE
SHEET 2 OF 6 SYSTEM ITEM :LCC'S / M. BOXES/ JN. BOXES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.3 ELECTRICAL COMPONENTS 1. MAKE MA VISUAL SAMPLE BHEL SPEC. BHEL SPEC. LOG BOOK 3/2 - -
LIKE FUSE, SWITCHES, TYPE & BOM & BOM
INDICATING LAMPS, RATING
PUSH BUTTON,
TERMINALS GASKETS
TERMINALS, 2 OPERATION/
2.OPERATION/ CR ELECTRICAL SAMPLE RELEVANT IS AND RELEVANT IS AND DO
-DO- 3/2 21
2,1 2
CABLE GLANDS AND FUNCTIONAL TEST CATALOGUE CATALOGUE
LUGS CHECK
2.1 NIBBLING/PUNCHING 1. CUTOUT MA MEASUREMENT 100% APPD. DRGS APPD. DRGS LOG BOOK 3/2 - 2,1 STANDARD CUT OUTS
SIZES TO BE DONE WITH DIES &
PUNCHES ONLY
2.2 PANEL FABRICATION 1. DIMENSIONS MA MEASUREMENT 100% APPR. DRGS APPR. DRGS LOG BOOK 3/2 2 -
2. ALIGNMENT MA MEASUREMENT 100% MFR'S STD MFR'S STD LOG BOOK 3/2 2 -
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDOR'S COMPANY SEAL
386
FORM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
TITLE NUMBER
QUALITY PLAN BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-005/01 TITLE
SHEET 3 OF 6 SYSTEM ITEM :LCC'S / M. BOXES/ JN. BOXES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT GENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.3 SURFACE PREPARATION 1. PROCESS MA PROCESS PERIODIC BHEL SPEC., BHEL SPEC., LOG BOOK 3/2 - - IF SAND/SHOT BLASTING,
AND PRE-TREATMENT PARAMETERS CHECK MFR. SPEC., MFR. SPEC., ACID PICKLINGS IS NOT
((7 OR 8 TANK PROCESS)) LIKE BATH TEMP,, IS-6005 IS-6005 REQUIRED.
Q
CONCENTRATION,
DIPPING/
REMOVAL TIME
2.4 PRIMER APPLICATION 1. SURFACE MA VISUAL 100% MFR. SPEC., MFR. SPEC., LOG BOOK 3/2 - -
& PAINTING FINISH IS-6005 IS-6005
& COVERAGE
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDOR'S COMPANY SEAL
387
FORM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
TITLE NUMBER
QUALITY PLAN BIDDER/ QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-005/01 TITLE
SHEET 4 OF 6 SYSTEM ITEM :LCC'S / M. BOXES/ JN. BOXES SECTION VOLUME III
SL. ONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT GENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.5 WIRING, GASKET, NAME 1. WIRING LAYOUT MA VISUAL 100% APPD . DRGS & APPD . DRGS & LOG BOOK 3/2 - - PVC CHANNELS TO BE
PLATE, COMPONENT SPEC. SPEC. USED
MOUNTING ETC.
2. WORKMANSHIP MA VISUAL 100% -DO- -DO- -DO- 3/2 - -
AND FINISH
CORRECTNESS
COMPLETENESS
3 FINAL INSPECTION
3.1 COMPLETE JUNCTION 1. WORKMANSHIP MA VISUAL 100% BHEL SPEC. BHEL SPEC. INSPN 3/2 2,1 -
BOX/ LCC'S & FINISH, PAINT APPD. DRG APPD. DRG REPORT
MARSHALLING BOXES SHADE/GALV. RELEVANT. IS RELEVANT. IS
THICKNESS &
ADHESION
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDOR'S COMPANY SEAL
388
FORM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
TITLE NUMBER :
QUALITY PLAN BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-005/01 TITLE
SHEET 5 OF 6 SYSTEM ITEM :LCC'S / M. BOXES/ JN. BOXES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
6. COMPONENT MA VISUAL 100% APPD. DRG. APPD. DRG. -DO- 3/2 2,1 -
IDENTIFICATION
(MARKING/
NAME PLATES)
8. DOOR LOCK MA OPERATON 100% APPD. DRG NO MISMATCH -DO- 3/2 2,1 -
FUNCTIONING
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDOR'S COMPANY SEAL
389
FORM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
TITLE NUMBER
QUALITY PLAN BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-005/01 TITLE
SHEET 6 OF 6 SYSTEM ITEM :LCC'S / M. BOXES/ JN. BOXES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
9.OVERALL MA MEASUREMENT 100% APPD. DRG. APPD. DRG. INSPN. 3/2 2,1 -
DIMENSIONS REPORT
10. CONTINUITY CR ELECTRICAL 100% APPD. DRG., APPD. DRG., -DO- 3/2 2,1 -
BHEL SPEC., BHEL SPEC.,
& RELEVANT IS & RELEVANT IS
11. IR-HV-IR CR ELECTRICAL 100% -DO- -DO- -DO- 3/2 2,1 - IR-HV-IR
TEST TO BE DONE
12.OPERATION CR ELECTRICAL 100% -DO- -DO- -DO- 3/2 2,1 - BEFORE OPERATIONAL TESTS
INTERLOCKS OPERATION
ETC AND FUNCTION
IN ENERGISED
CONDITION
13. TEMP RISE CR ELECTRICAL ONE/ TYPE/ BHEL SPEC. BHEL SPEC. -DO- 3/2 2,1 -
(IF APPLICABLE) SIZE RELEVANT IS RELEVANT IS
14. DEGREE OF CR WATER AND ONE/ TYPE -DO- -DO- -DO- 3/2 2 - FLAME/EXPLOSION PROOF
PROTECTION & DUST TESTS, TEST, IF SPECIFIED IN
FLAME/ FLAME/ BHEL SPEC.
