PORTAL FRAME
DESIGN CALCULATION
MARCH 2021 – REVISION No. 00
PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00
INTRODUCTION
TRASAN CONTRACTING PTY LTD is pleased to be part of the contract for project
PROPOSED BOAT SHED by SIMON TOCAS.
The project is located at PINDERI CRESCENT, DAMPIER.
DOCUMENT SCOPE
STRUCTURAL STEEL FRAMING
REFERENCES
The design calculation was made sure to be in accordance with the following
Structural Design Codes and Standards:
● Australian/New Zealand Standard, AS/NZS 1170.0:2002 for Wind Load;
● Design Guide for Metal Cladding Fasteners, AAMA TIR-A9-14 for Fasteners Design;
● Australian/New Zealand Standard, AS/NZS 4100:2020 for Steel Structures.
● Australian/New Zealand Standard, AS/NZS 4600:2018 for Cold-formed Steel Structures.
● Australian Standard, AS 4600:2018 for Reinforced Concrete Structures.
MATERIAL SPECIFICATIONS
STEEL FRAMES
Type C250/C250L0 AS 1163
Unit Weight 77.00 kN/m3
Modulus of Elasticity 200000 MPa
Tensile Strength 320 MPa
Yield Strength 250 MPa
FOUNDATION FOOTING
Concrete Type 20 MPa
Unit Weight 23.54 kN/m3
Flexural Tensile 2.70 MPa
Principal Tensile 1.80 MPa
Mean Compressive 24.00 MPa
Modulus of Elasticity 200000 MPa
Rebar Grade 40
Tensile Strength 420 MPa
Yield Strength 280 MPa
SCREWS
Type STAINLESS STEEL 316
PERFORMANCE CRITERIA
All members shall not exceed the maximum allowable stress capacity of the analyzed section.
(D/C Ratio ≤ 1.00)
All members shall not exceed the maximum allowable deflections:
STEEL FRAMES
For Frames with Load parallel to the axis of consideration (Simply Supported)
LOAD COMBINATION: TDL + WL
L/360 L = unsupported span
For Portal Frames Subject to Sway
LOAD COMBINATION: TDL + WL
H/400 H = unsupported span
APPE
NDIX
1:
Techn
ical
Data
TRASAN
EXPOSURE CATEGORY
Technical Data
Terrain Category 1
TRASAN
Technical Data Hip or Gable Roof with θ = 15°
TRASAN
Technical Data
TRASAN
Technical Data
Shielding Multiplier, Ms 1
TRASAN
Technical Data
Topography Factor, Mt 1
TRASAN
Technical Data
d= 0m b= 0m d/b = #DIV/0!
Ext. Pressure Leeward, Cp,e -0.3
TRASAN
x/h = 1.11
Ext. Pressure Sidewalls, Cp,e -0.5
Technical Data
mean roof height, h = 4937.5 mm sidewall length, d = 5500 mm
h/d = 0.90
Ext. Pressure Roof Downwind, Cp,e -0.58
Technical Data
External Factor, Kc,e 0.8
Internal Factor, Kc,i 0.8
Technical Data
TRASAN
Technical Data