Professional Documents
Culture Documents
REVISION HISTORY
Rev. Description ERO/ECN #
A Initial Release 041251
B Added Revision History page and drawing number in footer. Revised figures 1-10, 1- C23375
13, and 1-14. Formatting corrections.
C Corrected text and figure item callouts items in figures 1-4, 1-5, and 1-6. C24068
D Make formatting correction. C24394
E Remove references to ARH and Ansaldo Ross Hill on pages 1-1, 1-2, and 1-25. C24670
F Update figures. C25368
G Update (2) photos (Figure 1-5, Figure 1-9); add photo numbers; update figure number C25939
style.
H Revise Figure 1-1 to reduce printing time and printer memory problems. C26330
J Convert to Word 97 format. C28670
K Add Table of Contents codes. Correct Level 5 and Level 6 styles and errors. C29222
• Generator Units for control of engine- Engine Governor 0.5 Hz steady-state regulation
with one Second response time
generator sets. at 5% load unbalance of rated
• SCR Units for AC to DC rectification for load
traction motor power and control. Generator Voltage Regulator
• Transformer Feeder Unit - AC feeder ±3% regulation one second
response time with ±10% load
breakers to feed step-down unbalance of rated KVAR's
transformers that deliver low voltage
power for AC auxiliaries such as motor DC Output Zero to 750 VDC at zero through
maximum current
blowers, water pumping, lighting and
living accommodations. Current Rating (Continuous Duty)
SCR bridge output is usually
• DW Dynamic Brake - electrical zero to 1,800 ADC (this can vary
resistance or regenerative brake for depending on model).
Drawworks motors.
MECHANICAL
• Field Supply Unit for DC field supply to
shunt wound, separately excited DC Temperature Range -22°F to 105°F
traction motors. (-30°C to 40°C)
• Driller's Console for control of all drilling Cubicle Construction Fabricated from 12 gauge
functions from the drill floor. cold-rolled steel with welded
construction and expanded
• Mud Pump/Cement Pump Console for metal ventilation openings.
local control of the pumps during The cubicle bus is solid
copper with a 0.0005 Inch
maintenance. (0.0013 cM) electroplating of
• Motor Control Center containing starters silver.
for AC auxiliary motors and feeder Console Construction Fabricated from 12-gauge
breakers for lighting panels and smaller #304 stainless steel plate
distribution transformers. with welded construction.
SPECIFICATIONS (CONCLUDED)
OPERATING PROCEDURE
FOR GENERATOR SYSTEM SYNCHRONIZING GENERATORS
MODELS 1201 THROUGH 1650
TO BRING AN ADDITIONAL
During the following procedures, GENERATOR ON LINE
refer to Figures 1-3 through 1-6.
1. (Models 1200, 1201, 1500) Turn the
STARTING AN ENGINE SYNCHRONIZING switch (Item 9 on
Figure 1-3, Item 11 on Figure 1-4) to
1. Place the ENGINE CONTROL SYNC.
switch to IDLE. OR
2. Start the engine and run it at idle 1. (Model 1400) Turn the
speed until it is warmed up. SYNCRONIZING switch (Item 15 on
Figure 1-5) to the number of
3. Place the ENGINE CONTROL
generator about to be brought on
switch to RUN.
line.
OR
1. (Model 1600) turn the
BRINGING THE FIRST SYNCHRONIZING SWITCH (Item
GENERATOR ON LINE 20 on Figure 1-6) to AUTO.
2. Position the VOLTS ADJUST knob
1. Turn the SYNC switch to the number (Item 13 on Figure 1-3 and 1-4, Item
of generator about to be brought on 10 on Figure 1-5, Item 17 on Figure
line. The PUSH TO CLOSE 1-6) so the AC VOLTMETER (Item 5
pushbutton on the appropriate on Figures 1-3 and 1-4, Item 18 on
generator cubicle door should Figure 1-5, Item 7 on Figure 1-6)
illuminate. indicates 600 Volts.
2. Set the SPEED ADJUST control
knob so the FREQUENCY meter
indicates 60 Hz.