EXPLOSION EXPLOSION
PROOF TESTS
NOTE:
IF TC'S FOR DEGREE OF PROTECTION/EXPLOSION PROOFNESS IS AVAILABLE FROM AN INDEPENDENT LABORATORY FOR IDENTICAL DESIGN (SIZE SHALL BE
SMALLER THAN THAT INDICATED IN THE TC) THESE TESTS NEED NOT BE REPEATED.
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDOR'S COMPANY SEAL
390
CUSTOMER : PROJECT SPECIFICATION :
QUALITY PLAN TITLE NUMBER :
BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-508-00-Q-002 TITLE :
SHEET 1 OF 1 SYSTEM ITEM LEAD ACID BATTERY (DC SYSTEM) SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.0 FINISHED BATTERY / CELL 1.TYPE TEST MA TEST IS:1651 & IS:1651 & IS:1651 & INSPN 3,2 - 2,1
1652/BHEL 1652/BHEL 1652/BHEL REPORT
SPEC SPEC SPEC
BSI:6290 BSI:6290 BSI:6290
Pt-4 Pt-4 Pt-4
2.ACCEPTANCE
2 ACCEPTANCE MA TEST -DO-
DO -DO-
DO -DO-
DO 2 2,1
21 -
TEST
2.0 ACCESSORIES 1.VISUAL AND MA TEST 100% BHEL DRG BHEL DRG INSPECTION 3,2 2,1 -
DIMENSIONS
391
FORM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
QUALITY PLAN TITLE NUMBER
BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-001/01 TITLE
SHEET 1 OF 3 SYSTEM ITEM LT SWGR/CONTROL PNLS/DIST. BD SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
5. PAINT MA MEASUREMENT FEW APPD. DRG/ APPD. DRG/ -DO- 2 1 - 2. GLANDS & LUGS TO BE
THICKNESS PLACES APPD .DATA APPD .DATA SUPPLIED ALONG WITH BOARDS
SHEET.& OTHER SHEET.& OTHER
RELEVANT IS RELEVANT IS
392
FORM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
QUALITY PLAN TITLE NUMBER
BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-001/01 TITLE
SHEET 2 OF 3 SYSTEM ITEM LT SWGR/CONTROL PNLS/DIST. BD SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
10. FUNCTION CR ELECT. & MECH. 100% -DO- -DO- -DO- 2 1 - SHALL INCLUDE REMOTE
PERFORMANCE TESTS SIMULATION
11. TYPE TESTS CR ELECT. TESTS 1/ITEM -DO- -DO- -DO- 2 - 1 SEE NOTE 'C'
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDOR'S COMPANY SEAL
393
FORM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
TITLE NUMBER
QUALITY PLAN BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-001/01 TITLE
SHEET 3 OF 3 SYSTEM CABLE ITEM LT SWGR/CONTROL PNLS/DIST. BD SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
NOTE :
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDOR'S COMPANY SEAL
394
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-506-00-Q-004/01 TITLE
SHEET 1 OF 6 SYSTEM ITEM :LV & MV BUSDUCT SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.0 MATERIALS/COMPONENTS
1.1 ALUMINIUM AND COPPER 1. DIMENSION MA MEASUREMENT 100% BHEL SPECS./ BHEL SPECS./ TEST CERT 2 - -
BARS & FLEXIBLES IS:5082/IS:736 IS:5082/IS:736
IS:737/IS:1897 IS:737/IS:1897
1.2 ENCLOSURE MATERIALS 1. DIMENSION MA MEASUREMENT 100% IS:513 / BHEL IS:513 / BHEL INSP REPORT 2 - -
SPECS. SPECS.
1.3 INSULATORS, SEAL OFF 1.ROUTINE TEST MA ELECTRICAL/ 100% BHEL SPECS./ BHEL SPECS./ MRF TEST 3 - 2,1
BUSHING, CABLES, WIRES, MEASUREMENT RELEV IS RELEV. IS CERT./LOG
SPACE HEATERS BOOK
2.TYPE TEST MA ELECTRICAL/ 1/TYPE -DO- -DO- -DO- 3 - 2,1 FOR INSULATOR BUSHING
MEASUREMENT
395
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-004/01 TITLE
SHEET 2 OF 6 SYSTEM ITEM :LV & MV BUSDUCT SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.4 BELLEVILLI WASHERS, PLAIN 1.DIMENSION MA MEASUREMENT RANDOM -DO- -DO- LOG BOOK 2 - -
& SPRING
SPRING, WASHERS & CHECK
FASTENERS, DISC WASHERS
1.5 NEOPRENE RUBBER 1.OIL ABSORPTION MA MEASUREMENT 1PIECE/LOT IS-3400/BHEL IS-3400/BHEL TEST 3 - 1,2
BELLOWS & GASKET SPEC./BS-2752 SPEC./BS-2752 REPORT
1.6 BUS BAR SLEEVES 1. DIMENSION & MA MEAS & TESTS 1/LOT MANUFS STD MANUFS STD INSP. 3,2 - -
MATERIAL RELV. STD RELV. STD REPORT &
CERTIFICATE TC
2.0 IN-PROCESS
2.1 FABRICATION OF DIMENSION MA MEASUREMENT 100% APPD./MFG DRG APPD./MFG DRG INSP REPORT 2 - -
ENCLOSURES
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
396
CUSTOMER : PROJECT SPECIFICATION :
QUALITY PLAN TITLE NUMBER :
BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-004/01 TITLE
SHEET 3 OF 6 SYSTEM ITEM :LV & MV BUSDUCT SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.3 INITIAL PAINTING (PRIMER) 1.SURFACE FINISH MA VISUAL 100% -DO- -DO- -DO- 2 - -
& COVERAGE
2.4 FINISHING OF BUSBARS/ 1.TYPE OF MA VISUAL 100% BHEL SPEC/FAB BHEL SPEC/FAB -DO- 2 - -
FLEXIBLES (TINNING/ FINISH DRG/IS SPEC. DRG/IS SPEC.
