Project: Fit-Out to Carrefour at Oasis Mall, Kampala, Uganda
1906-OASIS-MAR-ME 003 (Rev.001)-Water Treatment plant
1. Feed and Pressure Booster Pump models shown in the Schedule is Grundfos CM5-6
But in the Catalogue model marked is Grundfos CM5-4. Contractor to confirm the model.
2. Pressure Booster Pump set should be with VFDs for each pump. Pressure switches
accepted only for Feed Booster Pump.
3. Sediment and Carbon Cartridge Filters should be selected to ensure 1.5L/S flow as per
design. Contractor to confirm the same. Sediment Filter should be 3XWPP20, 20" and
Carbon filter should be 6XGAC20, 20" to ensure the required flow.
4. Submit detailed dimensional drawings for Booster Pump sets as a whole - 2 Pumps
with (1D+1S) and 100L Pressure Vessel.
5. Provide details of Pressure Vessel
6. Tank should bear pipe connections with flanges for make-up water, overflow, drain,
suction pipe to pumps, air-vent with insect screen, air-tight manholes and float valve in
make-up water line.
7. All equipments selection should be based on the required flow rate as per design.
8. Submit compliance statement to the above comments.
Approved As Noted
Jojo D'Cruz
29-08-2019