You are on page 1of 2

AVERAGE ILLUMINANCE CALCULATION FORM

PROJECT: SHORE SUPPORT FACILITY ARIHANT


PROJECT NUMBER:
CALCULATION BY: GE (SERVICES) DGNP (V)
DATE: (DATE) 30/12/2019 PAGE: 1

ROOM BOILER SHED


IES ILLUMINANCE CATEGORY C
MAINTAINED ILLUMINANCE, FC, (LUX) 150
FIXTURE MFR/MODEL WILLIAMS/SERIES USG
DATA TYPE DISTRIBUTION DIRECT
NO. OF LAMPS PER FIXTURE 4
RATED LAMP LUMEN & WATTS/LAMP 2350
LUMENS PER FIXTURE (LPF) 9400
Room Dimensions h 13.00 W, width 10.00 L, length 12.00
hcc 3.00 Rc 0.80 Rw1 0.50
ROOM CHARACTERS hrc 7.50 Rw 0.50 Rw2 0.50
hfc 2.50 Rf 0.30 Rw3 0.50

P PERMITER 44.00
A AREA 120.00
PAR PERIMETER/AREA RATIO (P/A) 0.37
CCR 2.5 x PAR x hcc 2.75
RCR 2.5 x PAR x hrc 6.88
FCR 2.5 x PAR x hfc 2.29
Pcc FROM TABLE E-1 (Rc, Rw1, CCR) 0.48
Pw SAME AS Rw OR Rw2 0.50
Pfc FROM TABLE E-2 (Rf, Rw3, FCR) 0.24
CU FROM TABLE E-3 (FIXTURE MFGR.) 0.27
INTERPOLATING BETWEEN RCR AND
Pcc, Pw, Pfc
LOF BF - BALLAST FACTOR 0.95 0.95
VF - VOLTAGE FACTOR 1
OTHER 1
LLF LLD - LAMP LUMEN DEPREC 0.8 0.70
LDD - LUMINAIRE DIRT DEPREC. 0.87
OTHER 1
NUMBER OF FIXTURES 0.996502
NUMBER OF FIXTURES 1
LUX 150.5266