PLATING,/PAINTING/
SLEEVING)
3.0 ASSEMBLY
3.1 BUSBAR ASSEMBLY 1.PHASE MA VERIFICATION 100% ASSEMBLY DRG/ ASSEMBLY DRG/ -DO- 2 - -
SEQUENCE BHEL SPEC. BHEL SPEC.
BS-159/BS-162 BS-159/BS-162
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
397
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-004/01 TITLE
SHEET 4 OF 6 SYSTEM ITEM :LV & MV BUSDUCT SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
5.TIGHTNESS OF MA MECHANICAL 100% BHEL SPEC. BHEL SPEC. INSP REPORT 2 - 1 ALUMINIUM BUS BARS JOINTS
JOINTS AND MANUFS STD MANUFS STD WILL BE BOLTED WITH BILLET
FLEXIBLE WASHER AND THIGHTENING
SHALL BE DONE BY TORQUE
6.CLEARANCE TO MA MEASUREMENT 100% -DO- -DO- -DO- 2 - 1 WRENCH ALSO THE JOINT
BODY /EARTH SURFACE SHALL HAVE
& PHASE TO SUITABLE COMPOUND
PHASE
3.2 EARTHING 1.SIZE & MA MEASUREMENT 100% BHEL SPEC. BHEL SPEC. -DO- 2 - -
MATERIAL ASSEMBLY DRG. ASSEMBLY DRG.
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
398
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-004/01 TITLE
SHEET 5 OF 6 SYSTEM ITEM :LV & MV BUSDUCT SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.COMPLETE MA VISUAL 100% BHEL SPEC BHEL SPEC 2 1 - ALL HARDWARES WHICH ARE
LAYOUT LAYOUT DRGS/ LAYOUT DRGS/ EXPOSED TO OUTDOOR SHALL
FAB.DRG. FAB.DRG. BE TOUCHED WITH ANTI
CORROSSION RUST PREVENTION
3.GENERAL & MA VISUAL 100% -DO- -DO- -DO- 2 1 - SOLUTION, VARNISH BEFORE
MARKING- PACKING REPORTS TO BE
APPEARANCE SUBMITTED TO BHEL
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
399
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-506-00-Q-004/01 TITLE
SHEET 6 OF 6 SYSTEM ITEM :LV & MV BUSDUCT SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
400
FORM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION:
TITLE NUMBER
QUALITY PLAN BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-505-00-Q-002/01 TITLE
SHEET 1 OF4 SYSTEM ITEM NEUTRAL GROUNDING RESISTOR SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.0 MATERIALS
1.1 SHEET STEEL AND 1. DIMENSIONS MA MEASUREMENT 10% IS-1079 IS-1079 INSPN. 2 - -
STRUCTURES IS-2026 IS-2026 REPORT
IS-513 IS-513
2 SURFACE FINISH
2. MI VISUAL 100% -DO-
DO -DO-
DO -DO-
DO 2 - -
1.3 RESISTOR GRIDS 1. SURFACE FINISH CR VISUAL 100% BHEL DRG./SPEC. BHEL DRG./SPEC. INSPN. 3/2 - -
MFG. DRAWING MFG. DRAWING REPORT
401
FORM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
TITLE NUMBER
QUALITY PLAN BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-505-00-Q-002/01 TITLE
SHEET 2 OF 4 SYSTEM ITEM NEUTRAL GROUNDING RESISTOR SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
4. CHEMICAL MA CHEM ANALYSIS 1/ LOT BHEL DRG./SPEC. BHEL DRG./SPEC. TEST 3/2 - 1
COMPOSITION MFG. DRAWING MFG. DRAWING CERTIFICATE
1.4 MICA INSULATED TIE-RODS 1. DIMENSIONS MA MEASUREMENT 100% MFR'S. STD. MFR'S. STD. -DO- 2 - -
MICA WASHERS, STEEL
WASHER 2 SURFACE
2. MA VISUAL INSPN
INSPN. 100% DRAWING DRAWING -DO-
DO 2 - -
1.5 PORCELAIN INSULATORS 1. DIMENSIONS MA MEASUREMENT 10% MFR'S. STD. MFR'S. STD. -DO- 2 - - PORCELAIN INSULATORS
(POST & BUSHING TYPES) SHALL BE OF APPROVED
2. SURFACE MA MEASUREMENT 100% DRAWING DRAWING -DO- 2 - - MAKE
FINISH & DEFECTS
3. DRY P.F. HV MA ELEC. 100% BHEL SPECN. BHEL SPECN TEST CERT. 2 - 1
TEST IS IS
2 FABRICATION
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDOR'S COMPANY SEAL
402
FORM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
TITLE NUMBER
QUALITY PLAN BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-505-00-Q-002/01 TITLE
SHEET 3 OF 4 SYSTEM CABLE ITEM NEUTRAL GROUNDING RESISTOR SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
3.1 RESISTOR UNIT FRAME 1. HV TEST CR ELECTRICAL 100% BHEL SPECN/ BHEL SPECN TEST 2 - -
ASSEMBLED IS-1822/ IS-1822/ REPORT
BS-587 BS-587
4 FINAL ASSEMBLY
4.1 COMPLETE NGR 1. HV TEST CR ELECTRICAL 100% BHEL SPECN/ BHEL SPECN TEST 2 1 -
IS-1822 IS-1822 REPORT
BS-587 BS-587
