PRESENTATION
BOILERS
MISSION OS OIL FIRED STEAM SMALL
? ?
? ?
MISSION OL
BOILER DESIGN
STEAM DIAGRAM
STEAM WATER DIAGRAM
HOT WELL
FEED WATER PUMPS
BOILERS SYTEM OVERVIEW
EXHAUST GAS BOILER
FUEL FEED SYSTEM
MISSION™ OL
STEAM DIAGRAM MISSION OL
STEAM WATER PI DIAGRAM
HOT WELL
FEED WATER PUMPS
BOILERS SYSTEM OVERVIEW
EXHAUST GAS BOILER
FUEL OIL SYSTEM
FO SYSTEM – PI DIAGRAM
KBSD
STEAM ATOMISING BURNER
STEAM ATOMISING BURNER KBSD
Air
inlet
Burner lance
Burner register
Secondary swirler
Igniter Primary swirler
Atomiser
STEAM ATOMISING BURNER WIND BOX
NEW TYPE
OLD TYPE
STEAM
OIL
STEAM ATOMISING BURNER
ATOMISING STEAM VERSUS OIL FLOW AND DURING LANCE PURGING
Steam Atomising
Burner
Atm. St.
Controller
7
6
Atm. Steam Press
OIL -
ATOM ISING
5
4 0
PRES
0%OIL-ATZ N BAR
3 3.0 0
10%OIL-ATZ N BAR
3 3 10 3.0 1.5
20%OIL-ATZ N BAR
3.5 20 3.5 2
30%OIL-ATZ N BAR
4 2 30 4.0 3
40%OIL-ATZ N BAR
5 40 5.0 4
50%OIL-ATZ N BAR
5.5 1 50 5.5 5
6 0 60 6.0 7
60%OIL-ATZ N BAR
70%OIL-ATZ N BAR
6.2 70 6.2 9
80%OIL-ATZ N BAR
6.2 0
80 10 6.2 20 30
12 40 50 60 70 80 90 100
6.2 90 6.2 15 Oil Flow
90%OIL-ATZ N BAR
100%OIL-ATZ N BAR
6.2 100 6.2 18
DIESEL OIL IGNITION BURNER
IGNITION BURNER ARRANGEMENT
Magnetic switch
Flame scanner
ignition burner
Hose for
combustion air
Air inlet
Ignition electrodes
4 mm
8-12 mm
Nozzle
Nozzle
10-12 mm
MISSION CONTROL SYSTEM
COMUNICATION - CONFIGURATION
COMUNICATION - CONFIGURATION
COMUNICATION - CONFIGURATION
WHAT IS THIS AND HOW DOES IT WORKS ?
WORKING PROGRAM
BASIC PROGRAM
WORKING DATA
FIRST POWER UP , DEFAULT DATA IS LOADED
OPERATION CONDITION , OPERATION DATA
OPERATION CONDITION , POWER DOWN
NOT ACTIVE
ACTIVE
OPERATION CONDITION , POWER ON AGAIN
Version
&
RAM
check
Version
&
RAM
check
COPY EEPROM?
