PROPOSED BOAT SHED

SIMON TOCAS

PORTAL FRAME
DESIGN CALCULATION
MARCH 2021 – REVISION No. 00

 
PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00

INTRODUCTION
TRASAN CONTRACTING PTY LTD is pleased to be part of the contract for project
PROPOSED BOAT SHED by SIMON TOCAS.
The project is located at PINDERI CRESCENT, DAMPIER.

DOCUMENT SCOPE
STRUCTURAL STEEL FRAMING

REFERENCES
The design calculation was made sure to be in accordance with the following
Structural Design Codes and Standards:
● Australian/New Zealand Standard, AS/NZS 1170.0:2002 for Wind Load;
● Design Guide for Metal Cladding Fasteners, AAMA TIR-A9-14 for Fasteners Design;
● Australian/New Zealand Standard, AS/NZS 4100:2020 for Steel Structures.
● Australian/New Zealand Standard, AS/NZS 4600:2018 for Cold-formed Steel Structures.
● Australian Standard, AS 4600:2018 for Reinforced Concrete Structures.

MATERIAL SPECIFICATIONS
STEEL FRAMES
Type C250/C250L0 AS 1163
Unit Weight 77.00 kN/m3
Modulus of Elasticity 200000 MPa
Tensile Strength 320 MPa
Yield Strength 250 MPa
FOUNDATION FOOTING
Concrete Type 20 MPa
Unit Weight 23.54 kN/m3
Flexural Tensile 2.70 MPa
Principal Tensile 1.80 MPa
Mean Compressive 24.00 MPa
Modulus of Elasticity 200000 MPa
Rebar Grade 40
Tensile Strength 420 MPa
Yield Strength 280 MPa
SCREWS
Type STAINLESS STEEL 316

Trasan Contracting Pty Ltd Page 1 of 16


PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00

PERFORMANCE CRITERIA
All members shall not exceed the maximum allowable stress capacity of the analyzed section.
(D/C Ratio ≤ 1.00)
All members shall not exceed the maximum allowable deflections:
STEEL FRAMES
For Frames with Load parallel to the axis of consideration (Simply Supported)
LOAD COMBINATION: TDL + WL
L/360 L = unsupported span
For Portal Frames Subject to Sway
LOAD COMBINATION: TDL + WL
H/400 H = unsupported span

Trasan Contracting Pty Ltd Page 2 of 16


PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00

WIND LOAD (AS/NZS 1170.0:2002, AS/NZS 1170.1:2002, AS/NZS 1170.2:2011)


Occupancy Category Miscellaneous (AS/NZS 1170.0 & 1170.1 :2002)
Building Category Enclosed (AS/NZS 1170.2 :2011)
Western Australia Town Karratha 1 Section 4.2.1 (a) - 1170.2
Terrain Category 1 1 2 Figure 3.1(A) - 1170.2
Exposure Category 2 Region D - Severe Tropical Cyclones 3 Table 5.2(B) - 1170.2
Internal and External Pressure for Walls and Roofs 4 Table 3.3 - 1170.2
Mean Roof Height, h 4.95 5 Table 3.3 - 1170.2
Podium Length, L 13.60 6 Section 3.4 - 1170.2
Podium Width, B 5.50 7 Table 3.1 - 1170.2
Podium Corner Width, a 0.55 m 8 Table 3.1 & 3.2 - 1170.0
Tower Length, L 13.60 m 9 Table 3.2 - 1170.2
Tower Width, B 5.50 m 10
Table 4.3 - 1170.2
Tower Corner Width, a 0.55 m 11
Section 4.4 - 1170.2
Shape Category Regular 12
Table 5.1(B) - 1170.2
Roof Type 3 Hip or Gable Roof with θ = 15° 13 Table 5.2(A) - 1170.2
System Type MWFRS 14 Table 5.2(B) - 1170.2
Design Working Life 4 >100 yrs 15 Table 5.2(C) - 1170.2
Annual Exceedance Probability 5 1 / 1000 16 Table 5.3(C) - 1170.2
Region Factor, F 6 1.1 17 Table 5.3(B) - 1170.2
Wind Velocity, V R 7 94 m/s 18 Table 5.5 (Case b) - 1170.2
Building Type Low Rise 19 Table 5.5 (Case b) - 1170.2
Importance Level, I 8 2 - Ordinary 20 Section 5.4.4 - 1170.2
Wind Direction Multiplier, Md 9 1.00 21
Section 5.4.5 - 1170.2
Shielding Multiplier, Ms 10
1.00 22
Section 5.4.2 - 1170.2
Topography Factor, Mt 11 1.00 23
Section 5.2(1) - 1170.2
Internal Pressure Coefficients, Cp,i 12
-0.30 , 0.0 24 Section 5.2(2) - 1170.2
Ext. Pressure Windward, Cp,e 13
0.80 25 Section 5.2(2) - 1170.2
Ext. Pressure Leeward, Cp,e 14 -0.30 26 Section 5.2(2) - 1170.2
Ext. Pressure Sidewalls, Cp,e 15
-0.50 27 Section 5.2(2) - 1170.2
Ext. Pressure Roof Downwind, Cp,e 16
-0.58 28 Section 5.2(2) - 1170.2
Ext. Pressure Roof Upwind, Cp,e 17 -0.94 , -0.46 29 Section 5.2(2) - 1170.2
External Factor, Kc,e 18 0.80
Internal Factor, Kc,i 19 0.80
Local Pressure Factor, Kl 20 1.00
Permeable Cladding Reduction, Kp 21
1.00
Area Reduction Factor, Ka 22 1.00
Internal Aerodynamic Shape Factor, Cfig,i 23 -0.24 , 0.00
Windward Wall External A.S.F , Cfig,e 24 0.640
Leeward Wall External A.S.F , Cfig,e 25 -0.240
Side Walls External A.S.F , Cfig,e 26 -0.400
Roof Downwind External A.S.F , Cfig,e 27 -0.464
Roof Upwind Upwind A.S.F , Cfig,e 28 -0.752
Roof Upwind Upwind A.S.F , Cfig,e 29 -0.368