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDOR'S COMPANY SEAL
403
FORM NO. PEM-6041-0
CUSTOMER PROJECT SPECIFICATION
TITLE NUMBER
QUALITY PLAN BIDDER/ QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-507-00-Q-002/01 TITLE
SHEET 4 OF 4 SYSTEM ITEM NEUTRAL GROUNDING RESISTOR SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDOR'S COMPANY SEAL
404
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-557-00-Q-001/01 TITLE
SHEET 1 OF 4 SYSTEM ITEM PUBLIC ADDRESS SYSTEM SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
4.0 SPEAKERS 1. TYPE TEST MA ELECT. & 1/TYPE BHEL. SPEC. BHEL. SPEC. TEST CERT. 3/2 2 1
MEAS IS7741, IS7527 IS7741, IS7527
405
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-557-00-Q-001/01 TITLE
SHEET 2 OF 4 SYSTEM ITEM PUBLIC ADDRESS SYSTEM SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
406
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-557-00-Q-001/01 TITLE
SHEET 3 OF 4 SYSTEM ITEM PUBLIC ADDRESS SYSTEM SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
407
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-557-00-Q-001/01 TITLE
SHEET 4 OF 4 SYSTEM ITEM PUBLIC ADDRESS SYSTEM SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
7 PACKING 1.WOOD SPECIES MA VISUAL 100% BHEL SPEC/ BHEL SPEC/ -DO- 2 - 1
MFR STD MFR STD
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
408
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-507-00-Q-002/02 TITLE
SHEET 1 OF 5 SYSTEM ITEM :PVC POWER & CONTROL CABLE SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.1 PVC Compound(for insulation 1. Physical properties MA Physical Tests Sample IS-5831/BHEL IS-5831/BHEL Log Book/ 3/2 - 2
and sheath) Specification Specification Test Cert.
3. Make & Type MA Visual 100% Plant Std. Plant Std. -do- 2 - -
1.2 Galvanised steel wire/strip 1. Phy.and Elec. MA Physical & Sample* IS-3975 BHEL IS-3975/BHEL -do- 3/2 - 2 * Sample from each
Properties Electrical Tests Specification Specification Batch/Lot.
1.3 Copper/Aluminium Rods/ 1. Physical Properties MA Physical Tests -do- IS-613 IS-613 -do- 3/2 - 2
IS-5484 IS-5484
Wires IS-8130 IS-8130
AND BHEL AND BHEL
Specification Specification
2. Chemical
Composition & purityMA Chemical analysis -do- -do- -do- -do- 3/2 - 2
409
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-002/02 TITLE
SHEET 2 OF 5 SYSTEM ITEM :PVC POWER & CONTROL CABLE SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.0 IN PROCESS
2.1 Wire Drawing , Tinning and 1. Physical, Electr. CR Phy.&Elect. Tests Sample BHEL Specn. BHEL Specn. Log Book 2 - 1
Annealing Finish & dimension Visual & Meas. IS-8130 IS-8130
2.
2 Chemical test for CR Chemical Test Sample do
-do- do
-do- do
-do- 2 - -
Tinning
2.2 Stranding of wires 1. No.of wires MA Counting Sample Vendors/BHEL Vendors/BHEL -do- 2 - -
Specn. & Apprd. Specn. & Apprd.
Data Sheet & Data Sheet &
Relevant IS Relevant IS
2.3 Core Insulation 1. Surface finish MA Visual 100% - Free from bulging -do- 2 - 1
(No repair permitted) burnt particles
lumps, cuts &
Scratches.
2 Insulation thickness CR Measurement Sample Appd.data sheet Appd.data sheet -do- 2 - -
IS-1554 IS-1554
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
410
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-002/02 TITLE
SHEET 3 OF 5 SYSTEM ITEM :PVC POWER & CONTROL CABLE SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
3. Concentricity # CR Measurement Sample Mfr's Std./Appd. Mfr's Std./Appd. Log Book 2 - 1 # To be checked at
data sheet data sheet starting & finish end of
Extruded Length
4 Dia over insulation MA Measurement Sample -do- -do- -do- 2 - -
5. Spark Test or Water CR Electrical 100% Mfr's Std. Mfr's Std. -do- 2 - 1
Immersion test
2.4 Core Laying 1. Dia over laidup core MA Measurement Sample -do- -do- Log Book 2 - -
2.5 InnerSheath Extrusion 1. Surface finish MA Visual 100% -- Free from bulging, -do- 2 - -
burnt particles,
lumps cuts &
scratches.
