A. PROJECT DETAILS
PROJECT : 5-Storey Hospital
PROJECT LOCATION : Ilo-Ilo City
PROJECT DATE : 01 April, 2019
B. REFERENCE CODE
National Structural Code of the Philippines 2015 7th Edition
C. LOADS
A.1 DEAD LOADS
a. ROOF
→ Waterproofing = 0.07 kPa (Bituminous, smooth surface)
b. CEILING
→ Acoustical Fiber board = 0.15 kPa (with suspended steel channel system
c. WALLS
→ Exterior (150mm CHB) = 3.3 kPa
(Non-Load Bearing CHB)
→ Interior (100mm CHB) = 3.17 kPa
d. FLOOR FINISH
→ Marble and mortar on = 1.58 kPa
stone-concrete fill
e. MOVABLE PARTITION = 1.00 kPa
f. MATERIALS
→ Reinforced Concrete = 24.0 kN/cu.m.
→ Steel = 77.3 kN/cu.m.
→ Soil (Compacted Backfill) = 17.3 kN/cu.m.
D. MATERIALS
→ Concrete f'c = 28 MPa
→ Steel
Gr. 60 Main Bars fy = 414 MPa
Gr. 40 Small Bars fy = 276 MPa
E. SOIL DATA
→ Soil Ult. Bearing Stress ᶲqs = 380 kPa
F. DESIGN CONSTANTS
414 Mpa 276 Mpa
ẞ 1= ẞ1 = 0.85 ẞ1 = 0.85
m= m= 17.394957983 m= 11.59664
, smooth surface)
earing CHB)
Valley Fault)
Gammad,Colene C. Group 9
CE 5-3
2014-03497-MN-0
DESIGN CRITERIA
A. PROJECT DETAILS
PROJECT : 5-Storey Hospital
PROJECT LOCATION : Ilo-Ilo City
PROJECT DATE : 01 April, 2019
B. REFERENCE CODE :
National Structural Code of the Philippines 2015 7th Edition
C. LOADS
A.1 DEAD LOADS
a. ROOF
→ Roof Covering = 0.10 kPa
Gypsum Sheating, 13mm
→ HDPE Foam Insulation = 0.03 kPa
10 mm thk (w/ 2 sides Alum & Wire Mesh)
→ Utilities (MEP) = 0.24 kPa
→ Waterproofing = 0.07 kPa
b. CEILING
→ Acoustical Fiber board = 0.15 kPa
c. WALLS
→ Exterior (150mm CHB) = 3.3 kPa
→ Interior (100mm CHB) = 3.17 kPa
→ Windows = 0.38 kPa
d. FLOOR FINISH
→ Marble and mortar on = 1.58 kPa
stone-concrete fill
e. MOVABLE PARTITION = 1.00 kPa
f. MATERIALS
→ Reinforced Concrete = 23.6 kN/cu.m.
→ Steel = 77.3 kN/cu.m.
→ Soil (Compacted Backfill) = 17.3 kN/cu.m.
