You are on page 1of 1

Building Performance Rating Method Calculation of the Proposed and Baseline Building Performance

Baseline Building Service Hot-Water heating system and, based on the occupancy of the proposed building, the
Systems occupancy of the proposed building, there building has service water loads, then an
In general, the service hot water system in is no service hot water load, then no electric resistance electric water heating
the baseline building shall comply with the service hot water system shall be modeled system shall be used for both the baseline
mandatory measures and prescriptive in the baseline building or the proposed building and the proposed building that
requirements specified in Chapter 7 of the building. meets the minimum efficiency
Standard. The baseline building water If an addition is being rated with requirements of § 7.2.2. An identical
heating system shall use the same energy consideration of the existing portion of system shall be used for both the
source as the proposed building, if the the building and the existing building has a proposed building and the baseline
proposed building uses electric water water heater that will continue to be used building so that there is no benefit or
heaters, then so should the baseline for the existing building, the addition or penalty in the building performance rating.
building. The baseline building service both, then the baseline building service When the proposed building includes
water heating system shall meet the water heating system shall reflect the a single system for both space heating and
minimum efficiency requirements actual system type using actual component service water heating, the baseline building
specified in § 7.2.2 of the Standard. capacities and efficiencies of the existing shall use separate systems meeting the
Not all nonresidential buildings have system. minimum efficiency requirements
service hot water systems. In the In the case where the proposed applicable to each system individually.
extremely rare case that the proposed building does not include a service water When the prescriptive requirements of
building does not include a service water heating system, but based on the § 6.3.6.2 require that heat be recovered

Table G-B—Acceptable Occupant Densities, Receptacle Power Densities, and Service Hot Water Consumption1

Receptacle
Occupancy Density2 Power Density3 Service Hot Water Quantities4
Building Type ft2/Person Watts/ ft 2 Btu/h . Person
(Btu/h . ft2) (Btu/h . ft2)

Assembly 50 (4.60) 0.25 (0.85) 215


Health/Institutional 200 (1.15) 1.00 (3.41) 135
Hotel/Motel 250 (0.92) 0.25 (0.85) 1,110
Light Manufacturing 750 (0.31) 0.20 (0.68) 225
Office 275 (0.84) 0.75 (2.56) 175
Parking Garage NA NA NA
Restaurant 100 (2.30) 0.10 (0.34) 390
Retail 300 (0.77) 0.25 (0.85) 135
School 75 (3.07) 0.50 (1.71) 215
Warehouse 15,000 (0.02) 0.10 (0.34) 225
1. The occupancy densities, receptacle power densities, and service hot water consumption values are from ASHRAE Standard 90.1-1989 and addenda.
2. Values are in square feet of conditioned floor area per person. Heat generation in Btu per person per hour is 230 sensible and 190 latent. Figures in parenthesis are equivalent Btu per
hour per square foot.
3. Values are in Watts per square foot of conditioned floor area. Figures in parenthesis are equivalent Btu per hour per square foot. These values are the minimum acceptable. If other
process loads are not input (such as for computers, cooking, refrigeration, etc.), it is recommended that receptacle power densities be increased until total process energy consumption is equivalent
to 25% of the total.
4. Values are in Btu per person per hour.

G-32 User’s Manual for ANSI/ASHRAE/IESNA Standard 90.1-2007

You might also like