2.6 Armouring 1. No.of wires/Strips MA Counting At the start of BHEL Specn./ Appd. BHEL Specn./ Appd. -do- 2 - -
the process Data sheet Data sheet
IS-3975 & IS-1554 IS-3975 & IS-1554
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
411
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-002/02 TITLE
SHEET 4 OF 5 SYSTEM ITEM :PVC POWER & CONTROL CABLE SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
3. Lay Length MA Visual, Meas. At the start of BHEL Specn./ Appd. BHEL Specn./ Appd. Log Book 2 - -
the process Data sheet Data sheet
IS-3975 & IS-1554 IS-3975 & IS-1554
2.7 Outer Sheath Extrusion 1. Surface Finish MA Visual 100% - Free from Bulging Log Book 2 - -
Burnt particles,
lumps, cuts &
scratches
2.Sheath thickness MA Measurement Sample IS-5831 & IS-1554 IS-5831 & IS-1554 Log Book 2 - -
Data Sheet Data Sheet
4. Marking MA Visual 100% IS-1554 & BHEL IS-1554 & BHEL Test Report 2 - - Sequential marking shall
Specn. Specn. be done by printing
2.8 Finished Cable 1. Routine Test CR Elec. & Meas. 100% IS-1554 & BHEL IS-1554 & BHEL Test Report 2 - 1
Specn Specn
2. Type & FRLS Tests CR Elec., Phy & Meas. Sample * -do-/Apprd.data -do-/Apprd.data Test Report 2 - 1 * One Drum/Size/Lot
sheet sheet
3.0 Final Inspection 1. Finish & Length MA Visual (See remark) BHEL specn. Free from Bulging Test Report 2 1 - One drum each for
IS-1554 Burnt particles, Power & control
lumps, cuts & cables in a Lot
scratches
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
412
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-002/02 TITLE
SHEET 5 OF 5 SYSTEM ITEM :PVC POWER & CONTROL CABLE SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
5. Acceptance Tests CR Phy & Elect. Tests -do- -do- -do- -do- 2 1
6. Type & FRLS Tests CR Measurement (SEE REMARK) BHEL Specn. BHEL Specn. -do- 2 1 - Type Test shall be
Apprd.Data Sheet Apprd.Data Sheet witnessed on one sample
per type(Power/control)
NOTES:- of every lot
(A) JOINTS IN WIRE SHALL BE AS PERMITTED BY IS / BHEL SPECIFICATION. VENDOR TO CERTIFY THE SAME.
(B) NO REPAIR OF CORE INSULATION PERMITTED
(C) CABLE ENDS SHALL BE SEALED AS PER BHEL SPECIFICATION
(D) PURCHASER SHALL HAVE RIGHT TO WITNESS THE SPARK TEST AT CORE STAGE
(E) RECORD OF RAW MATERIAL, PROCESS & ALL STAGES SHALL BE CERTIFIED BY VENDORS QC. AND ARE LIABLE TO AUDIT CHECK BY PURCHASER.
(F) FILLERS/DUMMY CORES ETC. SHALL BE AS PER BHEL SPECIFICATION
(G) WHEREVER EXTENT OF CHECK FOR STAGE IS MENTIONED AS SAMPLES, THE SAME SHALL BE AS PER VENDORS SAMPLING PLAN
(H) VENDOR SHALL FURNISH COMPLIANCE CERTIFICATE TO THE INSPECTION AGENCY CONFIRMING THE PACKING AS PER BHEL SPECIFICATION.
LEGEND : P : PERFORMER W: WITNESSER V: VERIFIER (1) BHEL/BHEL's CUSTOMER: 2-VENDOR : 3 SUB VENDOR
PARTICULARS BIDDER/VENDOR
BHEL NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
413
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION
VENDOR NUMBER PED-507-00-Q-006/01 TITLE
SHEET 1 OF 1 SYSTEM ITEM RIGID STEEL CONDUITS & PIPES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTICS CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
FINISHED PRODUCT
1. DIMENSIONAL MA MEASUREMENT 5 SAMPLES AS PER IS-9537 AS PER IS-9537 IR 2 1 -
CONFORMITY PER SIZE PT I & II PT I & II
PER LOT AND OTHER IS AND OTHER IS
414
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-005/03 TITLE
SHEET 1 OF 2 SYSTEM ITEM : CABLE TRAYS & ACCESSORIES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.1 ROLLED SHEET 1.CHEM.& PHY. MA VERIFICATION 100% IS1079/ IS1079/ MILL TC 3/2 - - STEEL SHALL BE PROCURED
PROPERTIES OF TC'S SPECIFICATION SPECIFICATION FROM SAIL/TISCO/RINL/
AUTHORISED RE-ROLLERS/
MANUFACTURER AS PER
BHEL APPROVED SOURCES.
IS-1730/ IS-1730/
2.DIMENSIONS MA MEASUREMENT 100% QC RECORD 3/2 - -
SPECIFICATION SPECIFICATION
1.2 ZINC CHEM.COMP. MA CHEM TEST EACH HEAT IS-209 IS-209 QC RECORD 3/2 - 1/2
2.0 IN-PROCESS
2.1 FABRICATION 1.DIMENSIONS MA MEASUREMENT 100% APPD.DRGS. APPD.DRGS. QC RECORD 2 - 1 INSPECTION AT BLACK
STAGE BY BHEL/ BHEL
AUTHORISED INSPECTION
AGENCY
2.WELDING MA VISUAL 100% GOOD WELDING FREE FROM QC RECORD 2 - 1 WELDING IS TO BE DONE
QUALITY PRACTICE DEFECTS & BY QUALIFIED WELDERS
SLAG
415
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-005/03 TITLE
SHEET 2 OF 2 SYSTEM ITEM : CABLE TRAYS & ACCESSORIES SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
3.1 (CABLE TRAY, ACCESSO- 1.DIMENSIONS MA MEASUREMENT IS-2500 APPD. DRGS. APPD. DRGS. INSP. REPORT 3 2, 1 - FASTENERS SHALL BE OF
RIES & HARDWARES) LEVEL IV REPUTED & APPROVED
MAKE.
3.RIGIDITY MA DEFLECTION 1/ LOT SPECIFICATION SPECIFICATION INSP. REPORT 2 1 - 600 MM OR 450 MM WIDE
(FOR TRAYS) TEST CABLE TRAY TO BE
TESTED
416
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-509-00-Q-001/02 TITLE
SHEET 1 OF 3 SYSTEM ITEM : EARTHING & LIGHTNING PROTECTION MATERIALS SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.1 MILD STEEL (FLATS & RODS) 1.CHEMICAL & MA VERIFICATION, 100% IS:1079 IS:1079 MILL TC 3 - 2 STEEL SHALL BE
AS PER SPECIFICATION PHYSICAL OF TC'S PROCURED FROM SAIL/
PROPERTIES TISCO/ RINL/ AUTHORISED
RE-ROLLERS/
MANUFACTURERS AS PER
BHEL APPROVED
SOURCES
SOURCES.