20600-09 Rev. A
Item Description
1. GEN Circuit Breaker
2. AC Kilowatts Meter
3. AC Kilovars Meter
4. AC Ammeter
5. AC Voltmeter
6. Generator Run Light
7. Generator On Line Light
8. Engine Control Switch
9. Synchronizing Switch
10. Ammeter Select Switch
11. Voltmeter Select Switch
12. Speed Adjust Knob
13. Volts Adjust Knob
14. % AC Ground Ammeter
15. % DC Ground Ammeter
16. Ground Fault Indicator Lamps
17. Ground Detector Test Button
18. Power Limit Light
19. Hertz (Frequency) Meter
20. Synchroscope
21. Synchronizing Lights
Figure 1-3. Controls and Indicators for Models 1200 and 1500
Item Description
1. GEN Circuit Breaker
2. AC Kilowatts Meter
3. AC Ammeter
4. AC Kilovars Meter
5. AC Voltmeter
6. Generator Run Light
7. Generator On Line Light
8. Ammeter Select Switch
9. Voltmeter Select Switch
10. Engine Control Switch
11. Synchronizing Switch
12. Speed Adjust Knob
13. Volts Adjust Knob
14. % AC Ground Ammeter
15. % DC Ground Ammeter
16. Ground Fault Indicator Lights
17. Ground Detector Test Push Button
18. Power Limit Light
19. Synchronizing Lights
20. Synchroscope
21. Hertz (Frequency) Meter
Item Description
1. GEN Circuit Breaker
2. AC Kilowatts Meter
3. Kilovars Meter
4. AC Ammeter
5. Engine Control Run/Off/Idle Switch
6. GEN Run Light
7. GEN On Line Light
8. Push to Close Lighted Pushbutton
9. Speed Adjust Knob
10. Volts Adjust Knob
11. % AC Ground Fault
12. % DC Ground Fault
13. Ground Fault Indicator Lights
14. Ground Detector Test Push Button
15. Generator Synchronization
Select Switch
16. Frequency (Hertz) Meter
17. Synchroscope
18. AC Voltmeter
19. Synchronizing Lights
20. Power Limit Light
21. Hour Meter
4. Crank the handle of the GEN 2. Charge the circuit breaker (if
CIRCUIT BREAKER (Item 1 on necessary), by pushing the
Figures 1-3, 1-4, and 1-5, Item 24 on CHARGE pushbutton (for
Figure 1-6) once to charge the GEN electrically-charged circuit breakers)
CIRCUIT BREAKER. (refer to Figures 1-3 through 1-6) or
5. Close the GEN CIRCUIT BREAKER by cranking the circuit breaker
when the needle of the handle (for manually-charged circuit
SYNCROSCOPE points straight up, breakers). Some systems have
the SYNCHRONIZING LIGHTS go molded-case circuit breakers. These
out, and the PUSH TO CLOSE do not require charging.
pushbutton on the GEN CIRCUIT 3. Close the SCR circuit breaker by
BREAKER is illuminated. pushing the PUSH TO CLOSE
6. Position the VOLTAGE ADJUST pushbutton (this may be mounted
knob so the KVAR meter gives the remotely or directly on the circuit
same reading as the other breaker). Crank the circuit breaker
generator(s) on line. handle once to close molded-case
7. Turn the SYNCHRONIZING circuit breakers.
SWITCH to the OFF position.
KW SHARING
A master/slave circuit automatically
balances the Kilowatts (Horsepower)
among all on-line engines (the load is
shared equally).
AC ground faults can occur anywhere along Figure 1-7 shows an SCR bridge Current
the AC power network (generator to AC bus versus Voltage response curve. Figure 1-8
cables, feeder distribution to the AC motors, shows DC series and shunt motors Speed
and the generator control bus in the cubicle versus Torque curves. These are for a
itself). The GROUND DETECTOR lights specific brand and model motor. Other
will isolate the fault to one of the phases, brands and models will be different.
and the % AC GROUND meter will indicate
the degree of the fault.
20600-91 Rev. A
20600-92 Rev. A
FS-201-01
weatherproof plug panels (see Figure 1-10). Figure 1-10. Plug Panel of One SCR
House
Ventilation and Ducting Push the cubicle carefully into the location,
jack down, and remove the trolley
The room air must be changed twice per horizontal forks.
minute when the cubicles are enclosed in a
room. Ducting in the front and rear of the Mounting
room should force the air to flow the full
length of room. Butt the sides of the cubicles tightly
together.
Heat Loss
Bolt the cubicles together at the top and
Heat loss for a SCR system housed in a bottom using 3/8" bolts.
room fully insulated on walls, floor and Install the AC bus splices to connect the
ceiling, and containing no distribution bus together from cubicle to cubicle.
transformers, is approximately 2.5 tons for
each 1,000 HP of DC load. Cable Installation
Vibration Pads Refer to the cabling diagrams in the SCR
job book. Cables between the cubicles are
If the cubicles are mounted in a high furnished by the customer unless the SCR
vibration area, such as the region close to drive system is installed in a Power Control
the engine skid, the cubicles should be Building.
mounted on vibration insulating pads. The
vibration frequency should be within 30 Hz, All power terminations are made through
and the amplitude should not exceed 0.02 the cubicle top unless otherwise designed.
cM. Korfund spring-type vibration isolators
are recommended. If the SCR system is supplied inside a
Power Control Building, power and control
Location cable terminations are at one end of the
building.
