STRUCTURAL DESIGN CALCULATION

TWO-STOREY RESIDENTIAL
Project Name : BUILDING

Project Owner :

Project Address :

Designed by:

Civil Engineer
Table of Contents

1. DESIGN DATA & CRITERIA

2. STRUCTURAL DESIGN ANALYSIS


DESIGN DATA & CRITERIA

I DEAD LOADS
Concrete 24 kN/m3
Steel 7.7 kN/m3
Water 9.81 kN/m3
Soil 18 kN/m3
150mm CHB Wall (400mm Grout Spacing 2.11 kPa
100mm CHB Wall (400mm Grout Spacing 1.98 kPa
Ceramic Tile with 25mm mortar 1.1 kPa
Plaster (Each Face) 0.24 kPa
Ceiling 0.15 kPa
Electrical and Plumbing Accessories 0.2 kPa
Roofing Material with Insulation 0.25 kPa
Miscellaneous Load 1 kPa
Total 7.03 kPa
II LIVE LOADS
Stores 2400 N/m2
Total 2400 N/m2
III WIND LOAD
Basic Wind Speed 250 kph
Occupancy Category IV - Standard Occupancy
Wind Directionality Factor, Kd 1
Exposure Category Exposure B
Topographic Factor, Kzt 1
Gust Effect Factor 0.85
Enclosure Classification Enclosed

IV LOAD COMBINATION
LOAD AND RESISTANCE FACTOR DESIGN LOAD COMBINATION
DEAD LOADS
Concrete
24.0 kN/m3
Steel
7.7 kN/m3
Water
9.81 kN/m3
Soil
18.0 kN/m3
150mm CHB Wall (400mm Grout Spacing)
2.11 kPa
100mm CHB Wall (400mm Grout Spacing)
1.98 kPa
Ceramic Tile with 25mm mortar
1.10 kPa
Plaster (Each Face)
0.24 kPa
Ceiling
0.15 kPa
Electrical and Plumbing Accessories
0.20 kPa
Roofing Material with Insulation
0.25 kPa
• LIVE LOADS
Office
2.4 kPa
Roof Live Load
Storage Area
1.0 kPa
6.0 kPa
• WIND LOAD
Basic Wind Speed
250 kph
Occupancy Category
IV – Standard Occupancy
Wind Directionality factor, Kd
1
Exposure Category
Exposure B
Topographic Factor, Kzt
1
Gust Effect Factor
0.85
Enclosure Classification
Enclosed