1.2 ZINC 1.CHEM.COMP. MA CHEM.TEST SAMPLE IS - 209 IS - 209 QC RECORD 3/2 - 1/2
2.0 IN-PROCESS
417
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
QUALITY PLAN BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-509-00-Q-001/02 TITLE
SHEET 2 OF 3 SYSTEM ITEM : EARTHING & LIGHTNING PROTECTION MATERIALS SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO.
NO CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
418
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
STANDARD QUALITY PLAN
BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-001, R-02 TITLE
SHEET 1 OF 5 SYSTEM ITEM : XLPE P
Power C bl
Cables SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.1 XLPE Compound 1. Physical properties MA Physical Tests Sample/ Lot IS:7098 & Mfrs Std. IS:7098 & Mfrs Std. Test Report 3/2 - 1,2 Raw material verification
Log Book as per approved sub-
vendor list
2. Elec.Properties MA Electrical Tests -do- -do- -do- -do- 3/2 - 1,2
1.2 Semi Conducting Compound 1. Phy.and Elec. MA Phy.and Elec. -do- Manufacturer's Manufacturer's -do- 3/2 - 1,2
Properties Tests standard standard
1.3 Copper Foil 1. Dimensions MA Measurement -do- Manufacturer's std./ Manufacturer's std./ Log Book 2 - 2
Appd. Data sheet Appd. Data sheet
1.4 PVC Compound (for sheath) 1. Physical properties MA Physical Tests Sample/ lot IS:5831/BHEL IS:5831/BHEL Log Book/ 3/2 - 2
Specification Specification Test Report
15
1.5 Galvanised steel wire/strip 1 Phy
1. Phy. and Elec
Elec. MA Physical & Sample from IS:3975/ BHEL IS:3975/ BHEL Log Book/ 3/2 - 2
Properties Electrical Tests each batch/ Specification Specification Test Cert.
lot
419
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
STANDARD QUALITY PLAN
BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-001, R-02 TITLE
SHEET 2 OF 5 SYSTEM ITEM XLPE Power Cables SECTION VOLUME III
SL
SL. COMPONENT/OPERATION CHARACTERISTIC CAT
CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
1.6 Copper/Aluminium Rods/ 1. Physical MA Physical Tests -do- IS:613, IS-5484, IS:613, IS-5484, -do- 3/2 - 2
Wires Properties IS:8130 & IS:8130 &
BHEL Specification BHEL Specification
2 Chemical
2.
Composition MA Chemical -do- -do- -do- -do- 3/2 - 2
& purity analysis
2.0 IN PROCESS
2.1 Wire Drawing , Tinning and 1. Physical, Electrical, CR Phy. & Elect. Tests Sample IS:8130 & IS:8130 & Log Book 2 - 1
Annealing Finish & dimension Visual / Meas. BHEL Specn. BHEL Specn.
2.2 Stranding of wires 1. No. of wires MA Counting -do- BHEL Specn, Apprd. BHEL Specn, Apprd. -do- 2 - -
Data Sheet & Data Sheet &
Relevant IS Relevant IS
2.3 Conductor Screening 1. Radial thickness MA -do- Sample BHEL Specn & Apprd. BHEL Specn & Apprd. Log Book 2 - -
Data Sheet Data Sheet
420
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
STANDARD QUALITY PLAN
BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-001,
Q , R-02 TITLE
SHEET 3 OF 5 SYSTEM ITEM XLPE Power Cables SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.4 Core Insulation (XLPE) 1. Surface finish MA Visual 100% - -do- Log Book 2 - 1
((No repair
p permitted)
p )
2. Concentricity # CR Measurement Sample Mfr's Std./Appd. Mfr's Std./Appd. Log Book 2 - 1 # To be checked at
data sheet data sheet starting & finish end of
Extruded Length
2.5 Insulation Screening, 1. Surface finish MA Visual Sample - Free from bulging Log Book 2 - -
(Non Metallic & Metallic ) burnt particles
lumps, cuts &
Scratches.
421
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
STANDARD QUALITY PLAN
BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-001, R-02 TITLE
SHEET 4 OF 5 SYSTEM ITEM XLPE Power Cables SECTION VOLUME III
SL. COMPONENT/OPERATION CHARACTERISTIC CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.6 Core Laying 1. Dia over laid up core MA Measurement Sample Apprd. Data Sheet Apprd. Data Sheet Log Book 2 - -
2.Sequence of lay, MA Visual & Meas. Sample IS 7098/ Mfrs.Std. IS 7098/ Mfrs.Std. -do- 2 - -
& direction
2.7 InnerSheath Extrusion 1. Surface finish MA Visual 100% -- Free from bulging, -do- 2 - -
burnt particles,
lumps cuts &
scratches.