•LOCAL PANEL 1
•LOCAL PANEL 2
•POWER PANEL 1
•POWER PANEL 2
•BURNER TYPE
• AND OTHERS
Basic Functions:
•Steam Pressure Controller
•Oil / Air Flow Controllers
•Atomising Steam Controller
•Water Level Control
•Oil Pressure (Ring Line) Controller
•Oil Temperature Controller
•Alarm & Shutdown Functions
Basic PID Controllers
Oil Flow
Calibration
Controlling the Steam Pressure
P X-mitter
on Boiler /
St. Line
Mst Stm
Controller
dp X-mitter
Windbox/
Flow Furnace
meter
Boiler / Steam Line
P X-Mitter
barg
6,5
SP 7
Steam Pressure
50
High Low
Selector Selector
50 48
Compare Compare
with other with other
values values
48 1
Air/Oil
SP 50 48 MV Ratio %Oil %Air MV 48 48 SP
0 0
Air Controller 48 10 13 Oil Controller
1 Auto 20 22 1 Auto
30 Hand 30 33 21 Hand
50 40 42 48
50 51
50 60 60 48
70 69
80 78
I/P 90 88 I/P
100 97
dp Flow
P X-Mitter
SP 7
Auto 1
19 Hand
50
High Low
Selector Selector
50 48
BURNER SYSTEM
OIL OK DIFF N% 2
Compare Compare AIR OK DIFF N% 2
with other with other MAN STEP N% 1
values values AIR OIL DIF N% 100 OK
MAX OIL OUT N% 30
REDUCED PRS N BAR 5
LOAD LIMIT N% 50
48 1
Air/Oil
SP 50 48 MV Ratio %Oil %Air MV 48 48 SP
0 0 START/STOP LIMITS
Air Controller 48 10 13 Oil Controller M.START DIF N BAR 0,2
1 Auto 20 22 1 Auto M.STOP DIFF N BAR 0,8
15 Hand 30 33 17 Hand MIN.FIRING POSITION
50 40 42 48 AIR POS. N% 16
50 51 OIL POS. N% 15
50 60 60 48 PURGE POSITION
70 69 AIR POS. N% 70
80 78 OIL POS. N% 15
I/P 90 88 I/P IGNITION POSITION
100 97 AIR POS. N% 18
dp Flow OIL POS. N% 15
RISING
1 AirOffset Air Flow Oil Flow OilOffset 1 WARM UP LIM N BAR 2
RISING DIFF N BAR 1
MOD.FR.DIFF N BAR 1
STEAM PURGE POSITION
AIR POS. N% 30
OIL POS. N% 30
STAND BY POSITION
AIR POS.
N% -20
OIL POS.
N% 20
Two Boiler System
Basic PID Controllers
Oil Flow
Mst Stm
Controller
dp X-mitter dp X-mitter
Windbox/ Windbox/
Flow Furnace Flow Furnace
meter meter
Boiler 1 Boiler 2
Two Boiler System / Control
Principle
Boiler / Steam Line
P X-Mitter
barg
SP 7
Auto 1
Parameters
19 Hand
50
High Low
Selector Selector
50 0
BURNER SYSTEM
OIL OK DIFF N% 2 OK
Compare Compare AIR OK DIFF N% 2
with other with other MAN STEP N% 1
values values AIR OIL DIF N% 100 OK
MAX OIL OUT N% 30
-20 20 REDUCED PRS N BAR 5
LOAD LIMIT N% 50
0 1
Air/Oil 0
SP -20 0 MV Ratio %Oil %Air MV 20 20 SP Step
0 0 START/STOP LIMITS
Air Controller 0 10 13 Oil Controller M.START DIF N BAR 0,2
1 Auto 20 22 1 Auto M.STOP DIFF N BAR 0,8
45 Hand 30 33 17 Hand 7 MIN.FIRING POSITION
-20 40 42 20 AIR POS. N% 16
50 51 OIL POS. N% 15
-20 -20 60 60 20 2 PURGE POSITION
70 69 AIR POS. N% 70
80 78 OIL POS. N% 15
I/P 90 88 I/P 3 IGNITION POSITION
100 97 (4-6) AIR POS. N% 16
dp Flow OIL POS. N% 18
RISING
1 AirOffset Air Flow Oil Flow OilOffset 1 WARM UP LIM N BAR 2
RISING DIFF N BAR 1
MOD.FR.DIFF N BAR 1
10 STEAM PURGE POSITION
(11-13) AIR POS. N% 30
OIL POS. N% 30
0 STAND BY POSITION
(1) AIR POS.
N% -20
OIL POS.
N% 20
Slave Boiler Condition
•Stopped / Cold
•Stopped / Heating Coil
•Burner in Auto => Pressure Maintenance
SETTINGS
START/STOP
LIM ITS
M .START DIF N BAR lo: 0 hi: 27 def: 0.3
•Manual operation
•Normal Auto load sharing
•Forced Inert Gas operation
(local/external)
Inert Gas
Operation
PC Remote
Control
Trend
curves &
Optimizing