LEGEND: SERVICE ENTRANCE TYPICAL LOAD SCHEDULE : P1 T0 P5

M KILOWATT HOUR METER CIRCUIT CB


DESCRIPTION QTY VOLTS WATTS AMPS CONDUCTOR SIZE CONDUIT SIZE
2-14.0 mm²˛ THW
NO. RATING
SERVICE
PANEL BOARD
Stranded Copper Wire,
C1 4 230 400 1.74 20 A 2- 3.5 mm² THW Stranded Copper Wire 20 mm dia. uPVC Pipe
ENTRANCE inside 20mm Ø RSC pipe LIGHTING LOAD
12W LED BULB 360 20 A 20 mm dia. uPVC Pipe
C2 CONVENIENCE OUTLET 2 230 1.56 2- 3.5 mm² THW Stranded Copper Wire
1 18W LED TUBE
C3 A.C.U. OUTLET 1HP 1 230 746 3.24 30 A 20 mm dia. uPVC Pipe
2- 5.5 mm² THW Stranded Copper Wire
# CIRCUIT HOMERUN
MAIN 230 1506 6.54 40 A 2- 8.0 mm² THW Stranded Copper Wire 20 mm dia. uPVC Pipe
M2 CONVENIENCE OUTLET
2-14 mm²˛ THW
Stranded Copper Wire,
inside 20mm Ø RSC pipe acu
AIRCON OUTET
COMPUTATIONS: IL = 1,506 WATTS (0.85DF) / 230VOLTS
PB 2-8.0 mm²˛ THW Stranded
Copper Wire, inside 20mm Ø ONE GANG SWITCH
= 5.56 AMPERES
SA
uPVC pipe
60A ,2p
LIGHTING CKT LINE TOTAL CONNECTED LOAD:
POWER CKT LINE IT = 5.56 AMPERES X 5
= 27.83 AMPERES
SUB
M1
SUB
M3
SUB
M5
SPECIFICATION: USE:
P1 P3 P5 SINGLE PHASE 230 VOLTS, 60HZ
POWER SUPPLY : 1- 60A, 2P,CB AS MAIN
SERVICE ENTRANCE :
MAIN 40A 20A C1 MAIN 40A 20A C1 MAIN 40A 20A C1
CONDUCTOR SIZE : 14 mm² THW STRANDED COPPER WIRE
2- 14 mm² THW Stranded Copper Wire inside 20mm Ø
C2 20A 30A
C3 C2 20A 30A
C3 C2 20A 30A
C3 CONDUIT SIZE : 20 MM DIA. RSC PIPE Rigid Steel Conduit Pipe for Service Entrance
MAIN DISCONNECT : SEE RISER DIAGRAM
SUB SUB
M2 M4 BRANCH CIRCUIT :
P2 P4 CONDUCTOR SIZE, CONDUIT SIZE AND BREAKERS RATING SHALL BE
AS INDICATED IN THE SCHEDULE OF LOADS AND / OR RISER DIAGRAM
MAIN 40A 20A C1 MAIN 40A 20A C1
ELECTRICAL INSTALLATIONS SHALL BE DONE IN ACCORDANCE
C2 20A 30A
C3 C2 20A 30A
C3 WITH THE LATEST RULES & REGULATION OF THE PHILIPPINE
ELECTRICAL CODE & THE LOCAL POWER COMPANY & ORDINANCE
PROMULATED BY THE LOCAL GOVERNMENT.

SINGLE LINE DIAGRAM ALL ELECTRICAL MATERIALS TO BE INSTALLED HEREIN MUST BE


BRAND NEW & OF APPROVED TYPE & QUALITY.
ALL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A
DULY LICENSED ELECTRICAL ENGINEER OR OF A REGISTERED
MASTER ELECTRICIAN
R I Z A L A V E N U E
MOUNTING HEIGHTS ABOVE FINISH FLOOR LINE

ISAAC ABALAYA
SWITCHES
PANEL BOARD
1.37 m
1.83 m
center
center NFA

WAREHOUSE
CENTRAL
KILOWATT HOUR METER 1.83 m center
CONVENIENCE OUTLET 0.30 m center

N
2600mm 1750mm 2900mm 1950mm 1750mm 1750mm 1750mm 1750mm 1500mm 1750mm 1650mm

N S T.

ELEMENTARY
ISAAC ABALAYAN
SCHOOL
d
d c d
d c d c c PUROK
c ACACIA

Sc Sc Sc Sc Sc
3150mm

4150mm

1 1 1 1 b
1 b b b b

P3
P5 P4 2 P2 P1 THIS SITE
2 2 3 2 3 3 2
3 3
acu acu acu acu
S abd S abd acu
S abd Sabd S abd
SUB SUB SUB SUB SUB
M5 M4 M3 M2 M1

1 1 1
1

VICINITY MAP
a 1000mm

a a
a a
1

E1 LIGHTING AND POWER LAYOUT


12 SCALE: NTS

SIGNED/ SEALED PROJECT TITLE LOCATION : SHEET TITLE OWNER SHEET NO.:

ELECTRICAL INSTALLATION BRGY. SAN JOSE, DIGOS CITY ELECTRICAL PLAN ENGR. ISABEL O. CAMOCAMO