2.8 Armour 1. No.of wires/Strips MA Counting At the start of BHEL Specn./ BHEL Specn./ -do- 2 - -
the process Apprd.Data sheet Apprd.Data sheet
3. Lay Length MA Meas. -do- Plant Standard Plant Standard Log Book 2 - -
4. Coverage MA Measurement -do- BHEL Specn./ Appd. BHEL Specn./ Appd. -do- 2 - -
Data Sheet Data Sheet
29
2.9 Outer Sheath Extrusion 1 Surface Finish
1. MA Visual 100% - Free from Bulging
Bulging, Log Book 2 - -
burnt particles, lumps,
cuts & scratches
2.Sheath thickness MA Measurement Sample Appd. Data Sheet Appd. Data Sheet Log Book 2 - -
4. Marking MA Visual 100% IS:7098, BHEL Specn. IS:7098, BHEL Specn. Test Report 2 - - Sequential marking shall
& Appd. Data Sheet & Appd. Data Sheet be done by printing
BHEL PARTICULARS BIDDER/VENDOR
NAME
SIGNATURE
DATE BIDDER'S/VENDORS COMPANY SEAL
422
CUSTOMER : PROJECT SPECIFICATION :
TITLE NUMBER :
STANDARD QUALITY PLAN
BIDDER/ : QUALITY PLAN SPECIFICATION :
VENDOR NUMBER PED-507-00-Q-001, R-02 TITLE
SHEET 5 OF 5 SYSTEM ITEM XLPE Power Cables SECTION VOLUME III
SL
SL. COMPONENT/OPERATION CHARACTERISTIC CAT
CAT. TYPE/ EXTENT OF REFERENCE ACCEPTANCE FORMAT AGENCY REMARKS
NO. CHECK METHOD OF CHECK DOCUMENT NORM OF RECORD
CHECK P W V
1 2 3 4 5 6 7 8 9 10 11
2.10 Finished Cable 1. Routine Test CR Elec. & Meas. 100% IS:7098 & BHEL specnIS:7098 & BHEL specn. Test Report 2 - 1
2 Type Tests *
2. CR Physical & Sample * BHEL Specn
Specn. BHEL Specn
Specn. -do-
do 2 1 * As per specn
specn.
Electrical Tests Apprd. Data Sheet Apprd.Data Sheet
3.0 Final Inspection 1. Finish & Length MA Visual, (See remark) BHEL specn. & BHEL Specn./ -do- 2 1 - One drum in each Lot
Measurement IS:7098 Free from Bulging
Burnt particles,
lumps, cuts &
scratches
5. Acceptance Tests CR Phy, Elect. Tests -do- BHEL Specn -do- -do- 2 1
Apprd. Data Sheet
NOTES:-
(A) JOINTS IN WIRE SHALL BE AS PERMITTED BY IS / BHEL SPECIFICATION, VENDOR TO CERTIFY THE SAME.
(B) NO REPAIR OF CORE INSULATION PERMITTED
(C) CABLE ENDS SHALL BE SEALED AS PER BHEL SPECIFICATION
(D) PURCHASER SHALL HAVE RIGHT TO WITNESS THE SPARK TEST AT CORE STAGE
(E) RECORD OF RAW MATERIAL, PROCESS & ALL STAGES SHALL BE CERTIFIED BY VENDORS QC. AND ARE LIABLE TO AUDIT CHECK BY PURCHASER.
(F) FILLERS/DUMMY CORES ETC. SHALL BE AS PER BHEL SPECIFICATION
(G) WHEREVER EXTENT OF CHECK FOR STAGE IS MENTIONED AS SAMPLES, THE SAME SHALL BE AS PER SAMPLING PLAN AGREED BY PURCHASER.
(H) VENDOR SHALL FURNISH COMPLIANCE CERTIFICATE TO THE INSPECTION AGENCY CONFIRMING THE PACKING AS PER BHEL SPECIFICATION. IN EXPORT ORDE
PACKING SHALL BE AS PER BHEL SPECIFICATION & THE SAME SHALL BE WITNESSED.
423
700MW CCPP AT NEDUNOOR, KARIMNAGAR (job no. I-59) ANNEXURE-B
BHEL Clarification (ELECTRICAL) submitted to customer
S. No. Volume Section Page No. Clause No. Technical Specification Clarification
1.0(f) &
Electrical key Fault level shall be limited to 44
line diagram kA rms for 6.6 kV systems .... & 6.6 kV system with fault level limited to 40 kA
1 III D3.0 1 OF 17
dwg. No.: as per key SLD, fault level at rms has been offered.
TCE.5960A- 6.6kV system is 40kA.
EL-SK-2001
The motors rated 175 kW and The motors rated above 175 kW shall be
1 III D3.0 12 OF 17 1.18( c) above shall be 6.6kV and motors 6.6kV and motors rated upto 175 kW shall be
rated upto 175 kW shall be 400V. 400 V.
The generator side current transformer is
(c) Generator side current envisaged as a part of the isolated phase
…………………….GT side. busduct.
2 III D 3.2 2 OF 8 2.9 (c & d)
The voltage transformer, lightning arresters &
(d) Voltage transformers with surge capacitors are envisaged as a part of
……………transformer side. SPVT & VT cubicle provided as part of
generator busduct & associated equipement.
(a) A switched
short………..disconnector.
3 III D 3.2 2 OF 8 2.10 (a & b) Manual shorting link has been offered.
(b) A manually fitted
…………..connection.
Two nos. transformer feeders (One (1) no. on
each bus), rated 2000kVA for Colony
9.3 &
supply(in customer scope) are considered in
Electrical key Additionally One (1) no.
BHEL scope as per clause no. 9.3 of section
line diagram transformer feeder on each bus
4 III D3.9 2 OF 15 D3.9 Vol-III of customer specification. Further
dwg. No.: (colony supply) for Owner’s use
HT cable, LT service transformer, LT busduct,
TCE.5960A- shall be provided.
LT power/control cables & LT switchgear for
EL-SK-2001
the same are excluded from BHEL scope of
supply.
