You are on page 1of 25

^/
13 SEP2019
CoxHewlett& BaileyWoodland RCA PROJECT OFR- - OMAA
Signature:.................
POBox7013CloistersSquareWA6850
360MurrayStreetPerthWA6000Australia
T + 61893223&M F + 61893221664 wwwcosw au

ARCHITECTSADVICE Advice Number: OAAM-AA-08152 1


Project Oman Across Ages Museum

Job 614020
number

Proprietor Royal Court Affairs


Contractor SPML- OSCO Joint Venture
File no.

Sheet 1 Of Date-29/09/2019

The Contractor shall comply with directions described withoutvariation to the Contract sum and without
adjustment to the time for Substantial Completion. Should the Contractor consider that compliance
with these directions involves a variation to the Contract Sum or an adjustmentto the time ofSubstantial
Completion of the works, he/she shall inform the Resident Engineer(RCA) and obtain written approval
before executing the work

SUBJECT MEP3-MS-GE-0004 Rev. O Method Statement for Installation of Fire Sealants on MEP Services

DOCUMENT REFERENCE- OAAM/SPOS/DT/MEP3/001526


REQUIRED BY DATE - N/A

^Narne David Kirwan Resident


Signed

^^^^(. /^C^.
Copies to - RCA, MIL

Cox Architecture Pty Ltd ACN 002 535 891


NominatedArchitects: Steve Woodland No. 1965, Sreg Hewlett No. 1029.

Page 1 f 1

T2)^K)^
^

^-P^ ^^r ^OMM^J^S


^-^O^^o}^
REFER TO THE COMMENTS ATTACHED.

PROVIDE THE DETAILS OF ROP APPROVAL / PRE QUALIFICATION FOR THE


APPLICATOR / THIRD PARTY INSTALLER, FOR THE REVIEW AND APPROVAL

PRASANTH

29/09/2019
DOCUMENT REVIEW SHEET
Project Name: Oman Museum Across Ages, Nizwa, Sultanate of Oman Project Number 1661
Doc Ref: 1661-TEN-OAAM-MST-007 Issue Date 28.09.2019

System: Fire & Life Safety System Document Reference: OAAM-MEP3-GE-0004 / R0

Category Method Statement for the Installation of Fire sealants on MEP services

Reviewed By: Yuvaraj M Approved By: Ikhwan Razali


Sr. Fire Engineer Principal Fire Engineer

Review Findings

Tenable Fire Engineering had reviewed the MST (refer category) and our observations are as follows:

a) MST approved, please follow below


b) Ensure and maintain Firestop Log/register
c) Follow approved Mockups, for label or Marking

Required Action

Review Status
☐ Approved ☒ Approved with Comments ☐ Not Approved

☐ Attachments

Issued by:

Yuvaraj M
Sr. Fire Engineer
P.O Box 250, PC 118, Muscat, Sultanate of Oman; T: +968 24693056, F: +968 24693057, E: info@tenablefec.com, www.tenablefec.com
CONTRACTOR DOCUMENT REVIEW
(B) NO EXCEPTION TAKEN.
(A) NO EXCEPTION TAKEN. COMPLY WITH COMMENTS.
WORK MAY PROCEED.
(C) NO EXCEPTION TAKEN
EXCEPT CLOUDED AREAS. (D) REVISE AND RESUBMIT.
RESUBMIT CLOUDED AREAS. WORK NOT TO PROCEED.

Aurecon Australasia Pty Ltd


ABN 54 005 139 873
BY: PRASANTH
Azhar.Uddin
DATE: 25/09/2019
21/8/2017
PROJECT No: 247055
DATE RECEIVED: 02/09/2019
This review is only for general conformance with the
design concept of the project and general compliance
with the information given in the contract documents.
Any action shown is subject to the requirements of
the contract documents. This review does not relieve
the Contractor of their Contractual obligations nor of
their responsibilities of ensuring the work is complete,
accurate and correct. Any amendment does not
constitute an order of authority for a price variation to
the contract.
PROVIDE DETAILS