DECK
LOT 19, BLK. 04, PILAR VILLAGE, SAN ISIDRO CITY OF SAN FERNANDO, PAMPANGA.
Footing To GF
GF to 2F
2F to Roof Beam
Roof Beam to Apex
Properties
Beams Columns Slabs f'c fy
20.68 Mpa 414 Mpa
3000psi Gr.60
1. Self Weight
Concrete Unit weight = 24 kN/m3
2. Member Load
150mm CHB 3.11 kN/m per meter
height
100mm CHB 2.98 kN/m per meter
height
Seismic Parameters
UBC 97 / NSCP 2015
Zone = 4
Seismic Source Type
=A
Importance Factor ( I ) = 1.0 ( Standard
Occupancy )
R = 8.5 Special Moment Frame
DESIGNING OF BEAMS
Design of Critical Beam 2nd Floor
Dia.
Mu b d fc' fy d' Bar
Actual (m (m (Mp (Mp (m Es (m
(kN-m) ∅ m) m) a) a) m) β (Mpa) m)
0. 0. 2000
78.321 9 200 322 21 414 65 9 00 16
Rn =Mu/(∅bd^2 )
Rn = 4.209628435
ρ=(0.85fc')/fy [1-√(1-2Rn/(0.85fc'))]
ρ= 0.011776466
Doubly = FALSE
Singly = TRUE
Longitudinal Reinforcement
a=Asfy/(0.85f^' c b)
# of Bars = 4 Pcs
a= 93.21842017
Mu = ∅Asfy(d – a/2)
Mu = 82.33 kN-m
SHEAR DESIGN
fyt = 275
ØVc = Ø0.17ʎf'c^0.5bwd = 48.1
ØVs =Vu -ØVc = 21.9
0.5ØVc = 24.1
ØVc = 48.1
3ØVc = 144.4
5ØVc = 240.7
REGION III OK
S =ØAvfytd/ØVs = 533.3
S = d/2 = 180
REGION IV OK
S =ØAvfytd/ØVs = 533.3
S =d/4 = 90
Dia.
Mu b d fc' fy d' Bar
Actual (mm (m (Mp (Mp (m Es (mm
(kN-m) ∅ ) m) a) a) m) β (Mpa) )
0. 20000
16 0.9 150 224 21 414 65 9 0 12
Rn =Mu/(∅bd^2 )
Rn = 2.362055933
ρ=(0.85fc')/fy [1-√(1-2Rn/(0.85fc'))]
ρ= 0.006143076
ρmax=(0.003+fy/Es)/(0.005+0.003)(ρbal)
ρmax = 0.013743207
Doubly = FALSE
Singly = TRUE
a=Asfy/(0.85f^' c b)
# of Bars = 3
a= 69.91381513
Mu = ∅Asfy(d – a/2)
Mu = 23886750.16
SHEAR DESIGN
fyt = 275
ØVc = Ø0.17ʎf'c^0.5bwd = 48.1
ØVs =Vu -ØVc = 21.9
0.5ØVc = 24.1
ØVc = 48.1
3ØVc = 144.4
5ØVc = 240.7
REGION III OK
S =ØAvfytd/ØVs = 533.3
S = d/2 = 180
REGION IV OK
S =ØAvfytd/ØVs = 533.3
S =d/4 = 90
THEREFORE:
f'c (MPa) = 21
fy (MPa) = 275
S (m) = 3
L (m) = 3.6
A. m = S/L = 0.83
B. t =P*1000/180 = 73.33 100
Clear Cover (mm)=20
Main Bar (mm) = 10
Short Span(mm) d = 75 2.3
Long Span (mm)d = 65
C. LOADS (KN/m)
Dead load
1. Super Imposed = 2.3
2. SelfWeight γ*t*1= 2.76
TOTAL DL = 5.06 kN/m
Live Load (KN/m)
1. Occupancies = 1.9
Check LL reduction
Ai = 10.8
Lr = 3.12
Wu = 9.112
D. MOMENT COEFF
Cadl = 0.028
Call = 0.039
Cbdl = 0.013
Cbll = 0.02
Ca = 0.072
Cb = 0.021
F. SPACING REBAR
Rn = Mu/φbd²
ρ = 0.85f'c/fy (1-(1-2Rn/0.85f'c)^1/2)
ρmin = 1.4/fy
As = ρbd
S = 1000Ab/As
E. MOMENTS KN-m
1. SHORT SPAN
1.1. MIDDLE STRIP = 2.60
1.2. COLUMN STRIP
CONTINUOUS = 5.90
DISCONINUOUS = 0.87
2. LONG SPAN
2.1. MIDDLE STRIP = 2
2.2. COLUMN STRIP
CONTINUOUS = 2
DISCONINUOUS = 1
LOADS (Columns)
Pu = 1.2DL (Column Wt.) + Axial Load
Pu = 1.2(0.2)(0.4)(8)(23.6) + 290 KN = KN
1. As value (C1)
Use:
4- 16mm dia. bars
Using 16 mm dia RSB,
= (4)(π/4)(16)2 = 804.24 mm2
THEREFORE:
Use 400mm x 200mm section with 4 – 16mm dia. RSB reinforcements
With ties spaced 4 @ 50mm, 4 @ 100mm, rest @ 150mm.
FOUNDATION DESIGN
THEREFORE:
Use Isolated Footings. Use 200mm thickness with 300 mm spacing
using 16 mm dia. RSB both ways.