DESIGN OF

TWO-STOREY REINFORCED-CONCRETE RESIDENTIAL STRUCTURE U


STAAD.Pro & STAAD Advanced Concrete Designer RC

Main objectives
1) Calculate Wind Pressure for Components and Cladding per NSCP 20
2) Design the Roof Truss and Purlins per NSCP 2015/AISC 360-10 by LR
3) Derive dead load and live load values per NSCP 2015
4) Discuss NSCP 2015/UBC 97 Seismic parameters input to STAAD
5) Design the concrete elements in STAAD Advanced Concrete Designe
(beams, slabs, columns and footings)
SIDENTIAL STRUCTURE USING
Concrete Designer RCDC

and Cladding per NSCP 2015/ASCE 7-10


P 2015/AISC 360-10 by LRFD Method

eters input to STAAD


dvanced Concrete Designer RCDC
Purlin spacing 0.8 m
truss spacing 2.5 m

STORIES (LEVELS)

Levels Storey Height (m)

Footing to GF 1.8
GF to 2F 3
2F - Roof Beam 3
Roof Beam - Apex 2
9.8
Roof mean Height for wind load calculation
7.00 m
Roof Slope = 22.62deg
40km

Seismic Source Type A


Malolos City Bulacan
Bulacan
Bulacan = 250 kph
SAMPLE REINFORCED-CONCRETE BUILDING PROJECT USING
STAAD.Pro & STAAD Advanced Concrete Designer

STORIES (LEVELS)
Levels Storey Height (m)
Footing to GF 14
GF to 2F 3
2F - Roof Beam 3
Roof Beam - Apex 2
22

PROPERTIES
Beams Columns Slabs fc' fy
RB250x400 RC450X350 S115 20.68 Mpa 275 Mpa
(3000psi) (Gr40)

LOADS
Dead Load
1) Selfweight
Concrete unit weight = 24 kN/m3

2) Member Load
150mm CHB 3.11 kN/m per meter height
100mm CHB 2.98 kN/m per meter height

Floor Load Floors Roof


115mm slab - kN/m2
roof framing - 0.41 kN/m2
corrugated roofing sheet - 0.10 kN/m2
Floor finish 1.10 - kN/m2
Ceiling 0.10 0.10 kN/m2
MEP 0.10 0.10 kN/m2
Interior Partition - kN/m2
Water proofing - - kN/m2
1.30 0.71

Live Load
1.9 kN/m2 0.60 kN/m2

Seismic Parameters
UBC 97 / NSCP 2015
Zone = 4
Seismic Source Type = A
Importance Factor ( I ) = 1.0 (Standard Occupancy)
R = 8.5 - Special Moment Frame
Structure is located 40km from seismic source
Ct = 0.0731

Wind Parameters
Wind (ASCE 7-10 / NSCP 2015)
Vwind = 250 kph
I = 1.0
Exposure = B (typical residential structure in urban area)
=
Low‐Rise Buildings : Component and Cladding
Simplified Procedure
ASCE 7-10
PURLINS (EFFECTIVE ARE

Zone
1
2.14
-3.62
PURLIN SPACING =

1.07
-1.81
Pnet = λ Kzt Pnet9

1 1 TRUSS (EFFECTIVE AREA =


Zone
1
1.67
-3.38
TRUSS SPACING =

6.68
-13.52
PURLINS (EFFECTIVE AREA = 2.25 m2)
350kph
Zone
2 3 MEAN HEIGHT 7m
2.14 0 kn/m2 WIDTH 8m
-5.96 0 kn/m2 LENGTH 12
PURLIN SPACING = 0.5 a .8m

1.07 1.07 kn/m


-2.98 0 kn/m

TRUSS (EFFECTIVE AREA = 32m2)


350kph
Zone
2 3
1.67 1.67 kn/m2
-4.77 -7.52 kn/m2
TRUSS SPACING = 4m

6.68 6.68 kn/m 10% least horizontal dimension 0.8


-19.08 -30.08 kn/m 0.4h 3.2
4% least horizontal dimension 0.32
0.9 0.9 governs
0.8
3.2 governs
0.32
0.9
UBC 1997

0.75
PARAMETERS T = Ct (hn) sec UBC Eq. (30-8)
Z 0.4 = 0.341 sec
I 1 < 0.70 sec therefore Ft = 0;
Rwx 8.5
Rwz 8.5
Na 1
Nv 1 V= CvIW KN UBC Eq. (30-4)
S 4 RT
Ct 0.0731 = 386.90 KN
hn 7.8
W 1753.2
Cv 0.64
Ca 0.44

Total design base shear need not exceed:


V = 2.5Ca IW KN UBC Eq. (30-5)
R
= 226.88 KN DESIGN BASE SHEAR IS TOO LARGE!
USE THIS VALUE!

Design base shear shall not be less than:


V = 0.11CaIW KN UBC Eq. (30-6)
= 84.85 KN OK!

V = 0.8ZNvIW KN UBC Eq. (30-7)


R
= 66.00 KN OK!

If Ft≠ 0:
Ft = 0.07TV UBC Eq. (30-14)
= 9.24 KN
< 0.25V = 96.73

ENGR JOHN PAUL DELA ROSA (CE)


LICENSE # 98600_PRC MANILA
0.004202
1.2 DL + 1.00 E + 0.5 LL

1 1.400 D
1 1.200 D + 1.600 Lp
1 1.420 D + 0.500 Lp + 1.250 E1
1 1.420 D + 0.500 Lp + 1.250 E2
1 1.420 D + 0.500 Lp - 1.250 E1
1 1.420 D + 0.500 Lp - 1.250 E2
1 1.420 D + 1.250 E1
1 1.420 D + 1.250 E2
1 1.420 D - 1.250 E1
1 1.420 D - 1.250 E2
1 0.680 D + 1.250 E1
1 0.680 D + 1.250 E2
1 0.680 D - 1.250 E1
1 0.680 D - 1.250 E2
E = ρ Eh + Ev
1.25

= 1.25 Eh

Ev = 0.5 Ca I DL
0.5 0.44 1 DL
= DL

= 0.22 DL