WIND LOAD (AS/NZS 1170.0:2002, AS/NZS 1170.1:2002, AS/NZS 1170.2:2011)


INTERNAL WIND
Floor Design EXTERNAL WIND PRESSURE, kPa NET EXTERNAL WIND PRESSURE, kPa (Pe-Pi)
PRESSURE, kPa
Mz,cat 6 V sit,β 7
Level Z (m) Windward Leeward S idewa rd Roof (Down) Roof (Up) Roof (Up) Windward Leeward S idewa rd Roof (Down) Roof (Up) Roof (Up)
P i,min P i,max
P e,max P e,max P e,max P e,max P e,max P e,max P e,max P e,max P e,max P e,max P e,max P e,max
GF 4.526 0.94 88.19 -1.120 0.000 2.986 -1.120 -1.866 -2.165 -3.509 -1.717 4.106 -1.120 -1.866 -2.165 -3.509 -1.717
ROOF 4.9505 0.95 89.18 -1.145 0.000 3.054 -1.145 -1.909 -2.214 -3.589 -1.756 4.200 -1.145 -1.909 -2.214 -3.589 -1.756

Trasan Contracting Pty Ltd Page 3 of 16


PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00

APPE
NDIX
1:
Techn
ical
Data

Trasan Contracting Pty Ltd Page 4 of 16


PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00

TRASAN
EXPOSURE CATEGORY

Technical Data

Terrain Category 1

Trasan Contracting Pty Ltd Page 5 of 16


PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00

TRASAN
Technical Data Hip or Gable Roof with θ = 15°

Trasan Contracting Pty Ltd Page 6 of 16


PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00

TRASAN
Technical Data

Importance Level 2 - Ordinary

Trasan Contracting Pty Ltd Page 7 of 16


PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00

Wind Direction Multiplier 1

TRASAN
Technical Data
Shielding Multiplier, Ms 1

Trasan Contracting Pty Ltd Page 8 of 16


PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00

TRASAN
Technical Data
Topography Factor, Mt 1

Internal Pressure Coefficients, Cp,i -0.3 , 0

Trasan Contracting Pty Ltd Page 9 of 16


PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00

Ext. Pressure Windward, Cp,e 0.8

TRASAN
Technical Data

d= 0m b= 0m d/b = #DIV/0!
Ext. Pressure Leeward, Cp,e -0.3

Trasan Contracting Pty Ltd Page 10 of 16


PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00

horizontal distance, x = 5500 mm mean roof height, h = 4937.5 mm

TRASAN
x/h = 1.11
Ext. Pressure Sidewalls, Cp,e -0.5

Technical Data
mean roof height, h = 4937.5 mm sidewall length, d = 5500 mm
h/d = 0.90
Ext. Pressure Roof Downwind, Cp,e -0.58

Trasan Contracting Pty Ltd Page 11 of 16


PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00

TRASAN mean roof height, h = 4937.5 mm

Ext. Pressure Roof Upwind, Cp,e -0.94


h/d =
,
sidewall length, d =
0.90
-0.46
5500 mm

Technical Data
External Factor, Kc,e 0.8
Internal Factor, Kc,i 0.8

Local Pressure Factor, Kl 1

Trasan Contracting Pty Ltd Page 12 of 16


PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00

TRASAN Permeable Cladding Reduction, Kp 1

Technical Data

Area Reduction Factor, Ka 1

Trasan Contracting Pty Ltd Page 13 of 16


PROPOSED BOAT SHED SIMON TOCAS
PORTAL FRAME – STEEL ANALYSIS REVISION NO. 00

TRASAN
Technical Data

Trasan Contracting Pty Ltd Page 14 of 16