Lift the cubicle with a crane into the general
The terminations are copper stubs with an
installation area. Use four lifting points per
one inch diameter bolt hole. The customer
cubicle. Refer to Figures 1-11 and 1-12 for
should furnish plated-copper, crimp-type
the lifting procedure.
lugs. Avoid screw-type pressure
connectors.
1. Check lights and meters on cubicles The system components are vulnerable to
and control consoles. three factors: inferior quality, harsh
2. Check Ground Detector indicators. operation and severe environment.
All three lamps should glow a dim
orange. The Ground Fault QUALITY
Percentage meters should read
close to Zero. Efforts to eliminate this source of failure are
3. Check field current supply of all made at our manufacturing and testing
shunt motors. facility. The system is rigorously tested
through every phase of operation. The
4. Ensure that KW's and KVAR's are
electronic modules are placed in ovens at
shared between all the generators
165°F (75°C) for 96 hours to simulate
on line.
numerous hours of operation at normal
5. During tripping, listen for switching temperature. Thus, components which are
action of the DW Dynamic Brake likely to fail during the first hours of
contactor. operation are replaced before shipment.
6. Ensure that all SCR blowers are
running. HARSH OPERATION
It consists of first looking at the broad Warning lights on the cubicle panels flag
possibilities of failure, and then breaking ground faults, AC surge, sprocket slip, and
down the likely possibility into successively reverse power conditions. Operational
smaller trouble spots. lights indicate whether a SCR or a
Generator is on the bus. Even voltmeters
Examine the whole system as it is situated and ammeters provide valuable
between the generators and the loads. troubleshooting information. For example,
Then narrow the search to a cubicle or a stalled motor is indicated by high current,
console, then to an internal assembly, and and low voltage. Low current and high
finally to a component. The malfunction voltage is an indication of an unloaded
can be quickly located by seeking out signs motor.
of trouble, such as extreme readings on the
meters, tripped circuit breakers, and SYSTEMS ANALYSIS
smoking components.
Think of the system as being made up of
A step-by-step troubleshooting approach interrelated blocks or units. Ignore the
should consist of the following items: contents of the unit, and simply consider
malfunction analysis, analysis of front panel the inputs and outputs. Refer to Figure 1-
indicators, systems analysis, and signal 15.
tracing.
DRILLER'S GENERATOR
CONSOLE
MALFUNCTION ANALYSIS
SCR BRIDGE
on the lockout switch, open the throttle, and
assume that the SCR unit is defective. 0 - 750 VDC SUPPLY
POWER
The faulty behavior of a motor or generator CONTROL
sure the fault is not outside the system Figure 1-15. System Block Diagram
before making extensive repairs such as
replacing a SCR cell.
The defective unit can be easily located by Signal tracing should continue back toward
tracing signals associated with the the Generator until the defective component
malfunction. is located. In extremely long series circuits,
it may be convenient to divide the circuit in
half. Begin the probe in the middle. If the
signal is missing, trace back toward the
generator until the signal is regained. If the
signal is present, trace away from the
generator until the signal is lost.
GENERATOR 1 CIRCUIT SCR 1 CONTACTOR
BREAKER
20601-08 Rev. A
MULTIMETER OSCILLOSCOPE
The Simpson Model 250 (or equivalent) is The oscilloscope is used to check the SCR
recommended to measure voltage and gate pulses and ripple on various DC
resistance values. The meter should be voltages. The Tektronix Model 305 (or
insulated, rugged and possess: equivalent) is recommended. The unit
chosen should have >3 Inch diagonal
DC/AC Volts:Zero through 1,000 Volts in viewing screen and two channels for
several ranges. comparing two signals.
Accuracy: 3% of full scale.
Ohms: Zero through 10 MΩ in
several ranges.
Accuracy: 2% of arc length.
CUBICLE REPAIR
AC CONTROL MODULE
FS-047-05
6. Reconnect the wiring harness by
FS-066-05
replacing each wire on the terminal
4. During new module installation, ensure board. Ensure that each wire is correctly
you match the wire number to pin placed and that the retaining screw is
number. tightened.
FS-066-03 FS-047-02
5. Reconnect the module to the cubicle 7. Swing the cover closed and fasten it in
wall with the four Deutsch fasteners. place with the Deutsch fastener on top.