424
700MW CCPP AT NEDUNOOR, KARIMNAGAR (job no. I-59)
BHEL deviations (ELECTRICAL) submitted to customer
S. No. Volume Section Page No. Clause No. Technical Specification Deviation
425
Doc. No. PE-TS-I59-888-E001
700MW KARIMNAGAR CCPP
TECHNICAL SPECIFICATION FOR Rev. : 0
GENERAL ELECTRICAL WORKS
Page : of
S.
Page No. Vol/ section/ Clause No. Technical Specification Clarification
No.
426
Doc. No. PE-TS-I59-888-E001
700MW KARIMNAGAR CCPP
TECHNICAL SPECIFICATION FOR Rev. : 0
GENERAL ELECTRICAL WORKS
Page : of
11. SPARES:
BIDDER TO QUOTE FOR MANDATORY SPARES, ERECTION & COMMISSIONING SPARES &
RECOMMENDED O&M SPARES (FOR 3 YEARS OF OPERATION). AN INDICATIVE LIST OF MANDATORY
SPARES IS GIVEN BELOW FOR REFERENCE.
2 DC System
( Spares applicable separately for each battery bank)
2.1 Battery
(a) Battery Cell of each type 1No.
(b) Positive Plate of each Type 1No.
(c) Negative Plate of each Type 1No.
(d) Connectors with Nuts & Bolts 1 Set
(e) Vent Plugs 1 Set
427
Doc. No. PE-TS-I59-888-E001
700MW KARIMNAGAR CCPP
TECHNICAL SPECIFICATION FOR Rev. : 0
GENERAL ELECTRICAL WORKS
Page : of
3 Lighting Fixtures
3.1 Lighting fixtures (along with lamps) 3% of each type
428
700MW KARIMNAGAR CCPP PROJECT ANNEXURE-A
PROPOSED SCOPE SPLIT OF ELECTRICAL SYSTEMS BETWEEN BHEL & EPC PARTNER
B. P EPC-PARTNER
700MW KARIMNAGAR CCPP PROJECT
PROPOSED SCOPE SPLIT BETWEEN BHEL & EPC PARTNER
SCOPE
BASIC ENGINEERING
SUPERVISION OF
COMMISSIONING
COMMISSIONING
ENGINEERING
EXECUTION &
ERECTION &
ERECTION
DETAILED
SUPPLY
Sl. TERMINAL
SYSTEM / EQUIPMENT REMARKS
no. POINT
SCOPE OF SCOPE OF
SL
ITEM CABLE TYPE CABLE CABLE REMARKS REV
No.
LISTING SUPPLY
A MV SYSTEM
1 SWGR TO OUTGOING FEEDER MV PC P P 00
2 SWGR TO DDCMIS/ UCP G B(PE)-C&I P 00
3 SWGR TO LPBS CC P P 00
INTERCONNECTING CABLES FOR MV
4 LV PC, CC,F,G P P 00
SWGR
E 220 V DC SYSTEM
1 BATTERY/ CHARGER TO DCDB LV PC P P 00
2 DCDB TO STARTER PANEL FOR DC DRIVE LV PC B(HR) B(HR) 00
3 DCDB TO PANEL/ DC LOAD LV PC P P 00
4 STARTER PANEL TO FIELD CC B(HR) B(HR) 00
F 125 V DC SYSTEM
1 BATTERY/ CHARGER TO DCDB LV PC B(HY) B(HY) 00
2 DCDB TO STARTER PANEL FOR DC DRIVE LV PC B(HY) B(HY) 00
3 DCDB TO PANEL/ DC LOAD LV PC B(HY) B(HY) 00
4 STARTER PANEL TO FIELD CC B(HY) B(HY) 00
G 24 V DC SYSTEM
1 415V SWGR TO BATTERY CHARGER LV PC P P 00
1 BATTERY/ CHARGER TO DCDB LV PC B(ED) P 00
ALL OUTGOING POWER CABLES FROM
3 LV PC B(ED) P 00
24V DCDB VARIOUS LOADS
BIANRY & ANOLOG SIGNALS FROM 24V
4 F,G B(PE)-C&I P 00
SYSTEM TO DDCMIS
H UPS
INCOMING POWER CABLE FROM SWGR
1 PC P P
TO UPS
Page 1 of 2
ALL OUTGING POWER CABLE FROM UPS
2 PC B(ED) P 00
ACDB TO VARIOUS LOAD
BIANRY & ANOLOG SIGNALS FROM UPS
3 F, G B(PE)-C&I P 00
TO DDCMIS
ALL INTERCONNECTING POWER CABLES
4 PC B(ED) P 00
BETWEEN UPS, ACDB & BATTERY
I ELECTRONIC EARTHING
1 BETWEEN DDCMIS CABINETS PC B(ED) P
2 DDCMIS CABINETS TO ELECTRONIS PC B(ED) P 00
EARTH PIT
L SWITCHYARD
1 LT SWGR TO BATTERY CHARGER LV PC P P
2 LT SWGR TO ACDB LV PC P P
3 ALL SAS/ SCADA CABLES CC, F, G, FO
4 ALL OUTGOING CABLES FROM SWYD LV PC SWYD. VENDOR SCOPE
5 DCDB
ALL OUTGOING CABLES FROM SWYD LV PC
ACDB
CONTROL CABLES BETWEEN SWYD
6 CC, F, G P P
EQPT & GT, GRP, ECP, DDCMIS
ALL CONTROL CABLES TWO BETWEEN
7 CC, F, G P P
SWYD EQPT
MV PC, LV PC,
M ANY OTHER CABLE P P
CC,F,G, FS
MV PC: MV Power cable; LV PC: LV Power cable; CC: LV Control Cable; F: F-Type Instrumentation cable; G:
G-Type Instrumentation cable; FS: Fire Survival cables
Page 2 of 2