CEE 465 – Design of Structural Systems

Laura Citlali Medina Rodriguez


Final Project: Five Tower Bridge
Submittal #6
Due Date: March 30th, 2019

Seismic Loads

Figure 1. Elevation of Five Tower Bridge building.

Parking Level 3 +60'-0''


Parking Level 2 +70'-6''
Parking Level 1 +79'-9''
Lobby Level +90'-9''
Level 2 +102'-10''
Level 3 +114'-11''
Elevation Level 4 +127'-0''
Level 5 +139'-1''
Level 6 +151'-2''
Level 7 +163'-3''
Level 8 +175'-4''
Penthouse +187'-8 3/4''
Parapet +207'-11''
Total Height 147’ - 11’’
EW Longitude 233’- 4’’
NW Longitude 117’

Although the building has different dimensions in the parking levels and in the office
levels, the dimensions of the office levels will be used throughout all the building for
conservative calculatations. Floor loadings will be assumed depending on the floor
materials and general use:

Dead (psf) Office


Composite metal deck 42
Garage
One-way reinforced concrete 75
CMEP
Acoustic fiber board
10
MEP component
Office Floor
Terrazo 5
Marble 33
Roofing
Insulation + Waterproof 10
Office 50 + 15 (per partitions)
Live (psf) Parking 40
Lobbies 100

For typical floor:


w total=1.2 D+ 1.6 L=1.2 ( 42+10+5+10 ) +1.6 ( 50+15 ) =0.1844 kips/ ft 2
w=5034.12 kip

For lobby level:


w total=1.2 D+ 1.6 L=1.2 ( 42+10+33+10 ) +1.6 ( 100 )=0.274 kips/ ft 2
w=7480.2 kip

For parking levels:


w total=1.2 D+ 1.6 L=1.2 ( 75+10 )+ 1.6 ( 40 )=0.166 kips/ft 2
w=4531.8 kip

According to the ASCE 7-10, Chapter 11 and 12:


Parameter Symbol Value Clause or Equation
0.207
Ss USGS Report
Mapped Acceleration Parameters g
(with 5% damping considered) 0.061
S1 USGS Report
g
Fa 1.203 Table 11.4-1
Site Coefficients
Fv 1.721 Table 11.4-2
0.249
SMS 11.4-1
Maximum Considered Earthquake g
(MCE) 0.105
SM1 11.4-2
g
0.166
SDS 11.4-3
Design Spectral Acceleration g
(DSA) 0.070
SD1 11.4-4
g
Risk Category Type II Table 1.5-1
Seismic Importance Factor Ie 1.00 Table 1.5-2
Classification
Class C
determined
Site Soil Classification “Very Dense Soil
from the geotechnical
and Soft Rock”
report provided
S MS=F a S s=0.249 g S M 1=F v S1=0.105 g
2 2
S DS= S s=0.166 g S D 1= S1=0.070 g
3 3

The approximate period will be, using Table 12.8-2:

T a=C t hnx

where C t = 0.02
h n = height of building
x = 0.75

T a=0.8483 seconds

Spectral values:
SD1
T 0=0.2 =0.0843
S DS

S D1
T s= =0.4217
S DS

SD1
Sa = =0.0825 g
T

Equivalent Base Shear:


S
C s= D 1 =0.017
R
T
I( )
Considering special reinforced concrete shear walls (Case A.1) as lateral resisting
system:

Bearing walls system


Response Modification Coefficient R 5
Overstrength Factor Ω0 2 ½
Deflection Amplification Factor Cd 5
Structural System Limitations Including Structure Height hn NL

V =C s W

V typical floor=83.082 kips V lobby =108.313 kips V parking=74.792kips

Using these values:


w s h kx
C vx = n

∑ w i h ki
i=1

where k = 1.17415 since:


For a period of 0.5 s∨less k=1
For a period of 2.5 s∨more k=2
For a period between 0.5∧2.5 s linear interpolation

F x =C vx V

Level hx (ft) wx (kips) wxhxk Cvx Fx


Parking Level 3 0 4531.8 0 0 0
Parking Level 2 10.5 4531.8 71663.852 0.00725 0.542
Parking Level 1 19.75 4531.8 150473.785 0.01522 1.138
Lobby Level 30.75 7480.2 417702.003 0.04204 5.190
Level 2 42.83 5034.12 414801.736 0.04196 3.486
Level 3 54.92 5034.12 555428.504 0.05619 4.668
Level 4 67 5034.12 701470.309 0.07096 5.896
Level 5 79.08 5034.12 852194.120 0.08621 7.162
Level 6 91.17 5034.12 1007125.834 0.10188 8.464
Level 7 103.25 5034.12 1165554.480 0.11791 9.796
Level 8 115.33 5034.12 1327251.137 0.13426 11.155
Penthouse 127.65 5034.12 1495229.678 0.15126 12.567
Parapet 147.92 5034.12 1777708.898 0.17983 14.941
9885382.486 83.8314