ELECTRICAL SYMBOLS USED ELECTRICAL SPECIFICATION

SYMBOLS DESCRIPTION
· ALL WORKS HEREIN SHALL BE DONE IN ACCORDANCE W/THE PROVISIONS OF
FLUORESCENT LIGHT ELECTRICAL CODE OF THE PHILIPPINES AND THE LOCAL ORDINANCES AND
THE REQUIREMENTS OF THE COMPANY.
PIN LIGHT
· TYPES OF ELECTRICAL VOLTAGE SHALL BE 1 DIA,2W,250 V,60 HZ,ACB.
CIRCULAR LIGHT FIXTURE
· ALL MATERIALS AND FIXTURES SHALL BE BRAND NEW AND NEW APPROVE
DUPLEX CONVENIENCE OUTLET TYPE FOR LOCATION AND PURPOSES INTENDED.

PANEL BOARD · ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHT:

CIRCUIT HOMERUN WALL SWITCHES 1.40 mm ABOVE F.F.L.


CONV. OUTLET 0.40 mm ABOVE F.F.L.
CIRCUIT BREAKER PANEL BOARD 1.75 mm ABOVE F.F.L.
KHW METER 1.60 mm ABOVE F.F.L.
CONDUIT
· METHOD OF WIRING SHALL BE USE NON-METALLIC RIGID CONDUIT PVC S-401
Sa 1- GANG SWITCH TO CONCEALED IN CEILING AND DOUBLE WALLS AND EMBEDDED CONCRETE
WALL AND FLOOR SLABS.
Sab 2- GANG SWITCH
· ALL OUTDOOR INSTALLATIONS SHALL BE WEATHER PROOF.
Sabc , Sdef 3- GANG SWITCH
· ALL LIGHTING AND POWER PANEL BOARD SHALL BE CIRCUIT BREAKER TYPE.
WP WEATHER PROOF C.O.
· PULL OR JUNCTION BOXES SHALL BE INSTALLED WHERE NECESSARY EVEN IF
GROUND NOT INDICATED IN THE PLAN.
ACU

AIR CONDITION UNIT · ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE SUPERVISION OF A DULY
LICENSED ELECTRICAL ENGINEER OR MASTER ELECTRICIAN.