D. MATERIALS
→ Concrete f'c = 28 MPa
→ Steel
Gr. 60 Main Bars fy = 414 MPa
Gr. 40 Small Bars fy = 276 MPa
E. SOIL DATA
→ Soil Ult. Bearing Stress ᶲqs = 380 kPa
F. DESIGN CONSTANTS
𝟎.𝟖𝟓−(𝟎.𝟎𝟓( 〖𝒇 414 Mpa 276 Mpa
ẞ1= ′〗 _𝒄−𝟐𝟖))/𝟕 ẞ1 = 0.85 ẞ1 = 0.85
m =
𝒇_𝒚/(𝟎.𝟖𝟓 〖𝒇′〗 _𝒄 ) m = 17.394958 m = 11.5966
ρmin
√( 〖 𝒇′〗= _𝒄 )/(𝟒𝒇_𝒚 ) 𝒐𝒓 (𝟏.𝟒)/𝒇_𝒚 ρmin = 0.0033816 ρmin = 0.00507
W.I.H
DESIGN OF STAIRS
W2
W1
Wu"=W(cosϴ)^2
Figure - Cross Section of Stair and its Equivalent Two-Span Beam Fixed at both ends
Load Data
Live Load (exit facility) = 4.80 kPa
Dead Load
(ff) Floor Finish = 1.58 kPa
(c) Ceiling = 0.15 kPa
Moment Calculation
Distribution Factors
DFBA= 0.79544
DFBC= 0.20456
Positive Moments
Span AB - Landing
Reaction @ A = 38 kN/m upward
pt. of zero shear x= 2.55 m
Mpos(AB) = 16.78 KN-m/m
Span BC - Stairs
Reaction @ C = 9 kN/m upward
pt. of zero shear x= 1.12 m
Mpos(BC) = 1.94 KN-m/m
6.65m
A A
B B
3.9m C C
D D 2.1m
E E
F F
G G
H H
2. DETAILING
column
SLAB column
280 mm
12mm ∅
see beam detail spaced @ 300mm
2m 1.8 m
TYPICAL DETAIL OF STAIRWAY AT FLOOR TO FLOOR
DESIGN OF SLAB
CONDITION:
L/S > 2.00 ONE-WAY SLAB
L/S < 2.00 TWO-WAY SLAB
1. SLAB THICKNESS
Assume Beam Width= 300 mm L= clear long span
Concrete Unit Weight= 23.6 kN/cu.m S= clear short span
For 4th Floor and 5th Floor
2. DESIGN SUMMARY
Ext. Negative
Positive Int. Negative
Slab ID S-1
ln (m) 1.6625 3.195 3.6125
Coefficient 1/24 1/14 1/11
Mu (kN-m/m) 1.00744 6.37856 10.37843
d 74 mm 74 mm 74 mm
X 0.0007406377 0.0046892937 0.0076298635
req'd ρ 0.0007438459 0.0048242396 0.0080010537
use ρ 0.0007438459 0.0048242396 0.0080010537
Main Bars
req'd s 2054.6490724 316.80482035 191.0176365
3t 300 300 300
use s (mm) 300 300 190
Temp. Bars
req'd s 565.48667765 565.48667765 565.48667765
5t 700 700 700
use s (mm) 450 450 450
Ext. Negative Positive Int. Negative
Slab ID S-2
ln (m) 1.5975 3.195 3.6125
Coefficient 1/24 1/14 1/11
Mu (kN-m/m) 0.93021 6.37856 10.37843
d 74 mm 74 mm 74 mm
X 0.0006838553 0.0046892937 0.0076298635
req'd ρ 0.0006865887 0.0048242396 0.0080010537
use ρ 0.0006865887 0.0048242396 0.0080010537
Main Bars
req'd s 2225.9941319 316.80482035 191.0176365
3t 420 420 420
use s (mm) 420 310 190
Temp. Bars
req'd s 565.48667765 565.48667765 565.48667765
5t 700 700 700
use s (mm) 450 450 450
LD = Long direction
SD = Short direction
SLAB ID S-4
Design Moment at LD, Mo = 263.15 kN-m
Design Moment at SD, Mo = 251.46 kN-m
Clear Spalong 5.90 m Wu = 10.16 Kpa
short 5.65 m
Exterior Short Direction Interior Short Direction
Midspan Cont. Edge Midspan Cont. Edge
Moment Factor (%) 57 70 35 65
CS factor (%) 73.67 78.45 78.45 78.45
MS factor (%) 26.33 21.55 21.55 21.55
Mmiddle strip (kN-m) 37.74 37.93 18.96 35.22
Mms (kN) 12.27 12.33 6.17 11.45
d (mm) 124.00 124.00 124.00 124.00
X 0.00321 0.00323 0.00161 0.00300
req'd ρ 0.00328 0.00329 0.00163 0.00305
use ρ 0.00437 0.00439 0.00217 0.00407
req'd s 145.04279 144.28351 291.40239 155.60222
use s 140 mm 140 mm 290 mm 150 mm